MINIMUM - MAXIMUM OPERATING CONDITIONS

ALL MODELS

Min.-Max. Inlet Air Pressure (compressed air at inlet to dryer)

43.5 - 232 psig (3 - 16 barg)

Min.-Max. Inlet Air Temperature (compressed air at inlet to dryer)

39°F - 122°F (4°C - 50°C)

Min.-Max. Ambient Temperature

36°F - 113°F (2°C - 45°C)

REFRIGERANT PRESSURE SWITCH SETTINGS

Refrigerant Compressor Control

High Pressure Switch Setting

Model

Refrigerant

Cut-Out

psig (barg)

Cut-In

(psig)

FLX 1.1
FLX 1.2

FLX2.1-4

R-134a

304 psig

(21 barg)

Manual

Reset

FLX 1.5-1

FLX 1.5
FLX 2.1
FLX 3.1
FLX 4.1
FLX 4.5
FLX 5.5

R-407c

406 psig

(28 barg)

Manual

Reset

CORRECTION FACTORS (MULTIPLIERS)

Air Inlet Temperature

°F (°C)

Multiplier

Air Inlet Pressure

psig (barg)

Multiplier

Ambient Air Temperature

°F (°C)

Multiplier

80°F (27°C)
90°F (32°C)

100°F (38°C)
110°F (43°C)
120°F (49°C)

1.46
1.23
1.00
0.82
0.68

75 psig  (5.2 bar)

100 psig  (6.9 bar)
120 psig  (8.3 bar)

150 psig  (10.3 bar)
225 psig  (15.5 bar)

0.86
1.00
1.04
1.09
1.15

80°F (27°C)
90°F (32°C)

100°F (38°C)
110°F (43°C)
120°F (49°C)

1.12
1.06
1.00
0.83
0.68

Содержание SPX Flow FLEX Series

Страница 1: ...rs Models FLX 1 1 FLX 1 2 FLX 1 5 1 FLX 1 5 FLX 2 1 FLX 2 1 4 FLX 3 1 FLX 4 1 FLX 4 5 FLX 5 5 FOR M NO 7440062 R EVI S ION 09 2018 R EAD AN D U N D E R STAN D TH I S MAN UAL PR IOR TO OPE RATI NG OR S E RVICI NG TH I S PROD UCT I N STR UCTION MAN UAL ...

Страница 2: ...LX 1 2 11 Models FLX 1 5 1 FLX 1 5 FLX 2 1 FLX 2 1 4 12 Models FLX 3 1 FLX 4 1 13 Models FLX 4 5 FLX 5 5 14 Electrical Schematic Models FLX 1 1 FLX 1 2 115V 1PH 60Hz 15 Models FLX 1 5 1 115V 1Ph 60Hz 16 Models FLX 1 5 FLX 2 1 FLX 4 1 230V 1Ph 60Hz 17 Models FLX 2 1 4 FLX 3 1 FLX 4 5 FLX 5 5 460V 3Ph 60Hz 18 Air and Refrigerant Flow Schematic 19 REPLACEMENT PARTS 20 21 MAINTENANCE KITS 22 NOTES 23 ...

Страница 3: ...ions 2 Compressed air and electricity have the potential to cause personal injury or equipment damage Before doing any work on the dryer be sure the electrical supply has been locked and tagged and the internal pressure of the dryer has been vented to the atmosphere 3 Do not operate the dryer at pressures or temperatures above the maximum conditions shown on the data plate 4 Always supply electric...

Страница 4: ...on the dryer data plate and must be in accor dance with applicable codes Support all piping do not allow the weight of any piping to stress the dryer or filters Inlet and outlet shutoff valves and bypass valves are recommended Pip ing should be at least the size of the inlet and outlet connections to minimize pressure drop in the air system See Specification Table for dryer inlet and outlet connec...

Страница 5: ... cooled by outgoing cold air The inlet air is further cooled in the refrigeration chiller The condensate is removed from the air stream by an electronic drain valve The cold dry air is reheated by incoming warm air as it passes back through the air to air heat exchanger Using the outgo ing air to pre cool the inlet air condenses up to 65 percent of the moisture out of the inlet air before it reach...

Страница 6: ... Allow the dryer to run 15 minutes Confirm that the tem perature indicators are in the green zone 3 SLOWLY open the dryer outlet valves permitting flow through the dryer 4 Confirm that condensate is discharging from the drain valve by pressing the Push to Test button 5 Confirm that the inlet air temperature pressure and airflow to the dryer meet the specified requirements see Engi neering Data sec...

Страница 7: ... or other reasons use the following procedure 1 Turn off the power switch 2 Disconnect the main power supply 3 Lock out and tag the power supply in accordance with OSHA requirements If mechanical repairs are to be made or service is performed vent the internal pressure of the dryer to atmospheric pressure Restart the dryer according to the start up instructions Disconnect power supply and depressu...

Страница 8: ...least once daily See the Field Service Guide for remedies to drain valve malfunctions Monthly Maintenance It is recommended to inspect the condenser coils monthly If necessary remove dirt or other particles with compressed air from an OSHA approved air nozzle that limits its discharge pressure to 30 psig 2 1 kgf cm2 Yearly Maintenance It is recommended to replace the drain service unit annually Fo...

Страница 9: ...e The dew point level is red on LCD window Inlet air temperature too high Reduce aftercooler discharge temperature to design conditions See Engineering Data Tables Excessive airflow Check airflow and system capacity Reduce airflow or resize and replace system Condenser fouled or clogged Clean or replace condenser Fan motor inoperative Replace fan motor High ambient temperature Ventilate area See E...

Страница 10: ... 19 4 493 43 7 1 111 335 152 FLX 4 5 450 NPT 2 40 6 1 032 19 5 494 49 3 1 253 366 166 FLX 5 5 550 NPT 2 40 6 1 032 19 5 494 49 3 1 253 396 180 1 Rated Flow Capacity Conditions for rating dryers are in accordance with ISO 7183 Option A2 Compressed air at dryer inlet 100 psig 6 9 barg and 100 F 38 C ambient air temperature 100 F 38 C operating on 60 Hz power supply 2 Refer to dryer data plate for re...

Страница 11: ...ut Out psig barg Cut In psig FLX 1 1 FLX 1 2 FLX2 1 4 R 134a 304 psig 21 barg Manual Reset FLX 1 5 1 FLX 1 5 FLX 2 1 FLX 3 1 FLX 4 1 FLX 4 5 FLX 5 5 R 407c 406 psig 28 barg Manual Reset CORRECTION FACTORS MULTIPLIERS Air Inlet Temperature F C Multiplier Air Inlet Pressure psig barg Multiplier Ambient Air Temperature F C Multiplier 80 F 27 C 90 F 32 C 100 F 38 C 110 F 43 C 120 F 49 C 1 46 1 23 1 00...

Страница 12: ... H I J K FLX 1 1 4 69 119 4 97 126 2 8 41 213 5 19 20 487 7 14 27 362 4 29 58 751 2 12 75 324 23 72 602 5 3 39 86 2 15 40 391 2 22 14 562 4 1 NPT 120 54 5 DRIED AIR OUTLET WETTED AIR INLET AIR FLOW COOLING C D E F G MAIN POWER CABLE A B 4 Ø10 MOUNTING HOLES DRAIN OUTLET FOOT PRINT FRONT VIEW REAR VIEW RIGHT SIDE VIEW TOP VIEW H J K I ...

Страница 13: ...D E F G H I J K FLX 1 2 3 41 86 5 4 97 126 2 6 77 172 19 25 489 2 14 29 363 28 711 2 12 76 324 30 76 781 3 5 56 141 2 19 29 490 29 18 741 2 1 NPT 147 66 5 AIR FLOW COOLING DRIED AIR OUTLET WETTED AIR INLET F E C D A B 5 Ø10 MOUNTING HOLES G DRAIN OUTLET POWER CORD FOOT PRINT FRONT VIEW REAR VIEW RIGHT SIDE VIEW TOP VIEW J K I H ...

