50
PART 8. MAINTENANCE
C. CONDENSATE TRAP CLEANING INSTRUCTIONS
1) Turn off the power to the EVO.
2) Place a bucket under the
condensate trap. Use caution
when removing the clean-out cap,
as the trap is full of condensate
and it may be hot.
3) Remove the condensate clean-
out cap, and be sure the bucket
is under the open drain trap
assembly to catch the debris and
water.
4) Rinse out the clean-out cap in a
sink to remove any dirt or buildup
that may have accumulated.
5) Condensate drain assembly
should now be checked for non-
restricted flow throughout the
entire assembly.
6) Reinstall the clean-out cap on the
condensate trap.
7) Turn on the power to the EVO.
8) Make sure the hose from the
condensate trap is not submerged
too far into the neutralizer, there
should be an air gap between the
highest level of condensate and the
outlet hose from the trap.
9) Monitor the condensate drain
until flow has been established.
NOTE:
The condensate trap and entire drain system attached to it (above the
neutralizer) should be cleaned at least once every year.