8.3 Operating Modes
The boiler has 4 heating modes which can be selected by pressing the mode button
The currently selected mode is indicated by a block below the mode symbols on the fascia. Pressing the mode
button will cycle through the 4 modes 1 at a time.
Automatic > Continuous ‘Normal’ > Continuous ‘Reduced > Standby
↵
8.4 Information Button
Information about the boiler can be obtained at any time by pressing the info button. Repeated presses wsill cycle
through the following information:
Dhw temperature > Water Pressure > Operating Phase > Outside Temperature > Error Code > Boiler Tempearture
↵
Press the mode button to return to the default display
8.4.1 Extended Information Modes
The information button can be used to obtain additional information about the operation of
the boiler. To do this press both arrow buttons for 3 seconds. The time display will be
replaced by an address formed by a letter (b,C or d) & a digit (0-7). Use the arrow buttons to
change the letter and the + & - buttons to change the digit.
Press the information button to switch back to the information display or the mode button to return to
the default display.After 8 minutes the display will automatically change back to the default display
Operating mode
Effect of selection
Automatic operation
Heating circuit (HC1) runs according to time switch program 1
Standby
Heating circuit 1 is switched off, Frost protection functions active
Continuous ‘Normal’
Heating circuit 1 continuously on according to the adjusted nominal room tem-
perature set point or heating circuit set point
Continuous ‘Reduced’
Reduced room temperature set point or heating circuit frost protection set point
Display Code
Description
b0
Internal Software Diagnostic Code
b1
Boiler return temperature
b2
DHW temperature sensor 2
b3 -
b4 Outside
temperature
b5
Composite outside temperature
b6
Attenuated outside temperature
b7
Flow temperature 3-way valve
C1 Ionization
current
C2 Fan
speed
C3
Current fan control PWM
C4 Relative
output
C5 -
C6 Control
differential
d1
Set point of 2-position or modulating controller (PID)
d2
Current boiler temperature setpoint
d3
Room Temperature setpoint
d4
DHW temperature setpoint
d5
Maximum degree of modulation in heating mode
d6
Maximum speed at maximum output in heating mode
Содержание Sherborne SE64he
Страница 2: ......
Страница 10: ...HAMWORTHY HEATING LTD 8 SHERBORNE 500001167 E 4 Boiler Layout Description 4 1 Accessory Pack...
Страница 27: ...HAMWORTHY HEATING LTD 25 SHERBORNE 500001167 E...
Страница 29: ...HAMWORTHY HEATING LTD 27 SHERBORNE 500001167 E 8 9 Wiring Diagram...
Страница 30: ...HAMWORTHY HEATING LTD 28 SHERBORNE 500001167 E 8 10 Wiring Diagram LMU...
Страница 39: ...HAMWORTHY HEATING LTD 37 SHERBORNE 500001167 E External Control Wiring for Multiple Module Installation...
Страница 53: ......
Страница 54: ......