8.1
RS-232 Connection (for XVG/eXVG with RS-232 interface)
PC COM Port
(DB9M Connector)
XVG/eXVG Terminal
Block
Wire Color
(If XVG/eXVG is
supplied with optional
harness)
Signal
Pin #
Signal
Pin #
SERIAL RX
2
SERIAL TX
39
WHT/ORN/BLU
SERIAL TX
3
SERIAL RX
40
WHT/ORN/YEL
SERIAL RTN
5
SERIAL RTN
41
WHT/ORN/GRN
Table 14: RS-232 Interface Connection
8.2
RS-485 Connection (for XVG/eXVG with RS-485 interface)
PC COM Port
Through RS232-
RS485 Converter
XVG/eXVG Terminal
Block
Pin #
Signal
Pin #
Wire Color
(If XVG/eXVG is supplied
with optional harness)
TD(B)+
TXD-485A
(SERIAL TX)
39 WHT/ORN/BLU
TD(A)-
RXD-485B
(SERIAL RX)
40 WHT/ORN/YEL
GND (Optional)
SERIAL RTN
41
WHT/ORN/GRN
Table 15: RS-485 Interface Connection
9
XVG/eXVG Modbus Parameters
9.1
Setup Parameters
Set up parameters are write-able parameters used to setup and control all XVG/eXVG
operations. The following notes applied to all parameters:
-
Register Number: This is the Modbus address of the register in the XVG/eXVG.
-
All registers are readable.
-
RO: Read-only. The register is read-only.
-
W0: Open access for writing by any user.
-
W1: A Customer or Factory level password must be entered before writing is
allowed.
-
W2: A password must be entered and IDM_SETUPCONNECT (register no.
3005) set to 1 before writing is allowed.
-
W3: A factory level password must be entered before writing is allowed.
-
W4: A factory level password must be entered and IDM_SETUPCONNECT set
to 1 before writing is allowed.
11