lubricant oil. In addition, Hanbell also offers 250W oil heater to keep adequate lubricant oil temperature for large external oil
separator and applications in areas with low ambient temperature.
Specification
:
250W; 110V or 220V; IP 54; Outer diameter of cable: 6~8mm
Note:
1.
If compressor is installed in low ambient temperature, it is recommended to insulate oil separator against cold ambience.
2.
The cable connector equipped with oil heater is part of certified explosion proof unit which is prohibited to be changed
randomly. If it is required to be changed, it is necessary to use the spare part equal to oil heater cable specification and ATEX
explosion proof standard or contact Hanbell sales representative.
3.
The cable connector is required to be locked by wrench until it can’t be dismantled by manual, and should you require
technical document for further clarification, please contact Hanbell sales representative.
2.11 Oil level switch
There are 2 wires for the interlock to main control circuit or any micro controller’s independent circuit. To prevent from oil level
switch trip caused by oil foaming or surging in the sump, a time delay around 10 ~ 15 seconds is recommended before shut down
the compressor.
Max. contact capacity = 50W/SPST
Surge current = 0.5A
Max. voltage = 200V DC/ 240V AC
Max. current = 1A
Note:
1.
On the float ball there is a triangle mark which tells you its sensor direction. Therefore, before you install an oil level switch on
a compressor or an external oil separator, please use the triangle mark as your reference before install any oil level switch on
the compressor or external oil separator.
2.
Please check this triangle mark and modify the oil level switch if needed.
3.
If you have any other question, don’t hesitate to contact with Hanbell representatives for help.
4.
The illustration below show you the outside appearance of our oil level switch
5.
The cable connector equipped with oil heater is part of certified explosion proof unit which is prohibited to be changed
randomly. If it is required to be changed, it is necessary to use the spare part equal to oil heater cable specification and ATEX
explosion proof standard or contact Hanbell sales representative.
6.
The cable connector is required to be locked by wrench until it can’t be dismantled by manual, and should you require
technical document for further clarification, please contact Hanbell sales representative.
2.12 Oil drain valve
Oil drain valve is installed in compressor to drain out oil for maintenance.
Figure Oil drain valve
Normal Level
Low Level
N.O.
N.C.
Figure. Oil level switch
Содержание ExP Series
Страница 1: ...1 ...
Страница 6: ...6 1 4 ATEX code description II 2 G c IIB T4 II 2 G Ex d IIB T4 Gb ...
Страница 8: ...8 RC2 180 ExP A B RC2 200 ExP A ...
Страница 9: ...9 RC2 200 ExP B RC2 230 ExP A B UNIT SI mm Imperial in ...
Страница 10: ...10 RC2 260 ExP A B SI mm Imperial in UNIT RC2 300 ExP 320 ExP A ...
Страница 11: ...11 RC2 300 ExP 320 ExP B RC2 310 ExP A B ...
Страница 12: ...12 RC2 340 ExP 370 ExP A RC2 340 ExP 370 ExP B ...
Страница 13: ...13 RC2 410 ExP A B RC2 470 ExP A ...
Страница 14: ...14 RC2 470 ExP B RC2 510 ExP A B ...
Страница 15: ...15 RC2 550 ExP A RC2 550 ExP B ...
Страница 16: ...16 RC2 580 ExP A B RC2 620 ExP A B ...
Страница 17: ...17 RC2 710 ExP A RC2 710 ExP B ...
Страница 18: ...18 RC2 790 ExP A RC2 790 ExP B SI mm Imperial in UNIT ...
Страница 19: ...19 RC2 830 ExP A RC2 830 ExP B ...
Страница 20: ...20 RC2 930 ExP A R2C 930 ExP B ...