HAMPTON BAY H27-NG Скачать руководство пользователя страница 1

FPI FIREPLACE PRODUCTS INTERNATIONAL LTD.  6988 Venture St., Delta, BC  Canada, V4G 1H4

918-812

MODELS:      H27-NG Natural Gas       H27-LP Propane   

04/12/11

H27 Direct Vent Gas Fireplace

Owners & 

Installation Manual

WARNING:  
If the information in these instructions are not 
followed exactly, a fi re or explosion may result 
causing property damage, personal injury or loss 
of life. 

FOR YOUR SAFETY
Do not store or use gasoline or other fl ammable 
vapours and liquids in the vicinity of this or any 
other appliance.

Installation and service must be performed by 
a qualifi ed installer, service agency or the gas 
supplier.

FOR YOUR SAFETY

What to do if you smell gas:
  Do not try to light any appliance
  Do not touch any electrical switch: 

do not use any phone in your 
building.

  Immediately call your gas supplier 

from a neighbour's phone. Follow 
the gas supplier's instructions.

  If you cannot reach your gas sup-

plier, call the fi re department.

This appliance may only be 
installed in an aftermarket 
permanently located, manu-
factured (USA only) or mobile 
home, where not prohibited by 
local codes.

This appliance is only for use 
with the type of gas indicated 
on the rating plate. This ap-
pliance is not convertible for 
use with other gases, unless 
a certifi ed kit is used.

Tested by:

Installer: Please complete the details on the back cover 

and leave this manual with the homeowner.

Homeowner: Please keep these instructions for future reference.

www.hampton-fi re.com

Содержание H27-NG

Страница 1: ...Y What to do if you smell gas Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot reach your gas sup plier call the fire department This appliance may only be installed in an aftermarket permanently located manu factured USAonly or ...

Страница 2: ...pliance and has been designed to provide you with all the warmth and charm of a wood fireplace at the flick of a switch The model H27 has been approved by Warnock Hersey for both safety and efficiency As it also bears our own mark it promises to provide you with economy comfort and security for many trouble free years to follow Please take a moment now to acquaint yourself with these instructions ...

Страница 3: ...it 21 Residential and Manufactured Homes Mobile Home 23 Minimum horizontal termination Installations 23 Dura Vent Termination Kit 24 Horizontal terminations 25 Vertical 26 Terminations 26 Converting Class A Metal Chimney or 28 Masonry Chimney to Direct Vent System 28 Cathedral Ceilings 29 High Elevation 29 Gas Connection 29 Aeration Adjustment 30 Gas Pipe 30 Pressure Testing 30 Conversion from NG ...

Страница 4: ... locaux ou en l absence de tels r glements selon les codes installation ANS Z223 1 National Fuel Gas Code ou CSA B149 1 en vigueur Not for use with solid fuels FOYER AU GAZ À ÈVACUATION è d I Alimentation électrique Ne doit pas être utilisé avec un combustible solide Serial No No de serie 918 813 Maximum Input Minimum Input Orifice size Altitude Maximum Input Minimum Input Orifice size Altitude FA...

Страница 5: ...directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS 4 INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless upon ins...

Страница 6: ...6 Hampton H27 Direct Vent Freestanding Gas Stove DIMENSIONS Shown with optional side shelves ...

Страница 7: ... HIGH TEMPERATURES THE APPLIANCE SHOULD BE LOCATED OUT OF TRAFFIC AND AWAY FROM FURNITURE AND DRAPERIES WARNING FAILURE TO INSTALL THIS APPLIANCE CORRECTLY WILL VOID YOUR WARRANTY AND MAY CAUSE A SERIOUS HOUSE FIRE CLOTHING OR OTHER FLAMMABLE MATERIAL SHOULD NOT BE PLACED ON OR NEAR THE APPLIANCE CHILDREN AND ADULTS SHOULD BE ALERTED TO THE HAZARDS OF HIGH SURFACE TEMPERATURES ESPE CIALLY THE FIRE...

Страница 8: ...actory equippedwithameanstosecuretheunit This Hampton Mobile Manufactured Home listed appliance comes equipped with a dedicated 8 ground lug to which an 18 gauge copper wire from the steel chassis ground must be attached Thisappliancemayonlybeinstalledin an aftermarket permanently located manufactured USA only or mobile home where not prohibited by local codes This appliance is only for use with t...

Страница 9: ...Minimum Horizontal Termination e Dura Vent Termination Kit 5 Make gas connections Refer to the Gas Con nection section Test the pilot Must be as per diagram in the Maintenance Instruction section If converting to Propane make changes prior Refer to the Conversion from Natural Gas to Propane section 6 Test Gas Pressure Refer to the Pressure Testing section 7 Install standard and optional features R...

Страница 10: ...nt Termination requirements see Exterior Vent Terminal Locations section OPTIONAL FAN INSTALLATION Fan Kit Contains Qty Description 1 Fan Assembly c w green wire attached 1 Thermodisc 1 power cord 2 2 1 4 x 20 hex nut 1 Fan Speed Control 1 a Remove the rear access panel on the back of the stove by removing the 2 screws under the rear panel 2 Disconnect the red and grey wires Top Control Panel Asse...

Страница 11: ...re attaching the rear access panel the valve wires and the fan wires need to be connected Re connect the red and grey valve wires 13 Slide the Rear Access Panel back into position and secure with 2 screws Connect the fan wires WARNING Electrical Grounding Instructions This appliance is equipped with a three pronged grounding plug for your protection against shock hazard and should be plugged direc...

Страница 12: ...d listed as direct vent heater systems by Warnock Hersey These units use the balanced flue technology Co Axial system The inner liner vents products of combustion to the outside while the outer pipe draws outside combustion air into the combustion chambertherebyeliminatingtheneedtouseheated room air for combustion and losing warm room air up the chimney Note These flue pipes must not be connected ...

Страница 13: ...f center line extended above meter regulator assembly 36 90cm a J Clearance to service regulator vent outlet 36 90cm K Clearance to non mechanical air supply inlet to building or the combustion air inlet to any other appliance 12 30cm 9 23cm L Clearance to a mechanical air supply inlet 3 91cm above if within 10 3m horizontally 72 1 8m 36 90cm b M Clearance above paved sidewalk or a paved driveway ...

Страница 14: ...N A Adjustable Length 3 10 Galvanized N A N A N A 4DAL N A TC 4DLT Adjustable Length 3 10 Black N A N A N A 4DALB N A TC 4DLTB Adjustable Length 7 Galvanized N A N A 4D7A N A N A N A Adjustable Length 7 Black N A N A 4D7AB N A N A N A Extension Pipe 8 1 2 Galvanized 46DVA 08A N A N A N A N A N A Extension Pipe 8 1 2 Black 46DVA 08AB N A N A N A N A N A Adjustable Length 12 Galvanized N A N A 4D12A...

Страница 15: ...ation 36 N A N A N A N A N A TM 4ST36 Basic Horizontal Termination Kit A Disc 4DT HKA 4DHTK2 4DHTKA SV SHK N A Horizontal Termination Kit B 46DVA KHA Changed Components 4DT HKB 4DHTK1 4DHTKB SV HK N A Vertical Termination Kit Disc 4DT VKC 4DHTK 4DHTK SV FK N A FPI 946 506 P Vent Guard Optional for AstroCap 946 205 Vinyl Siding Shield for Riser Vent Terminal 510 994 Rigid Pipe Adaptor Must use with...

Страница 16: ... Direct Vent American Metal Products Ameri Vent Direct Vent Security Secure Vent Selkirk Direct Temp and ICC Excel AstroCapTM is a proprietary trademark of FPI Fireplace Products International Ltd Dura Vent and Direct Vent Pro are registered and or proprietary trademarks of Simpson Dura Vent Co Inc This product has been evaluated by Intertek for using a Rigid Pipe Adaptor in conjunction with Durav...

Страница 17: ...two 45o elbows If the vent is ENCLOSED in a chase min size 9 x 9 maintain a 1 1 4 clearance to combustibles May be installed in Manufactured Mobile Homes after first sale Horizontal Terminations for All Venting Systems The shaded areas in the diagram below show all allowable combinations of vertical runs with hori zontal terminations Maximum one 90O elbow two 45o elbows equal one 90o elbow Propane...

Страница 18: ...f 8 feet total vertical and max 8 feet total horizontal Please note min 1 foot between 90o elbows is required With these options maxi mum total pipe length is 30 feet with minimum of 6 feet total vertical and maximum 8 feet total horizontal Please note minimum 1 foot between 90o elbows is required One 90o elbow Two 45o elbows One 90o elbow Two 45o elbows H H1 V Vent restrictor position A fully ope...

Страница 19: ... 1 foot between 90o elbows is re quired Option H H1 V A 2 Max 2 Min B 3 Max 3 Min C 4 Max 4 Min D 5 Max 5 Min E 6 Max 6 Min Withtheseoptions max total pipelengthis30feetwithmin of6feettotalverticalandmax 6 feet total horizontal Please note min 1 foot between 90o elbows is required One 90o elbow Two 45o elbows One 90o elbow Two 45o elbows V1 V H Vent restrictor position A fully open refer to the Ve...

Страница 20: ... be attached to two 3 76mm co linear aluminium flex running the full length of the chimney See the Venting Arrangements chart below for minimum and maximum flue lengths See chart below for minimumdistancesfromroof Periodicallycheck that the vent is unrestricted Masonry chimneys may take various contours which the flexible liner will accommodate However keep the flexible liner as straight as possib...

Страница 21: ...arter collar and the 90o elbow Crimpedsectionofrigidpipe seats into the 90o elbow Only cut the uncrimped side of pipe Dismantle all pipe sections including vent terminal 2 Assembleatrialfittodeterminethevertical centerline for the vent termination a Cut a 9 1 2 x 9 1 2 241mm x 241 mm square hole on both the interior and exterior wall Adapter Trim Collar 4 ID Liner Spacer Spring Thimble Cover Termi...

Страница 22: ...event water from entering and to make a tight seal between the cap and the standoff 7 Stretch the 4 dia flex liner out fully and get a trial fit of the liner onto the 4 dia starter collar 8 Cut the 4 dia flex liner to the desired size Hint leave an extra 12 to 16 of length this will make the final assembly easier to work with 9 Secure the 4 dia flex liner to the 4 adapter with Mill Pac and 3 of th...

Страница 23: ...irements Determine the minimum clearance to combustibles from the rear of the unit to the wall It is also important to note the wall thickness Before cutting the vent hole through the wall ensure that ALL vent and termination clearances see the Exterior Vent Terminal locations section will be met Ifthisisanoutsidecorner theminimumdistance between the vent and the outside corner is 6 15cm See F on ...

Страница 24: ...al to horizontal type installations Warning Alwaysmaintainrequired clearances air spaces to nearby combustibles to prevent a fire hazard Do not fill air spaces with insulation Theminimumclearancerequirementsbetween the outer wall of the vent pipe and nearby combustible surfaces is 1 1 2 except when passingthroughawall ceiling oratthetermina tion where the use of a firestop or wall thimble reduces ...

Страница 25: ...etrated is constructed of non combustible material i e masonry block or concrete a 7 diameter hole is acceptable a The horizontal run of vent should have a 1 4 inch rise for every 1 foot of run towards the termination Never allow the vent to run downward This could cause high tempera tures and may present the possibility of a fire b Thelocationofthehorizontalventtermination on an exterior wall mus...

Страница 26: ...llation NOTE For best results and optimum performance with each approved vent ing system it is highly recommended to apply Mill Pac sealant supplied to every inner pipe connection Failure to do so may result in drafting or perform anceissuesnotcoveredunderwarranty Silicone red RTV is optional Diagram 5 c Before connecting the vent pipe to the vent termination slide the black decorative wall thimbl...

Страница 27: ...erformance issues not covered under warranty Silicone red RTV is optional 4 Assemble the desired lengths of black pipe and elbows necessary to reach from the appliance adapter up though the Round SupportBox Insurethatallpipesandelbow connections are in the fully twist locked position and sealed Diagram 10 The upper half of the flashing is installed under the roofing material and not nailed down un...

Страница 28: ...nd ma sonry chimneys cleanout doors and caps or plugs for cleanout tee fittings and ash dumps shall be secured in place and sealed before installing a Direct Vent system within the chimney If the appliance shuts off during operation contact a qualified service person to de termine if a negative pressure and or leaky chimneyconditionexists Donotoperatethe appliance until the problem is corrected Ap...

Страница 29: ...in 5 0 w c Propane min 12 0 w c Manifold Pressure Natural Gas 3 8 0 2 w c Propane 11 0 2 w c 7 Ensure vent is vertical and secure the base of the flashing to the roof with roofing rails slide storm collar over the pipe section and seal with a mastic 8 Install the vertical termination cap by twist locking it Notes a For multistorey vertical installations a Ceiling Fire stop is required at the secon...

Страница 30: ...o IN and or OUT pres sure tap s using a 5 16 ID hose 4 Light the pilot and turn the valve to ON posi tion Read manometer 5 The pressure check should be carried out with theunitburningandthesettingshouldbewithin the limits specified on the safety label 6 When finished reading manometer turn off the gas valve disconnect the hose and tighten the screw clockwise with a 1 8 flat screwdriver Note Screws...

Страница 31: ...k Generator Switch C W Wire 1 910 078 Battery Size AA Energizer En91 2 910 199 Clip Wire Holder 1 910 903 Wire Fan To Power Cord Ground 30 in Installation of the LPG Conversion Kit 1 Shut off the gas supply 2 a Lift off the Cast Top and Cast Front remove the glass front refer to Glass Replacement section in the H25 H27 manual and carefully remove the logs and lava rock refer to Log Installation se...

Страница 32: ...ench as shown in Fig 4 rotate the screw clockwise until snug do not overtighten 13 Verify that if the conversion is from NG to LPG the screw must be re assembled with the red o ring visible Fig 5 14 Re assemble the black protection cap Fig 6 WARNING Also check that the pilot and main burner injectors are appropriate for the gas type Fig 1 Fig 2 Fig 3 Fig 4 LPG Configuration Red o ring visible Fig ...

Страница 33: ... DC sparker generator wire through the hole of the DC spark heat shield 2 First remove the Piezo Ignition Wire from the Piezo Ignitor Then remove the Piezo Ignitor from the control panel 7 Attach the ground wire to the grounding stud 8 Attach the Piezo ignition wire to the DC Sparker Piezo Ignitor 14 Attach the heat shield to the DC sparker then mount onto the stove using the velcro already attach...

Страница 34: ...helogsarebrokendonotusetheunituntiltheyare replaced Broken logs can interfere with the pilot operation The gas log kit Part 350 930 contains the following a Rear Log b Left Side Front Log c Right Side Front Log d Center Front Log e Embers 902 156 f Platinum Embers 946 669 supplied with packaged manual Left Front Log Pin Pin Right Front Log Tabs NOTE Rear Tabs NOTE This is a rear view The Front Rig...

Страница 35: ...und where the embers are placed Avoid stacking platinum embers 6 Place the center cross log D so it rests in the notch located on the top of the rear log position as shown below Logs must be oriented as shown below 7 Test fire to ensure proper light off make sure flame flows smoothly from one end of burner to the other If there is any flame hesitation check that area for any blockage of the burner...

Страница 36: ...ional programmable thermostat but any 250 750 millivolt rated non anticipator type thermostat that is CSA ULC or UL approved may be used Thermostat Wire Table CAUTION Do not connect the millivolt wall thermostat wires to the 120V wires toinstallthereceiverandthereceptaclebox pro tection from extreme heat is very important Run wires from the fireplace to that location use Thermostat Wire Table 2 Co...

Страница 37: ...supply is needed for the fan blower operation Caution Ensure that the wires do not touch any hot surfaces and are away from sharp edges FINAL CHECK Before leaving this unit with the customer the installer must ensure that the appliance is firing correctly This includes 1 Clocking the appliance to ensure the cor rect firing rate rate noted on label at 15 minutes 2 If required adjusting the primary ...

Страница 38: ...pronged grounding plug for your protection against shock hazard and should be plugged directly into a properly grounded three prong receptacle Do not cut or remove the grounding prong from this plug For PROPANE Units and Units Equipped with DC Spark Boxes For installation of the DC Spark Box refer to the LP Conversion instructions in this manual ...

Страница 39: ... gas control knob so indicator points to OFF position and allow 5 minutes for any gas in the combustion chamber to escape 3 Turn gas control knob counterclockwise so indicator points to the PILOT position Depress the gas control knob fully Depress the igniter button several times until the pilot lights After approximately one minute releasethegascontrolknob Thepilotflame should continue to burn If...

Страница 40: ... floor WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electric switch do not use any phone in your building Immediately call your gas supplier from a neighbors phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department C Us try to repair it call a qualified service technician Force or attempted repair may result in a ...

Страница 41: ...rebox Different types and thicknesses of steel will expand and contract at different rates resulting in some cracking and ticking sounds will be heard throughout the cycling process WARNING CHILDREN AND ADULTS SHOULD BE ALERTED TO THE HAZARDS OF HIGH SURFACE TEMPERATURE AND SHOULD STAY AWAY TO AVOID BURNSORCLOTHINGIGNITION YOUNG CHILDREN SHOULD BE CAREFULLY SUPERVISED WHEN THEY ARE IN THE SAME ROO...

Страница 42: ...ENT The unit should never be used with broken logs Turn off the gas valve and allow the unit to cool before opening door to carefully remove the logs The pilot light generates enough heat to burn someone If for any reason a log should need replacement you must use the proper replacement log The position of these logs must be as shown in the diagram under Log Installation Note Improper positioning ...

Страница 43: ...thermocouple with a 9 mm metric wrench 16 Remove pilot nut with an 11 mm wrench 17 Remove valve to orifice nut with a 13 16 wrench 18 Remove inlet pipe with pipe wrench Note orientation of 90o elbow 19 Remove two 2 phillips head M5 screws on each side of the valve 20 Remove valve and remove gas out 90o brass fitting Note orientation of fitting INSTALLING VALVE ASSEMBLY 1 To install a new valve ass...

Страница 44: ... Description 49 Fan Air Divider 50 W260260 Top Relief Frame Gasket 51 942 117 Top Relief Frame 52 W260280 Top Relief Plate Gasket 53 770 066F Top Relief Plate 54 Capscrew 1 4 x 1 3 4 NC 55 Side Shield 57 W260108 Gasket for Inner Flue 58 W842051 Gasket for Flue Adaptor 59 945F Dura Vent Collar 79 Stove Base 114 Wire Tie 115 Wire Tie Mount 910 704 Wire Harness Fan End 134 356 003 Rear Panel 135 280 ...

Страница 45: ...nt Freestanding Gas Stove 45 Hampton H27 Direct Vent Freestanding Gas Stove 45 PARTS LIST PARTS LIST 4 2 57 5 5 5 5 6 30 79 44 79 45 55 144 30 6 1 54 54 51 52 53 50 19 24 59 38 146 149 148 137 136 135 134 150 MAIN ASSEMBLY ...

Страница 46: ...70 Orifice Gasket 66 910 038 Pilot Assy S I T 3 flame NG 910 039 Pilot Assy S I T 3 flame LP 67 Pilot Holder 68 W840470 Pilot Assembly Gasket 69 Valve Shield 70 Valve Bracket 71 260 042 Valve Gasket 73 Valve Cover Plate 74 Valve Access Door 75 350 930 Log Set Part Description 80 350 530 Burner Assembly Natural Gas 82 350 020 Log Tray Rear 86 260 565 Air Shutter Gear Assembly Female 87 904 565 Hex ...

Страница 47: ...id if requested It is the general practice of FPI to charge for larger higher priced replacement parts and issue credit once the replaced component has been returned to FPI and evaluated for manufacturer defect The authorized selling dealer is responsible for all in field service work carried out on your Hampton product FPI will not be liable for results or costs of workmanship from unauthorized s...

Страница 48: ...___________________________________________________________ Phone ___________________________________________________________ Date Installed ______________________________________________________ Serial No __________________________________________________________ Register your Regency warranty online www regency fire com Reasons to register your product online today View and modify a list of all ...