The Ex cable entry of cable box must installed at least by ATEX certified cable glands.
6.
It is required to ensure that all bolts, plugs and cable glands are sealed in Ex cable box to avoid malfunction.
※
Sealant can be used LOCTITE 554 or similar nature of glue, but according to EN 60079-14 standard can’t using the tape
seal.
7.
Unused opening shall be closed by ATEX certified blanking element or the blind plug provided with the cable box.
8.
If the user has to open the terminal box for maintenance, it is necessary to make sure the explosive atmosphere is not presented
around the equipment.
Gr o u n d in g b o lt
Gr o u n d in g b o lt
Figure 2.2 Grounding Terminal
Suggestion
:
a.
The regular setting of electric leak protection should be greater than 50mA; for a humid location, 25mA is better.
。
b.
Grounding voltage of casing should be no greater than 50V; for a humid location, the limit is 25V.
c.
The resistance between the protective earth and grounding conductor terminal should be no greater than 0.1 Ohm.
d. Air cut board (ACB) is regularly equipped with electric leak protection. Please refer to related settings for its normal action.
e.
If electric leak protection is active, please check if insulation of equipments is normal and if its wiring and setting are correct.
2.9 INT69HBY control module and PTC temperature sensor
In order to protect compressor, each RC2 series compressor has been installed three PTC temperature sensors inside motor coil and
another one at the discharge side of compressor. These sensors are connected to an INT69HBY control module to monitor the motor
and discharge temperature. If the temperature in one of the positions monitored exceeds the nominal response temperature of the
respective PTC thermistor, the sensor resistance increases and the INT69HBY control module output relay trips. The module resets
when the temperature drops below the response temperature by approx. 5K. The output replay provides a potential-free change-over
contact and is energized as long as the nominal response temperature is not exceeded.
Figure 2.3 INT69 HBY and PTC sensor connection
V/2
W/3
U/1
X/8
Y/9
Z/7
A
B
B Set:Pt100
Ω
/Pt1000
Ω
(Optional)
A Set:PTC
Содержание ExP Series
Страница 1: ...1 ...
Страница 6: ...6 1 4 ATEX code description II 2 G c IIB T4 II 2 G Ex d IIB T4 Gb ...
Страница 8: ...8 RC2 180 ExP A B RC2 200 ExP A ...
Страница 9: ...9 RC2 200 ExP B RC2 230 ExP A B UNIT SI mm Imperial in ...
Страница 10: ...10 RC2 260 ExP A B SI mm Imperial in UNIT RC2 300 ExP 320 ExP A ...
Страница 11: ...11 RC2 300 ExP 320 ExP B RC2 310 ExP A B ...
Страница 12: ...12 RC2 340 ExP 370 ExP A RC2 340 ExP 370 ExP B ...
Страница 13: ...13 RC2 410 ExP A B RC2 470 ExP A ...
Страница 14: ...14 RC2 470 ExP B RC2 510 ExP A B ...
Страница 15: ...15 RC2 550 ExP A RC2 550 ExP B ...
Страница 16: ...16 RC2 580 ExP A B RC2 620 ExP A B ...
Страница 17: ...17 RC2 710 ExP A RC2 710 ExP B ...
Страница 18: ...18 RC2 790 ExP A RC2 790 ExP B SI mm Imperial in UNIT ...
Страница 19: ...19 RC2 830 ExP A RC2 830 ExP B ...
Страница 20: ...20 RC2 930 ExP A R2C 930 ExP B ...