background image

 

User Manual MCx-xxxAS-1.05 

 

 

 

Page 11 of 18

                                                                                                                        

www.hanbayinc.com | 1 800 315 4461      

Rev.2021.8                                                                                                                                                                              [email protected] 

Signal Loss 

 

The “

SignalLostPosition

” register can be used (optional) to set the position of the actuator upon signal loss. 

Signal loss can only occur when controlling the actuator with 4-20 mA (or 1-5 V) input signals, i.e. when 

TargetFromRS485Flag

” is set to 1. The signal is considered lost when it falls below 2.80 mA (or 0.700 V). 

 

 
 

1. 

For actuators that are not connected to a UPS

 (Uninterruptible Power Supply), the loss of signal 

will be simultaneous with power loss. Consequently, the actuator will not be able to move anywhere. 
In the shutdown process, the actual position is automatically saved to the internal EEPROM. [This 
saving of the position only happens for min. 18 VDC supplies] When power is restored, the actuator 
will “know” where it’s at and will simply start to follow the signal as received. 

 

IF YOU HAVE TO

 turn the actuator manually when its power is turned off, it will lose its 

position, and it will need to be re-zeroed (as described in the Calibration section) 
 

 

2. 

For  actuators  that  are  connected  to  a  UPS

  the  actuator  will  move  to  the  position  defined  by  the 

value in the “SignalLostPosition” register. 

 

The default value is 0xFFFF (DEC: 65535). The actuator will ignore the lost signal, and simply remain 
in its current position. 
If the value is between 

“InputRangeLow” and “InputRangeHigh”, the actuator will move to the value 

in SignalLostPosition when the signal is lost 
 

 
 
 

Reading the Input Registers 

 

The physical meaning of the value in the “

CurrentPosition

” register depends on the values in the 

OutputRangeLow

” and “

OutputRangeHigh

” registers, as well as the “

NumberofTurns

” register. 

 

Example:

 

The actuator parameters are set to (decimal representation for simplicity): 
NumberOfTurns = 10 
OutputRangeLow = 500 
OutputRangeHigh = 2500 

 

If “CurrentPosition” equals to 500, that means the valve is closed

 

 

If “CurrentPosition” equals to 1500, that means the valve is 5 turns opened 

 
 
To read the value from the “

CurrentPosition

” register: 

 

Register name 

Address 

Max  Min 

Default  Actuator 

address 

Function 
code 

Register 
address 

Qty of 
registers 

CRC 

CurrentPosition  0x0014 

N/A  N/A  N/A 

Example:

 Read the current position in actuator 

number 31 

0x1F 

0x04 

0x0014 

0x0001 

0x---- 

1 byte 

1 byte 

2 bytes 

2 bytes 

2 bytes 

Register name 

Address 

Max 

Min 

Default  Actuator 

address 

Fct. 
code 

Register 
address 

Register 
new value 

CRC 

SignalLost 
Position 

0x0009 

Input 
Range 
Low 

Input 
Range 
High 

0xFFFF 

Example:

 Set the signal lost position to 3000 in 

actuator number 19 

0x13 

0x06 

0x0009 

0x0BB8 

0x---- 

1 byte 

1byte  2 bytes 

2 bytes 

2bytes 

Содержание MC-AS-1.05 Series

Страница 1: ...ignal and Feedback 3 Serial Port Connection 3 OPERATION 4 DIP switches 4 Set the communication parameters 4 Set the actuator address 5 Modbus Protocol 6 Speed and Torque Settings 7 Speed and Torque De...

Страница 2: ...standard with a Turck 6 position connector and a 20 cable with plug Cut the cable to the length required and then connect according to the following wire color schematic Pins indicate the connection...

Страница 3: ...Signal and Feedback Locate the correct connection terminals as shown in the picture on p 2 then connect your communication wires to PIN 3 and PIN 4 grey and pink wires as shown below Serial Port Conn...

Страница 4: ...n the signal is decreased with DIP 12 in the OFF position Putting DIP 12 in the ON position will cause counter clockwise turning for a decrease in signal For changes in DIP 12 position to take effect...

Страница 5: ...0 1 1 0 1 14 0 0 1 1 1 0 15 0 0 1 1 1 1 16 0 1 0 0 0 0 17 0 1 0 0 0 1 18 0 1 0 0 1 0 19 0 1 0 0 1 1 20 0 1 0 1 0 0 21 0 1 0 1 0 1 22 0 1 0 1 1 0 23 0 1 0 1 1 1 24 0 1 1 0 0 0 25 0 1 1 0 0 1 26 0 1 1...

Страница 6: ...e is not supported Actuator memory map Address DEC Address HEX Offset Register Name Type 0 0x0000 4001 MaximumSpeed Holding registers READ and WRITE 1 0x0001 4002 MaximumPower 2 0x0002 4003 NumberOfTu...

Страница 7: ...eed to 0 in actuator number 8 0x08 0x06 0x0000 0x0000 0x 1 byte 1 byte 2 bytes 2 bytes 2 bytes Possible values for the MaximumSpeed register are shown in the following table To see how these values re...

Страница 8: ...ess 0x0001 Seating Torque in lbs Operating torque is 100 12VDC 24VDC 0 23 0 17 35 1 11 1 30 60 2 7 2 55 115 3 4 3 70 145 NOTE If actuator is RCK xxxAS divide torque values by 3 To convert in lbs to Nm...

Страница 9: ...0x0B 0x06 0x0003 0x0000 0x 1 byte 1 byte 2 bytes 2 bytes 2 bytes The InputRangeLow register allows the user to set the lower limit of the input signal i e the value of the input signal at which the ac...

Страница 10: ...ing the valve completely This enables a new fully closed position to be established based on normal wear of the valve seat If the value in TargetPosition is the same as the value in InputRangeHigh the...

Страница 11: ...alLostPosition register The default value is 0xFFFF DEC 65535 The actuator will ignore the lost signal and simply remain in its current position If the value is between InputRangeLow and InputRangeHig...

Страница 12: ...lt Actuator address Function code Register address Qty of registers CRC StatusRegister 0x0015 N A N A N A Example Read the status register in actuator number 32 0x20 0x04 0x0015 0x0001 0x 1 byte 1 byt...

Страница 13: ...It will turn clockwise until the actuator has reached the fully closed position of the valve If the actuator is being controlled via Modbus protocol i e TargetFromRS485Flag register contains value 0...

Страница 14: ...s alone can solve basic problems See the Calibration section above for more details If the actuator does not move try following these steps 1 Re calibrate the actuator This will move the actuator rega...

Страница 15: ...User Manual MCx xxxAS 1 05 Page 15 of 18 www hanbayinc com 1 800 315 4461 Rev 2021 8 hanbaysales hanbayinc com ACTUATOR DIMENSIONS MCJ MCL MCM xxxAS models MCH xxxAS models...

Страница 16: ...User Manual MCx xxxAS 1 05 Page 16 of 18 www hanbayinc com 1 800 315 4461 Rev 2021 8 hanbaysales hanbayinc com MCF xxxAS models...

Страница 17: ...User Manual MCx xxxAS 1 05 Page 17 of 18 www hanbayinc com 1 800 315 4461 Rev 2021 8 hanbaysales hanbayinc com PART NUMBER BREAKDOWN Full Hanbay Part Number...

Страница 18: ...9 Px 10 3 Actuator Part Number Refer to part number breakdown for available options QR Code Scan this QR code for a direct link to the user manual for your unit Actuator Serial Number This serial numb...

Отзывы: