HAMWORTHY HEATING LTD
44
SHERBORNE
500001167/E
APPENDIX D - VENTILATION
D1.1 Air Supply
Detailed recommendations for air supply are given in BS 6644. The following notes are intended to give general
guidance. In all cases there must be provision for an adequate supply of air for both combustion & general
ventilation, in addition to that required for any other appliance.
Combustion air for the boiler is drawn through the slots in the rear edge of the side panels. The air inlets
must
be
kept open & free from blockage at all times.
D1.2.1 Air Supply by Natural Ventilation - Open Flue applications
The boiler room must have, or be provided with, permanent air vents directly to the outside air, at high level & at
low level. For an exposed boiler house, air vents should be fitted, preferably on all four sides, but at the least on
two sides. Air vents should have negligible resistance & must not be sited in any position where they are likely to
be easily blocked or flooded or in any position adjacent to an extraction system which is carrying flammable
vapour. Grilles or louvres must be so designed that high velocity air streams do not occur within the space
housing the boiler.
Boiler house ventilation
Low level (inlet) - 4cm² per kW of total rated input (Net)
High level (output) - 2cm² per kW of total rated input (Net)
Compartment ventilation
Where the boiler is to be installed in a cupboard or compartment, permanent high & low level ventilation is
required which must communicate direct to outside, for cooling purposes.
Low level (inlet) - 10cm² per kW of total rated input (Net)
High level (output) - 5cm² per kW of total rated input (Net)
D1.2.2 Air Supply by Natural Ventilation - Room Sealed Installations
Where the boiler(s) are to be installed in a boiler room or internal space, the room or internal space must have
permanent air vents directly to the outside air, at high level & at low level with the general requirements detailed
above on location & construction.
Boiler house ventilation
Low level (inlet) - 2cm² per kW of total rated input (Net)
High level (output) - 2cm² per kW of total rated input (Net)
Compartment ventilation
Where the boiler is to be installed in a cupboard or compartment, permanent high & low level ventilation is
required which may communicate to an adjoining room or outside, for cooling purposes.
Ventilation to a room or internal space - 10cm² per kW of total rated input (Net)
Ventilation direct to outside - 5cm² per kW of total rated input (Net)
D1.3 Air Supply by Mechanical Ventilation
Air supplied to the boiler room by Mechanical means should be as follows:
1) Mechanical ventilation must be interlocked with the boilers to prevent operation in
the event of ventilation fan failure
2) Mechanical inlet & mechanical extract can be utilised providing the design
extraction rate does not exceed one third of the design inlet rate.
3) Mechanical extract ventilation with natural inlet ventilation
MUST NOT
be used.
For Mechanical ventilation systems an automatic control should be provided to cut off the gas supply to the boiler,
in the event of failure of air flow in either inlet or extract fans.
D 1.4. Boiler House Temperatures
The air supplied for boiler house ventilation shall be such that the maximum temperatures within the boiler house
shall be as follows:
At floor level (or 100mm above floor level) = 25°C.
At mid-level (1.5m above floor level) = 32°C.
At ceiling level (or 100mm below ceiling level) = 40°C.
D 1.5. General Requirements
The air supply should be free from contamination such as building dust & insulation fibres from lagging. To avoid
unnecessary cleaning & servicing of the boiler modules, the boilers should not be fired whilst building work is
Содержание Sherborne SE64he
Страница 2: ......
Страница 10: ...HAMWORTHY HEATING LTD 8 SHERBORNE 500001167 E 4 Boiler Layout Description 4 1 Accessory Pack...
Страница 27: ...HAMWORTHY HEATING LTD 25 SHERBORNE 500001167 E...
Страница 29: ...HAMWORTHY HEATING LTD 27 SHERBORNE 500001167 E 8 9 Wiring Diagram...
Страница 30: ...HAMWORTHY HEATING LTD 28 SHERBORNE 500001167 E 8 10 Wiring Diagram LMU...
Страница 39: ...HAMWORTHY HEATING LTD 37 SHERBORNE 500001167 E External Control Wiring for Multiple Module Installation...
Страница 53: ......
Страница 54: ......