Страница 14: ... 2 17 44 443 29 97 761 2 15 91 404 35 50 901 3 3 39 86 2 27 16 690 33 91 861 2 2 NPT 188 5 85 5 FLX 2 1 4 86 123 5 7 86 199 6 3 63 92 24 38 619 2 17 44 443 29 97 761 2 15 91 404 37 85 961 3 3 39 86 2 29 53 750 36 27 921 2 2 NPT 217 98 5 FLX 2 1 4 4 86 123 5 7 86 199 6 3 63 92 24 38 619 2 17 44 443 29 97 761 2 15 91 404 37 85 961 3 3 39 86 2 29 53 750 36 27 921 2 2 NPT 244 110 5 DRIED AIR OUTLET WE...

Страница 15: ... VIEW RIGHT SIDE VIEW TOP VIEW H I J K MODEL DIMENSIONS INCHES MM INLET OUTLET CONNECTIONS WEIGHT Lb kg A B C D E F G H I J K FLX 3 1 4 86 123 5 7 86 199 6 8 31 211 2 25 59 650 19 41 493 35 88 911 2 17 88 454 43 75 1111 3 3 39 86 2 35 43 900 42 17 1071 2 2 NPT 324 147 FLX 4 1 4 86 123 5 8 58 218 8 35 212 25 56 649 2 19 41 493 35 88 911 2 17 88 454 43 75 1111 3 3 39 86 2 35 43 900 42 17 1071 2 2 NP...

Страница 16: ...HT SIDE VIEW TOP VIEW I J K L MODEL DIMENSIONS INCHES MM INLET OUTLET CONNECTIONS WEIGHT Lb kg A B C D E F G H I J K L FLX 4 5 4 87 123 8 8 58 218 9 79 248 6 30 83 783 19 43 493 5 40 61 1031 6 17 72 450 19 30 490 1 97 50 43 70 1110 47 64 1210 49 32 1252 8 2 NPT 366 166 FLX 5 5 4 87 123 8 8 58 218 9 78 248 6 30 83 783 19 43 493 5 40 61 1031 6 17 72 450 19 30 490 1 97 50 43 70 1110 47 64 1210 49 32 ...

Страница 17: ... COM ON R1 S1 FG S2 R2 COM ON COM RB RA TS1 TS2 DRAIN TRAP1 MC1 8 9 10 8 N1 L1 PCB LEGEND M1 Refrigerant Compressor M2 Fan Motor MC1 Magnetic Contactor CR Running Capacitor CS Starting Capacitor R PTC Relay S1 Switch On Off S2 Overload Protector S3 High Pressure Switch TS1 Temperature Sensor 1 TS2 Temperature Sensor 2 SOL No Loss Drain Valve PCB Control Board S0 Main Switch Customer s installation...

Страница 18: ... Sensor TS2 Heat Exchanger Inlet Temp Sensor TS3 Air Inlet Temp Sensor SOL No Loss Drain Valve PCB Control Board S0 Main Switch Customer s installation F0 Main Fuse Customer s installation N L E Customer s installation CH 115V 1PH 60Hz MC1 S1 S R CR M1 C S2 L1 N1 S0 F0 16A M2 SOL S3 1 DIP SW 2 3 4 AC IN1 COMP1 ALARM1 DRAIN COM N O N C COM ON R1 S1 FG S2 R2 COM ON COM RB RA TS1 TS2 DRAIN TRAP1 MC1 ...

Страница 19: ... TS2 DRAIN TRAP1 MC1 8 9 10 8 N1 L1 PCB TS3 RS232 RS485 RS232 RX GND RS232 TX RS485 GND RS485 LEGEND M1 Refrigerant Compressor M2 Fan Motor MC1 Magnetic Contactor CR Running Capacitor CH Crankcase Heater S1 Switch On Off S2 Overload Protector S3 High Pressure Switch TS1 Separator Inlet Temp Sensor TS2 Heat Exchanger Inlet Temp Sensor TS3 Air Inlet Temp Sensor SOL No Loss Drain Valve PCB Control Bo...

