background image

Page  25

31-5000731   Rev. 0

Typical Operating Characteristics

Blower Operation and Adjustment

NOTE: 

The following is a generalized procedure and does 

not apply to all thermostat controls.

1. 

Blower operation is dependent on thermostat control 

system.

2. 

Generally,  blower  operation  is  set  at  thermostat 

subbase  fan  switch.  With  fan  switch  in  ON  position, 

blower  operates  continuously.  With  fan  switch  in 

AUTO  position,  blower  cycles  with  demand  or  runs 

continuously while heating or cooling circuit cycles.

3. 

Depending  on  the  type  of  indoor  thermostat,  blower 

and entire unit will be off when the system switch is in 

OFF position.

Temperature Rise

Temperature rise for NF80UV units depends on unit input, 

blower speed, blower horsepower and static pressure as 

marked on the unit rating plate. The blower speed must be 

set for unit operation within the range of “TEMP. RISE °F” 

listed on the unit rating plate.

Supply Air

Return Air

Supply Duct Temperature

Return Duct Temperature 

_

Temperature Rise  =

Figure 23. Temperature Rise

External Static Pressure

1. 

Tap locations shown in Figure 24.

2. 

Punch  a  1/4”  diameter  hole  in  supply  and  return  air 

plenums.  Insert  manometer  hose  flush  with  inside 

edge of hole or insulation. Seal around the hose with 

permagum. Connect the zero end of the manometer to 

the discharge (supply) side of the system. On ducted 

systems, connect the other end of manometer to the 

return duct as above.

3. 

 With only the blower motor running and the evaporator 

coil dry, observe the manometer reading. Adjust blower 

motor speed to deliver the air desired according to the 

job  requirements.  For  heating  speed  external  static 

pressure drop must not be more than 0.5” W.C. For 

cooling speed external static pressure drop must not 

be more than 0.8” W.C.

4. 

Seal the hole when the check is complete.

Supply Duct Static

Return Duct 

Total Duct Static  = 

(dry coil)

Supply Air

Return Air

-

+

or

High

Low

Figure 24. External Static Pressure

Содержание GE NF80UV

Страница 1: ...31 5000731 Rev 0 11 22 GEA NF80UV 80 Upflow Horizontal Two Stage Variable Speed Gas Furnace Service Manual READ CAREFULLY KEEP THESE INSTRUCTIONS...

Страница 2: ...l injury or death Electric shock hazard Can cause injury or death Before attempting to perform any service or maintenance turn the electrical power to unit OFF at disconnect switch es Unit may have mu...

Страница 3: ...SICAL AND ELECTRICAL DATA Model Input Btuh Output Btuh AFUE ICS Nominal Cooling Capacity Gas Inlet in Volts Hz Phase Max Time Delay Breaker or Fuse Nominal F L A Trans V A Approx Shipping Weight lbs U...

Страница 4: ...orm 1977 1773 1759 1405 Norm 2015 1710 1560 1400 1779 1596 1583 1265 1810 1555 1395 1260 Low Fire 25 55 1977 1783 1497 1431 1st Stage 1560 1355 1230 1065 Norm 1797 1621 1361 1301 Norm 1425 1205 1085 9...

Страница 5: ...iption Natural to LP Kits 11K48 Two Stage 0 7500 ft 11K47 Two Stage 7500 ft Return Air Base 68W61 14 5 Inch A Width 68W62 17 5 Inch B Width 68W63 21 0 Inch C Width Note For vent length and clearances...

Страница 6: ...3 8 137 Right 1 9 16 40 Left 33 838 3 1 8 79 1 15 16 49 14 356 9 16 14 3 76 Right 6 3 4 171 Left 2 FLUE OUTLET Either Side 3 OPTIONAL EXTERNAL SIDE RETURN AIR FILTER KIT Either Side 16 406 14 3 4 375...

Страница 7: ...Figure 1 Expanded View HEAT EXCHANGER CABINET COMBUSTION AIR INDUCER BLOWER ASSEMBLY BURNER BOX ACCESS PANELS COMBUSTION AIR INDUCER PRESSURE SWITCH GAS VALVE CONTROL BOX Includes two stage integrate...

Страница 8: ...ignition and ignitor durability The control provides gas ignition safety checks and indoor blower control with two stage gas heating The furnace combustion air inducer gas valve and indoor blower are...

Страница 9: ...100 CFM count the flashes and multiply by 100 to determine the actual CFM delivered for example 5 flashes x 100 500 CFM Pin Function 1 Gas Valve Second Stage 2 Second Stage Prove Switch 3 Rollout Swit...

Страница 10: ...Humidifier 120VAC Line Input 120VAC XFMR Transformer 120VAC EAC Indoor Air Accessory 120VAC Cool Cool Speed 120VAC Park 1 Dead terminal for alternate speed tap Park 2 Dead terminal for alternate spee...

Страница 11: ...e bearings MOTOR CONTROLLER J49 J48 Figure 5 GenTeq Blower Motor B3 STATOR WINDINGS OUTPUT SHAFT BEARING ROTOR Figure 6 Blower Motor Components Internal Operation Each time the controller switches a s...

Страница 12: ...e motor Jack J48 is the power plug Line voltage must be applied to J48 pins 4 and 5 in order for the motor to operate When using 120VAC pins 1 and 2 must be jumpered Jack J49 connects the unit control...

Страница 13: ...AT output from controller to motor windings O volts 325VDC One revolution O volts 325VDC O volts 325VDC WINDING 1 WINDING 2 WINDING 3 O volts 325VDC O volts 325VDC O volts 325VDC WINDING 1 WINDING 2 W...

Страница 14: ...Heat Call Figure 10 Indoor Blower Operation High Heat W2 Call Figure 11 Indoor Blower Operation Call for Fan Percentage of High Stage Cooling Figure 12 Indoor Blower Operation Single Stage Cooling Fi...

Страница 15: ...ee Figure 14 The limit is a N C SPST manual reset limit When S47 senses rollout the circuit breaks and the ignition control immediately stops ignition and closes the gas valve Rollout can be caused by...

Страница 16: ...Page 16 31 5000731 Rev 0 Gaskets Collector Box Orifice Plate Flue Transition Pressure Switch Combustion Air Inducer Manifold And Gas Valve Ignitor Sensor Rollout Switches Figure 14 Heating Components...

Страница 17: ...nd Connect Alligator Clip to Flame Sensor Lead Flame Sensor Terminal Remove Sensor Wire from Integrated Control and Connect Alligator Clip to Terminal on Control DIGITAL METER To Control Sensor Termin...

Страница 18: ...r probes in order not to damage plug Check voltage during 20 second ignitor warm up period Voltage should read 120 volts 10 If voltage reads below these values check for correct supply voltage to furn...

Страница 19: ...combustion air inducer is operating It closes a circuit to the integrated control when pressure inside the combustion air inducer decreases to a certain set point Set points vary depending on unit siz...

Страница 20: ...nducer then reinstall the mounting screws See unit Installation Instructions for more detail The combustion air pressure switch must be moved for horizontal discharge air left position IMPORTANT vent...

Страница 21: ...nd to move the switch Never use tools If the switch will not turn or if the control switch will not move by hand do not try to repair it Placing the Furnace into Operation These units are equipped wit...

Страница 22: ...lock out If the unit locks out again call the service technician to inspect the unit for blockages 10 Is pressure switch closed Obstructed flue will cause unit to shut off at pressure switch Check fl...

Страница 23: ...Table 9 for manifold pressures and Table 10 for pressure switch and gas conversion kits Capacity Gas Orifice Size 0 7500 ft 1 Orifice Size 7501 10000 ft Manifold Pressure in w g 0 4500 ft Manifold Pr...

Страница 24: ...load indicates a poor or partial ground Compare the readings to Table 11 If the readings exceed the maximum shown in Table 11 make repairs before operating the furnace 2 In addition measure the AC vol...

Страница 25: ...F listed on the unit rating plate Supply Air Return Air Supply Duct Temperature Return Duct Temperature _ Temperature Rise Figure 23 Temperature Rise External Static Pressure 1 Tap locations shown in...

Страница 26: ...ssary 8 Evaluate the heat exchanger integrity by inspecting the heat exchanger per the AHRI heat exchanger inspection procedure This procedure can be viewed at www ahrinet org 9 Ensure sufficient comb...

Страница 27: ...acuum cleaner with a soft brush attachment over the face of burners Visually inspect inside the burners and crossovers for any blockage caused by foreign matter Remove any blockage Figure 26 shows bur...

Страница 28: ...Collector Box Orifice Plate Flue Transition Pressure Switch Combustion Air Inducer Manifold And Gas Valve Retention Rings Cross Over Ignitor Flame Sensor Rollout Switches Figure 26 Burner Combustion A...

Страница 29: ...TRAL TAP TO NEUTRAL TERMINAL ON IGNITION CONTROL 5 DO NOT CONNECT C COMMON CONNECTION BETWEEN INDOOR UNIT AND THERMOSTAT EXCEPT WHEN REQUIRED BY THE INDOOR THERMOSTAT REFER TO THE THERMOSTAT INSTALLAT...

Страница 30: ...Page 30 31 5000731 Rev 0 Figure 28 Wiring Schematic...

Страница 31: ...ains energized until the limits are closed Fan On When the thermostat is set for continuous fan operation and there is no demand for heating or cooling a call for fan closes the R to G circuit and the...

Страница 32: ...Printed in the U S A All specifications and illustrations subject to change without notice and without incurring obligations...

Отзывы: