HAMWORTHY HEATING LTD
40
UPTON FLOOR STANDING SERIES
500001340/C
APPENDIX C
-
FLUE DATA
-
Natural Gas & LPG
C1.0 FLUE SYSTEM
1. Detailed recommendations for flue systems are given in BS 6644, and IGE/UP/10. All flue discharges for plant
exceeding 150kW output must comply with the third edition of the 1993 Clean Air Act Memorandum.
WARNING: THE FLUE DISCHARGE FROM A UPTON BOILER WILL GENERATE A
PLUME AT THE TERMINAL EXIT. THIS MUST BE CONSIDERED WITH REGARD TO
TERMINAL LOCATION AND ADJACENT BUILDING FABRIC.
C1.1 General Requirements
The Upton
boilers are designed to be used with natural draught flues. Flue systems should be designed in
accordance with regulations and with reference to BS 6644 and IGE/UP/10.
Open (Natural draught ) Flue.
Type B23p: Flue pressurised, intake from ventilated plant room and discharge via horizontal/vertical flue.–
The following points should be noted:
a. Due to the high thermal efficiency of the boiler condensation in the flue will occur. It is strongly recommended
that twin wall or insulated flue pipe is used on all installations.
b. Care should be taken to ensure that the flue is installed such that any condensation is continuously drained.
Any flue system with a horizontal section should have a maximum slope of 3° upwards in the direction of the
exhaust gas flow. All joints should be such that any condensation is directed back down the slope to an open
MODEL
UF100
-
1
UF200
-
2
UF300
-
3
UF150
-
1
UF300
-
2
UF450
-
3
Flue Connection (B23p open flue)
mm
130
200
200
130
200
200
Approx. Flue Gas Temperature @ 80/60°C
°C
72
72
Approx. Flue Gas Temperature @ 50/30°C
°C
42
42
Approx. Flue Gas Volume @ 9.0% CO2 (@ 72°C)
m
3
/h
155
310
465
233
466
699
Maximum Natural Flue Draught
-
Hot (Cold)
Pa
100 (30)
100 (30)
Maximum pressure at flue sample point
Pa
120
150
Pressure available at Flue Connection
Pa
150
150
150
150
150
150
Approximate maximum straight flue length
m
114
267
126
54
126
59
MODEL
UF200
-
1
UF400
-
2
UF600
-
3
UF250
-
1
UF500
-
2
UF750
-
3
Flue Connection (B23p open flue)
mm
130
250
250
130
250
250
Approx. Flue Gas Temperature @ 80/60°C
°C
72
72
Approx. Flue Gas Temperature @ 50/30°C
°C
42
42
Approx. Flue Gas Volume @ 9.0% CO2 (@ 72°C)
m
3
/h
314
628
942
394
788
1182
Maximum Natural Flue Draught
-
Hot (Cold)
Pa
100 (30)
100 (30)
Maximum pressure at flue sample point
Pa
180
210
Pressure available at Flue Connection
Pa
150
150
150
150
130
130
Approximate maximum straight flue length
m
31
219
103
20
125
58
MODEL
UF300
-
1
UF600
-
2
UF900
-
3
UF350
-
1
UF700
-
2
UF1050
-
3
Flue Connection (B23p open flue)
mm
130
300
300
130
300
300
Approx. Flue Gas Temperature @ 80/60°C
°C
72
72
Approx. Flue Gas Temperature @ 50/30°C
°C
42
42
Approx. Flue Gas Volume @ 9.0% CO2 (@ 72°C)
m
3
/h
474
948
1422
543
1086
1629
Maximum Natural Flue Draught
-
Hot (Cold)
Pa
100 (30)
100 (30)
Maximum pressure at flue sample point
Pa
210
210
Pressure available at Flue Connection
Pa
100
100
80
110
70
60
Approximate maximum straight flue length
m
9
168
63
8
91
37
Figure C1
-
Flue Data