Страница 20: ...or TS3 Air Inlet Temp Sensor DRAIN TRAP No Loss Drain Valve PCB Control Board L3 L1 L2 0V 480V 0V 120V 460V 3PH 60HZ W1 U1 V1 W2 U2 V2 MAIN POWER TB1 L3 L1 E L2 F1 2A MOTOR FAN MC2 MC1 COMP TRANSFORMER 50VA 60Hz S1 CRANK CASE HEATER R1 T1 MC1 4 5 L1 L3 R2 T2 1 DIP SW 2 3 4 AC IN1 COMP1 ALARM1 DRAIN COM N O N C COM ON R1 S1 FG S2 R2 COM ON COM RB RA TS1 TS2 DRAIN TRAP1 11 10 9 8 R2 T2 PCB TS3 RS232...

Страница 21: ...FRIGERANT FLOW FILTER REFRIGERANT COMPRESSOR BRAZED PLATE HEAT EXCHANGER TEMP SENSOR1 TS1 REF PCM AIR WETTED AIR INLET DRIED AIR OUTLET AIR AIR MOISTURE SEPARATOR INTEGRATED DRAIN VALVE DRAIN OUTLET NO LOSS MANUAL VALVE HIGH PRESSURE SWITCH CONDENSER FAN BLADES FAN MOTOR COOLING AIR FLOW CAPILLARY TUBE AIR COOLED TEMP SENSOR2 TS2 TS3 TEMP SENSOR3 FLX1 5 5 5 ONLY H P S ...

Страница 22: ...33676 7433676 7 Plate Heat Exchanger 7440039 7440114 7440247 7440115 7440116 8 High Pressure Switch 3161273 3161273 7433678 7433678 7433678 9 No Loss Drain Valve 7440053 7440053 7440053 7440053 7440053 10 Controller 7440050 7440050 7440051 7440051 7440051 11 Temperature Sensor 7440054 7440054 7440249 7440249 7440249 12 Magnetic Contactor Compressor 7433697 7433697 7433697 7433697 7433697 13 Magnet...

Страница 23: ...51 7440051 11 Temperature Sensor 7440249 7440250 7440250 7440250 7440250 12 Magnetic Contactor Compressor 7440251 7440251 7433698 7440251 7440251 13 Magnetic Contactor Fan 7440221 7440221 7440221 7440221 14 On Off Switch 3209745 3209745 7440052 3209745 3209745 15 Start Capacitor 16 Run Capacitor 7433695 17 Crankcase Heater 7439996 7439996 7440067 7439996 7439996 18 Voltage Transformer 7439965 7439...

Страница 24: ... Element Filter Drain Valve Repair Kit 2 FLX1 1 FPMK 7461654 FLX1 2 FPMK 7461655 FLX1 5 FPMK 7440120 FLX2 1 FPMK 7461656 Model Kit Components FLX 3 1 FLX 4 1 FLX 4 5 FLX 5 5 Standard Kit No Loss Drain Valve Repair Kit Drain Cover FLXMK 7461648 FLXMK 7461648 FLXMK 7461648 FLXMK 7461648 Standard Kit with Mounted Filtration No Loss Drain Valve Repair Kit Drain Cover Prefilter Element Afterfilter Elem...

Страница 25: ...23 NOTES ...

Страница 26: ...is the exclusive remedy of any buyer of the manufacturer s product The maximum damages liability of the manufacturer is the original purchase price of the product or part THE FOREGOING WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER WRITTEN ORAL OR STATUTORY AND IS EXPRESSLY IN LIEU OF THE IMPLIED WARRANTY OF MERCHANTABILITY AND THE IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PU...

Отзывы: