75
Technical Data
This thermostatic valve will suit supplies of:
HIGH PRESSURE (HP-S)
Operating pressure:
max. 10 bar
Recommended operating pressure:
1 - 5 bar
Test pressure:
16 bar
Hot water temperature:
max. 80°C
Recommended hot water temp.:
65°C
Rate of flow:
58 l/min. @ 3 bar
Maximum outlet temperature:
43°C +/-*
Safety check:
40°C
Hot water connection:
Left hand
Cold water connection:
Right hand
Minimum difference between hot
water and mixed water temperature:
6 K
Hot and cold supply pressure should be balanced
Mixed water temperature
Application
Mixed water temperature
(at point of discharge).
Shower
41°C max.
Washbasin
41°C max.
Bath (44°C fill)
44°C max.
Bath (46°C fill)
46°C max.
* For preset outlet temperature adjustment – See page 63.
NB.
If a water supply is fed by gravity then the supply
pressure should be verified to ensure the conditions of use
are appropriate for the valve. Valves operating outside of
these supply conditions cannot be guaranteed to operate
as a TMV2 or TMV3 valve.
Recommended outlet temperatures
The BuildCert TMV scheme recommends the following
set maximum mixed water outlet temperatures for use in
all premises:
44°C for bath fill but see notes below;
41°C for showers;
41°C for washbasins.
The mixed water temperatures must never exceed 46°C.
The maximum mixed water temperature can be 2°C above
the recommended maximum set outlet temperatures.
Note:
46°C is the maximum mixed water temperature
from the bath tap. The maximum temperature takes account
of the allowable temperature tolerances inherent in thermo-
static mixing valves and temperature losses in metal baths.
It is not a safe bathing temperature for adults or children.
The British Burns Association recommends 37 to 37.5°C as
a comfortable bathing temperature for children. In premises
covered by the Care Standards Act 2000, the maximum
mixed water outlet temperature is 43°C
Installation Requirements
This thermostatic mixer valve must be installed in comp-
liance with current Water Regulations. If you have any
doubts about the Water Regulation requirements contact
your local water services provider or use the services of
a professional plumber.
This mixer valve is suitable for use with the following water
supply systems:
Gas Combination Boiler (multi-point) 1.0 - 10 bar*
Unvented System (pressure balanced) 1.0 - 10 bar
Pumped System 1.0 - 10 bar
IMPORTANT:
If you install this mixer with a gravity fed
system, there must be a minimum head (vertical distance)
from the underside of tlie cold water storage tank to the
showerhead position of at least 5 metre.
Before connecting the mixer, water should be flushed
through the system to remove all debris that might otherwise
damage the valve.
* If pressure is in excess of 3.5 bar, a pressure-reducing
valve should be fitted.
Supply Conditions TMV2
Operating pressure range
High pressure
Maximum static pressure - bar
10
Flow pressure, hot and cold - bar
0.5 to 5
Hot supply temperature - °C
55 to 65
Cold supply temperature - °C
5 to 25
Содержание AXOR STARck 10715000
Страница 24: ...1 MPa 0 1 0 5 MPa 1 6 MPa 1 MPa 10 bar 147 PSI 80 C 65 C 70 C 4 65 DIN EN 1717 63 63 42 67 68 68 0 3 MPa 24...
Страница 25: ...80 69 XXX 000 090 820 MTC A 42 C 65 C 180 180 60 25...
Страница 27: ...80 69 XXX 000 090 820 brushed nickel A 42 65 180 60 27...
Страница 43: ...80 69 XXX 000 090 820 A 42 C 65 C 180 180 60 43...
Страница 55: ...80 69 XXX 000 090 820 A 42 C 65 C 180 180 60 55...
Страница 58: ...80 69 XXX 000 090 820 A 42 65 180 180 60 58...
Страница 59: ...1 0 5 0 1 1 6 PSI 147 10 1 80 C 65 C 4 70 C 65 DIN EN 1717 DIN 1988 63 63 42 67 68 68 0 3 59...
Страница 60: ...60 2 3 1 X 1 2 mm Montage SW 4 mm 5 Nm 2 5 6 2 4 X 11 3 2 3 1 1 2 01800180 1...
Страница 64: ...64 Safety Function 2 3 2 1 1 SW 3 mm SW 3 mm z B 42 C for example 42 C 2 1 1 2 3 4 5 6 8a 8b 7 SW 2 mm 2 Nm...