27
Compressors require starting up at partial load.
Characteristics of Y-
Δ
starting
1.Starting current in Y connection is 1/3 of lock rotor ampere.
2.Starting torque in Y connection is 1/3 of lock rotor torque.
Characteristic of PWS starting
1. The starting current is around 40%~70% of lock rotor ampere. It depends on the system design and motor specifications.
2.7 Certification marking
The model is designed based on ATEX 2014/34/EU, and in compliance with the requirement of EN60079-0:2012,
EN60079-1:2014. It is also verified with ATEX Certification II 2 G c IIB T4 and II 2 G Ex d IIB T4, which is suitable for the
hazardous explosive atmospheres as Zone1 and Zone2.
2.8 Cable Box
1.
Hanbell designs and makes the cable box which meets IEC 60529:IP66 protection degree. Cable box schematic diagram and
the size of opening in cable box (for motor power line and control power line) refer to the drawing below Figure 2.1; cable
glands and plugs tightening torque refer to Table2.1.
1 / 2 " NPT/ M2 0
3 " NPT/ M7 5
1 / 2 " NPT/ M2 0
3 " NPT/ M7 5
WARNING : Do n o t o p en wh en en er g iz ed !
◎
RC2 - 1 0 0 ~ 1 8 0 Ex p
◎
RC2 - 2 0 0 ~ 9 3 0 Ex p
Figure 2.1 cable box schematic diagram
Component
specification
Tightening torque
Cable gland
3” NPT
400 N-m
1/2”NPT
M20
M75
Plug
3” NPT
400 N-m
1/2”NPT
M20
M75
Table 2.1 cable glands and plugs tightening torque
2.
Hanbell selection software provides working current and MCC based on the working condition, which can be the reference for
selecting electric wiring, magnetic contactor, and fuse.
3.
The anti-loose connector can prevent the compressor from sudden motor trip due to motor protector error.
4.
There’s a grounding terminal inside cable box. Please ensure its connection to the grounding wire. (shown on Figure 2.2)
Содержание ExP Series
Страница 1: ...1 ...
Страница 6: ...6 1 4 ATEX code description II 2 G c IIB T4 II 2 G Ex d IIB T4 Gb ...
Страница 8: ...8 RC2 180 ExP A B RC2 200 ExP A ...
Страница 9: ...9 RC2 200 ExP B RC2 230 ExP A B UNIT SI mm Imperial in ...
Страница 10: ...10 RC2 260 ExP A B SI mm Imperial in UNIT RC2 300 ExP 320 ExP A ...
Страница 11: ...11 RC2 300 ExP 320 ExP B RC2 310 ExP A B ...
Страница 12: ...12 RC2 340 ExP 370 ExP A RC2 340 ExP 370 ExP B ...
Страница 13: ...13 RC2 410 ExP A B RC2 470 ExP A ...
Страница 14: ...14 RC2 470 ExP B RC2 510 ExP A B ...
Страница 15: ...15 RC2 550 ExP A RC2 550 ExP B ...
Страница 16: ...16 RC2 580 ExP A B RC2 620 ExP A B ...
Страница 17: ...17 RC2 710 ExP A RC2 710 ExP B ...
Страница 18: ...18 RC2 790 ExP A RC2 790 ExP B SI mm Imperial in UNIT ...
Страница 19: ...19 RC2 830 ExP A RC2 830 ExP B ...
Страница 20: ...20 RC2 930 ExP A R2C 930 ExP B ...