HESS-OF-S-10K
Empowering Energy Clean And Affordable
30
•
Li-ion batter
Battery type
parameter
Ternary
lithium
(N13)
Ternary
lithium
(N14)
Lithium iron
phosphate
(LF16)
Lithium
iron
phosphate
(LF15)
Lithium
iron
phosphate
(LF14)
adjusta
ble
Overvoltage disconnect voltage
60V
60V
60V
60V
60V
Recharge recovery voltage after charging
(37 items)
50.4V
54.8V
53.6V
50.4V
47.6V
√
Equalize charging voltage
-
-
-
-
-
√
Boost charging voltage
53.2V
57.6V
56.8V
53.2V
49.2V
√
Float voltage
53.2V
57.6V
56.8V
53.2V
49.2
√
Undervoltage Alarm Voltage (01 Fault)
43.6V
46.8V
49.6V
46.4V
43.2V
√
Undervoltage alarm restores voltage
(01 failure)
Undervoltage alarm v0.8V
Undervoltage disconnect voltage (04 fault)
38.8V
42V
48.8V
45.6V
42V
√
Undervoltage disconnect recovery voltage
(04 fault) (35 setting items)
46V
49.6V
52.8V
49.6V
46V
√
Discharge limit voltage
36.4V
39.2V
46.4V
43.6V
40.8V
√
Over-discharge delay time
30s
30s
30s
30s
30s
√
Equalization duration
-
-
-
-
-
Equalize charging interval
-
-
-
-
-
Boost charging duration
120 min
120 min
120 min
120 min
120 min
√
If no BMS is connected, the inverter will charge according to battery voltage with a preset
charging curve. When the inverter communicates with the BMS, it will follow the BMS
instructions to perform a more complex stage charging process.
○
!
NOTICE