C1.3 Materials.
Materials used for the flue system must be mechanically robust, resistant to internal and external corrosion, non-
combustible and durable under the conditions to which they are likely to be subjected. Consideration must be
given to avoid possible freezing of condense water traps and pipework
C1.4 Suction
The flue system must be designed acknowledging that there is a positive pressure of generated by the boiler combustion
fan available to the flue system. It is recommended that a draught stabiliser is fitted to the flue system where the
draught is likely to become –ve at the boiler connection.
C1.5 Disconnection
Provisions should be made for disconnection of the flue pipe for servicing. It is advisable that bends are fitted with
removable covers for inspection and cleaning as appropriate.
WARNING: THE FLUE SYSTEM MUST BE SELF SUPPORTING AND NOT PRESENT
A RISK TO PEOPLE IN OR AROUND THE BUILDING.
C1.6 Flue Discharge
The flue system must ensure safe and efficient operation of the boiler to which it is attached, protect the
combustion process from wind effects and disperse the products of combustion to the external air. The flue must
terminate in a freely exposed position and be so situated as to prevent the products of combustion entering any
opening in a building. Where the flue diameter is less than 204mm (8”) diameter a terminal must be fitted. Where
the flue is of a larger size, consideration should be given to the fitting of a flue discharge terminal or grille to stop
ingress of birds etc.
C1.7 Surface Temperatures
Combustible materials in the vicinity of the boiler and flue shall not exceed 65°C during boiler operation. The flue
shall not be closer than 50mm to any combustible material, except where it passes through such material with a
non-combustible sleeve when the air gap may not be less than 25mm.
C1.8 Location
The flue system must not be placed or fitted where there is undue risk of accidental damage to the flue pipe or
undue danger to persons in the vicinity. Check that the flue and chimney are clear from any obstruction. Purewell
VariHeat he boilers are suitable for installation in a balanced compartment in accordance with the requirements
of BS 6644. Consult Hamworthy Heating Technical Department for help or assistance if in doubt.
C1.9. Condensate Discharge
Consideration should be given to possible freezing of condense water traps and pipework. This must be avoided
at all times by routing pipework within the building, where possible. It is strongly recommended that on modular
installations, the common header and chimney system must have separate drains for condensate disposal -
refer
to section 4.5.
Содержание 65he
Страница 2: ......
Страница 30: ...HAMWORTHY HEATING LTD 24 PUREWELL VariHeat he 500001170 K Figure 8 2 1 3 Operation and display philosophy...
Страница 40: ...HAMWORTHY HEATING LTD 34 PUREWELL VariHeat he 500001170 K Figure 8 3 11 Operating phases...
Страница 41: ...HAMWORTHY HEATING LTD 35 PUREWELL VariHeat he 500001170 K Figure 9 0 Boiler Wiring Schematic...
Страница 65: ......
Страница 66: ......