background image

 
HAMWORTHY HEATING LTD 

 

LILLIPUT HE 

 

500001047/F 

10 

ensure they remain in position. 

e. 

Remove the two reducing plugs - located at 
the top and bottom of the front section. 

f. 

Fit the boiler assembly tools* - one through 
the flow (top) connection and the other 
through the return (bottom) connection and 
evenly compress the sections together. 

g. 

Fit the four tie rods, tighten the tie rod nuts to 
a torque of 35 Nm (26 lbf.ft), and then 
carefully remove the two assembly tools. 

 

Replace the two reducing plugs in the front 
section and fit the thermostat pocket and 
drain valve in the top and bottom plugs 
respectively. Slide the stainless steel baffle 
plate into the roof of the combustion chamber 
(see item 24 Fig 4) locating the returned 
edges between the section fins. 

h. 

Fit the front door and rear combustion 
chamber plate, together with ceramic 
insulation, and secure with the nuts provided. 

N.B.

  The front boiler door may be hinged on either 

left or right side, as required. 
i. 

Fit flue box to rear section and secure using 
the screws provided. 

j. 

On completion of assembly, the heat 
exchanger should be hydraulically pressure 
tested to 1.5 times the maximum system 
pressure operating for 30 minutes (BS779 - 
1989, Amendment 1 - 1993). 

 

• 

Boiler assembly tools are available on loan, 
from Hamworthy Heating Ltd. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

6. BOILER 

ASSEMBLY 

 
6.1 Boiler 

Sections 

 

The heat exchanger is made up from THREE or 
FOUR different types of section, each weighing 
around 32kg (70 lb), as follows: 
 

• 

   One rear section  (R) 

• 

   One front section  (F) 

• 

   Intermediate sections     (I) 

• 

   Special intermediate sections  (SI) 

 
For the purposes of identification the 'Intermediate' 
sections have a joint face between the middle and 
upper part of the section, whereas the 'Special 
intermediate' sections do not. 
These sections MUST be assembled in the correct 
sequence working from the rear of the boiler as 
detailed in table 4 above. 
 

6.2 Assembly 

Procedure 

 

If it has been necessary to dismantle the boiler for 
any reason, the following procedure should be 
adopted to re-assemble it: 
 
a. 

Position the rear section and thoroughly clean 
the nipple seatings (at both top and bottom of 
the section) and the mastic rope groove 
around the perimeter of the section. 

b. 

Taking two new nipples, smear them with 
suitable nipple sealant  and insert them into 
their seatings - ensuring that they are at right 
angles to the face of the section.  Fit new 
mastic rope into the groove around the 
section.   

 
Should the mastic rope break during this operation 
the two ends must be overlapped and pressed 
together to avoid the possibility of leakage. 
 

c. 

Taking an intermediate section, thoroughly 
clean the four nipple seatings and the mastic 
rope grooves, and then carefully fit it to the 
rear section - locating the two nipples into 
their corresponding seatings.

 

d. 

Repeat this operation for each of the 
remaining intermediate, special intermediate, 
and front section, using new nipples and 
mastic rope at each joint.  The intermediate 
sections may need support on chocks to 

BOILER 

SECTION TYPE  

LILLIPUT HE 65 

SI 

 

 

LILLIPUT HE 90 

SI 

SI 

SI 

No. FROM REAR 

TABLE 4.Composition of Sections within Heat Exchanger

 

Содержание LILIPUT HE

Страница 1: ...SE INSTRUCTIONS MUST BE READ AND UNDERSTOOD BEFORE INSTALLING COMMISSIONING OPERATING OR SERVICING EQUIPMENT LILLIPUT HE GAS OIL FIRED CAST IRON SECTIONAL BOILERS INSTALLATION COMMISSIONING AND MAINTE...

Страница 2: ......

Страница 3: ...ISSION OPERATE OR MAINTAIN THIS UNIT THE LILLIPUT BOILER IS INTENDED FOR USE AS A COMMERCIAL APPLIANCE AND IS NOT CERTIFIED FOR USE IN DOMESTIC APPLICATIONS GAS FIRED VARIANTS OF THE LILLIPUT BOILER R...

Страница 4: ...il Supply 3 6 Flue System 3 7 Ventilation and Air Supply 3 7 1 Natural Ventilation 3 7 2 Mechanical Ventilation 4 0 WATER SYSTEM 7 4 1 Pipework 4 2 Pumps 4 3 Vent Pipe 4 4 Safety Valve 4 5 Pressure Ga...

Страница 5: ...ater Flow Rates and Pressure Drops 7 Table 4 Composition of Sections within Heat Exchanger 10 FIGURES Figure 1 Overall Dimensions and Clearances 3 Figure 2 Boiler Control Panel Wiring Diagram 9 Figure...

Страница 6: ...be used individually or in a multiple boiler configuration and are suitable for use on either open vented or sealed low temperature hot water heating systems For hot water production they can be used...

Страница 7: ...AS VOLUME AT NTP NAT GAS m3 h ft3 h 90 0 3178 118 2 4174 APPROX FLUE GAS TEMP NAT GAS deg C 190 FLUE DRAUGHT REQUIRED AT BOILER OUTLET mbar in wg 0 1 0 25 0 04 0 10 WEIGHT FILLED WITHOUT BURNER kg lb...

Страница 8: ...Dimensions and Clearances Fig 1 Overall Dimensions and Clearances BOILER MODEL Lmm Hmm Amm Gas Amm Oil Bmm Cmm Dmm min LILLIPUT HE 65 800 530 347 261 400 500 400 LILLIPUT HE 90 960 530 389 261 400 500...

Страница 9: ...allation commissioning and maintenance c British Gas Publications IM 2 Purging procedures for non domestic gas installations IM 5 Soundness testing procedures for industrial and commercial gas install...

Страница 10: ...sh Standards and Local Authority Regulations Oil Supply Lines The oil supply line s between storage tank and burner should be run in copper steel or aluminium pipe Galvanised pipes and fittings should...

Страница 11: ...output and above The following notes are given as general guidance 3 7 1 Air Supply by Natural Ventilation The boiler room must have or be provided with permanent air vents directly to the outside ai...

Страница 12: ...d be taken into account when selecting the circulating pump for the system In the case of open vented systems it is essential that the pump does not pump over i e push water out of the open vent pipe...

Страница 13: ...ief safety valve of approved manufacture and sized to match the boiler s rating in accordance with BS 6644 should be installed in the flow pipe between the boiler s and open vent pipe connection The s...

Страница 14: ...The boiler control panel includes a terminal block for all electrical connections to the boiler Refer to Fig 2 below Wiring diagrams showing the electrical connection of burner to boiler are given in...

Страница 15: ...One front section F Intermediate sections I Special intermediate sections SI For the purposes of identification the Intermediate sections have a joint face between the middle and upper part of the se...

Страница 16: ...oiler sections Check that the cut outs A are positioned around the rear spacers and secure in position with duct tape A Fit the rear insulation jacket over the flue outlet Secure the top and side edge...

Страница 17: ...cable entry hole A is at the front of the boiler Se cure the top cover to the rear cover using the 4x10 self tapping screws B A B B Remove the cable entry blanking plate A from the control con sole a...

Страница 18: ...r as detailed in British Gas Publications IM 5 and IM 2 respectively Check that gas meter is operational and has been checked by the local region of British Gas Check that gas meter and supply pipewor...

Страница 19: ...aximum pressure of gas train governor is not exceeded i Adjust start and main output gas rates as detailed in the manufacturer s technical information supplied with the gas train j Check that overheat...

Страница 20: ...ISOLATOR AND SHUT OFF FUEL SUPPLY TO BOILER a a For oil installations Desludge oil storage tank and examine for leaks and signs of deterioration b Examine contents gauge for visibility and clean or r...

Страница 21: ...LLIPUT HE 500001047 F 16 i h Check all flue joints for integrity j i Check ventilation ducts grilles to boiler room and ensure they are clear k j Re commission boiler as detailed in relevant parts of...

Страница 22: ...Hexagonal bush 1 BSP 573405119 9 Thermostat pocket 573405228 10 Plug BSP 573405121 11 Door hinge 573405229 12 Insulation front door 573405230 13 Insulation front 573405231 14 Front door 573405232 15...

Страница 23: ...HAMWORTHY HEATING LTD LILLIPUT HE 500001047 F 18 Fig 4 Exploded View of Boiler 26 Item 26 insulation to be placed between refractory brick and door casting...

Страница 24: ...LIGHT L N 3 WIRE BURNER CONNECTION FOR REMOTE LOCKOUT LAMP OR VOLT FREE SIGNAL FOR OVER TEM PERATURE LOCKOUT FOR BURNER WORKING SIGNAL FOR EXTERNAL THERMOSTAT OR PRESSURE SWITCH FOR EXTERNAL PUMP SWI...

Страница 25: ...mm 616 776 Combustion Chamber Type Reversed BURNER TYPE FOR GAS INSTALLATIONS Burner Manufacturer RIELLO BURNER MODEL 40 GS10 40 GS10 Blast Tube Penetration Dimension A mm 110 110 Burner Manufacturer...

Страница 26: ...HAMWORTHY HEATING LTD LILLIPUT HE 500001047 F 21 INSTALLER SITE ADDRESS BOILER TYPE BOILER SIZE S UNIT NO S SERIAL NO S FLUE NOTES...

Страница 27: ......

Страница 28: ......

Отзывы: