8
ENGINEERING DATA
SPECIFICATIONS
MODEL
Rated Capacity
1
(scfm)
Inlet /Outlet
Connections
Dimensions - inches (mm)
Net Weight
lbs (kg)
Height
Width
Length
FLX 1.1
75
NPT 1”
29.6
(751)
14.3
(363)
23.7
(603)
120
(54.5)
FLX 1.2
100
NPT 1”
28.0
(711)
14.3
(363)
30.7
(781)
147
(66.5)
FLX 1.5-1
150
NPT 2”
30.0
(761)
17.4
(443)
35.5
(901)
203
(92)
FLX 1.5
150
NPT 2”
30.0
(761)
17.4
(443)
35.5
(901)
189
(85.5)
FLX 2.1
200
NPT 2”
30.0
(761)
17.4
(443)
37.8
(961)
217
(98.5)
FLX 2.1-4
200
NPT 2”
30.0
(761)
17.4
(443)
37.8
(961)
244
(110.5)
FLX 3.1
300
NPT 2”
35.9
(911)
19.4
(493)
43.7
(1,111)
324
(147)
FLX 4.1
400
NPT 2”
35.9
(911)
19.4
(493)
43.7
(1,111)
335
(152)
FLX 4.5
450
NPT 2”
40.6
(1,032)
19.5
(494)
49.3
(1,253)
366
(166)
FLX 5.5
550
NPT 2”
40.6
(1,032)
19.5
(494)
49.3
(1,253)
396
(180)
1
Rated Flow Capacity - Conditions for rating dryers are in accordance with ISO 7183 (Option A2).
Compressed air at dryer inlet: 100 psig (6.9 barg) and 100°F (38°C); ambient air temperature: 100°F (38°C), operating on 60 Hz power
supply.
2
Refer to dryer data plate for refrigerant charge.
ELECTRICAL DATA
MODEL
Power Supply
Power
Consumption
(kW)
Refrigerant
Voltage
Phase
Hz
FLX 1.1
115
1
60
0.54
R-134a
FLX 1.2
115
1
60
0.62
FLX 1.5-1
115
1
60
1.04
R-407c
FLX 1.5
230
1
60
0.85
FLX 2.1
230
1
60
1.32
FLX 2.1-4
460
3
60
1.26
R-134a
FLX 3.1
460
3
60
1.99
R-407c
FLX 4.1
230
1
60
2.54
FLX 4.5
460
3
60
3.23
FLX 5.5
460
3
60
3.42
Содержание SPX Flow FLEX Series