halstrup-walcher PS27 Скачать руководство пользователя страница 6

 

Operating Instructions PS27 

 

1.4 Symbols 

The symbols below in these operating instructions point to the risks, which could arise 
in handling the equipment: 

 

 

 
WARNING!

 

It points to a hazard possibly extending from 
injures through to death should the instructions 
not be followed. 

 

 
CAUTION!

 

 
It points to a hazard which could cause 
considerable damage should the instructions not 
be followed. 

 

 

INFORMATION!

 

 
This indicates information, which is vital for 
proper appliance operations 

2. 

Description of the pressure transmitter 

Type PS27 differential pressure transmitters are pneumatic/electrical sensors for 
pressure testing (positive/negative gauge pressure and differential pressure) 
purposes. They are typically used in air-conditioning and ventilation technology e.g. 
pressure testing in ventilation ducts. The transmitter's core is a piezoresistive 
pressure transmitter.  

3. 

Startup 

3.1 Functional Description 

PS27 pressure transmitters are of the precision type and despite their sturdiness they 
should still be treated with care. Installation right next to heat and radiation sources 
e.g. radiators should be avoided as this may lead to measurement errors arising. 
Ideally the appliance should be vertically mounted on a wall not subject to any 
vibrations. To stop any condensed water entering the measurement cell, the 
transmitter together with the hose connections for positive gauge pr and 
negative gauge pressure - should be pointing downwards.  

 

The right pressure sign must be used in keeping with the following table when 
connecting the pressure to the transmitter: 

 

Type of pressure 

Connect pressure to  

Example 

pos. gauge pressure 

+ input 

0...1 kPa 

neg. gauge pressure 

- input 

0...- 500 Pa 

Differential pressure 

Higher pressure at + input 
lower pressure at - input 

0...125 Pa e.g via a differential 
pressure producer (e.g. measuring 
orifice) 

Symmetrical pressure ranges  + input 

 200 Pa 

Asymmetrical pressure 
ranges 

Input of the larger pressure 
range 

-300 Pa...+ 1 kPa 
(here connect to + input) 

Содержание PS27

Страница 1: ...ential Pressure Transmitter PS27 halstrup walcher GmbH Stegener Stra e 10 D 79199 Kirchzarten Germany Phone 49 0 76 61 39 63 0 Fax 49 0 76 61 39 63 99 E mail info halstrup walcher com Internet www hal...

Страница 2: ...Code 2022 The manufacturer owns the copyright to this instruction manual It contains technical data instructions and drawings detailing the device s features and how to use them It must not be copied...

Страница 3: ...must be given to these operating instructions and in particular to the associated safety instructions Do contact the manufacturer should you not understand all the sections Be heedful of the operatin...

Страница 4: ...er 6 3 Startup 6 3 1 Functional Description 6 3 2 Connections for Four Wire version standard in the device 7 3 3 Connections for Two Wire System Option 8 3 4 Connections M12 plug 8 4 Resetting Offset...

Страница 5: ...ator Only instructed persons as assigned by the plant operator are to operate the transmitter Do not perform any functional test involving compressed or breathable air This would otherwise damage thos...

Страница 6: ...ional Description PS27 pressure transmitters are of the precision type and despite their sturdiness they should still be treated with care Installation right next to heat and radiation sources e g rad...

Страница 7: ...gram on the appliance cover circuit board mount ST4 Pin Connection name Meaning 1 24V Power supply input 24VAC DC 2 GND Ground for power supply 3 OUT Voltage or current output 4 GND Ground for output...

Страница 8: ...ed via the input assigned for this purpose The user must ensure that the appliance is not subjected to any pressure during the calibration process as this might lead to a wrong offset value which in t...

Страница 9: ...ching of 4 measuring ranges into the appliance has been undertaken by the manufacturer The switches 1 and 2 of SW can be used to select the measuring range in question before the transmitter is switch...

Страница 10: ...sor s output so that any adjusted time delay will also cause a delay in relay triggering 9 In case of Malfunctions Fault description Possible cause Corrective action No output signal Supply voltage is...

Страница 11: ...o Fitting 4 or 6mm Output signals 0 2 10 V RL 50 kOhm 0 4 20 mA RL 500Ohm 4 20 mA two wire 17 32 V RL 500Ohm Switching contact optional max 230 VAC 6 A min 500 mW Display optional 3 digit LCD Overpres...

Страница 12: ...PS27 12 11 Dimensional Drawing For more information on our measurement technology products please visit our homepage at www halstrup walcher de en products measurement technology 7100 004354L_PS27 doc...

Страница 13: ...Operating Instructions PS27 13 12 Certificates of Conformity...

Страница 14: ...Operating Instructions PS27 14...

Страница 15: ...Operating Instructions PS27 15 Notes...

Отзывы: