background image

Supplied By www.heating spares.co  Tel. 0161 620 6677

CONTENTS

INTRODUCTION

1

The 

Halstead Best db 30,40,50 and 60

are wall mounted,

fan assisted balanced flue natural gas boilers incorporating a
cast iron heat exchanger. The appliance incorporates automatic
direct burner ignition and electronic temperature control. It
features an attractive white enamelled casing with a removable
front panel which when removed enables the appliance to be
fitted within a standard kitchen wall unit. (Remove top and
bottom panels of kitchen unit). 

The appliances are supplied with a standard concentric air and
flue duct suitable for flue lengths of up to 820mm (32in). The
duct assembly is connected to the boiler via an elbow which can
exit the appliance in any horizontal direction. Additional flue kits
are available to extend the flue length up to a maximum of
3.121m (123in), and further kits are available to provide up to
two bends in the flue, although the maximum length must be
reduced 
(as detailed in these instructions) to accommodate extra bends. 
A vertical outlet kit is also available for installations where an
outside wall is not accessible and it is required to fit the duct
"through the roof". Installation using the standard flue kit (with or
without straight extensions) is described in the main text of these
instructions. This booklet describes installations involving raised
flue systems, extra elbows, and the vertical outlet kit. 

The appliance can be installed from inside the room without
access to the external wall providing that a wall liner is fitted and
the wall thickness is less than 0.5m (19in). The wall liner is
available as an optional extra. See Section 4 for further details.
(Note: If the vertical outlet kit is to be used, access to the roof is
necessary). 

These appliances are most suitable for fully pumped, open
vented or sealed systems, but may be used on an open vent
system utilising gravity domestic hot water and pumped central
heating 

Fully Pumped:

If thermostatic radiator valves are fitted it is

recommended that a bypass is installed to provide a suitable
water circuit should all the thermostatic radiator valves be shut.
This bypass circuit should incorporate a minimum volume of 
7 litres. It may utilise one radiator which should be fitted with
lockshield valves only. 

Gravity:

It is recommended that when used on a gravity

domestic hot water application a Honeywell "C Plus" plan or
equivalent is fitted to the system to give suitable control over the
domestic hot water temperature. The cylinder thermostat should
be set NO higher than 60°C. The Honeywell "C Plus" will allow
the pump overun to operate (should it be necessary) without
warming the radiators when the domestic hot water only is on.
The bypass should have a water volume, (7 litres minimum) but
should NOT incorporate any radiators. The flow sensing
temperature is limited to 60°C in the gravity mode, when the CH
pump is off. This is to prevent the cylinder of DHW from
overheating. 

Page

1

INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

2

TECHNICAL SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . 1

2.1

Performance data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

2.2

Connection sizes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

2.3

General data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

2.4

Minimum clearance and overall dimensions . . . . . . . . . . . . . . 1

2.5

Air/flue duct specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

2.6

Exploded diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

3

INSTALLATION REQUIREMENTS . . . . . . . . . . . . . . . . . . . 7

3.1

Statutory requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

3.2

Boiler location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

3.3

Flue terminal position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

3.4

Ventilation requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

3.5

Gas supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

3.6

Electrical supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

3.7

Water systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

4

INSTALLING THE APPLIANCE . . . . . . . . . . . . . . . . . . . . 11

4.1

Unpacking the appliance. . . . . . . . . . . . . . . . . . . . . . . . . . . 11

4.2

Preparing the wall. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

4.3

Preparing the appliance . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

4.4

Mounting the appliance. . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

4.5

Flue/air duct installation . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

4.6

Gas connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

4.7

Water connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

4.8

Wiring instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

5

COMMISSIONING & TESTING  . . . . . . . . . . . . . . . . . . . 18

5.1

Open vented water systems  . . . . . . . . . . . . . . . . . . . . . . . . 18

5.2

Sealed water systems  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

5.3

User instructions  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

6

ROUTINE SERVICING . . . . . . . . . . . . . . . . . . . . . . . . . . 19

6.1

Main burner assembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

19

6.2

Fan assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

19

6.3

Heat exchanger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

19

6.4

Re-assemble and re-commission . . . . . . . . . . . . . . . . . . . . . 

19

7

PARTS REPLACEMENT. . . . . . . . . . . . . . . . . . . . . . . . . . 20

7.1

Overheat cut off device . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

20

7.2

Flow temperature thermistor . . . . . . . . . . . . . . . . . . . . . . . . 

20

7.3

Air pressure switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

20

7.4

Ignition PCB (fully enclosed). . . . . . . . . . . . . . . . . . . . . . . . . 

20

7.5

Aquastat PCB & Housing . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

7.6

Potentiometer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

7.7

Main burner injector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

7.8

Gas valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

7.9

Main burner. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

7.10

Ignition electrode (front left hand of burner). . . . . . . . . . . . . . 21

7.11

Flame sensing electrode (rear left of burner) . . . . . . . . . . . . . 21

7.12

Fan assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

7.13

Combustion chamber insulation . . . . . . . . . . . . . . . . . . . . . . 22

8

INTERNAL WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . 22

8.1

Functional flow wiring diagram . . . . . . . . . . . . . . . . . . . . . . 22

8.2

Illustrated wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . 22

9

FAULT FINDING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

10

SHORT PARTS LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

11

Supplementary instructions for Flue systems with 
vertical terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

12

Supplementary instructions for Flue systems incorporating an
additional 90° elbow. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

SE-DUCT Applications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Содержание Best db 30

Страница 1: ...st 50 G C No 41 333 52 Best 60 G C No 41 333 53 SUPPLY PRESSURE 20 mbar 0 0 8 6 TO BE LEFT WITH THE USER FOR USE WITH NATURAL GAS ONLY G20 CAST IRON WALL MOUNTED FAN ASSISTED BOILER B R I T I S H M A...

Страница 2: ...ne radiator which should be fitted with lockshield valves only Gravity It is recommended that when used on a gravity domestic hot water application a Honeywell C Plus plan or equivalent is fitted to t...

Страница 3: ...kw 8 79 11 72 14 65 17 58 Btu hr 30000 40000 50000 60000 kw 5 86 8 79 11 72 Btu hr 20000 30000 40000 60000 kw 11 13 14 75 18 43 22 37 Btu hr 37975 50315 62893 76326 kw 7 71 11 42 14 84 Btu hr 26316 3...

Страница 4: ...CT VERTICAL SOCKET 90 ELBOW NON FLANGED STANDARD DUCT 90 ELBOW NON FLANGED EXTENSION DUCT 2 d FLUE WITH 90 BEND TERMINAL DUCT STANDARD DUCT FLANGED ELBOW 90 ELBOW NON FLANGED EXTENSION DUCTS 2 e HORIZ...

Страница 5: ...a Standard flue assembly using either side or rear outlet Flue length L measured from the boiler outlet centre line to the outside wall face max 820mm Maximum wall thickness Wr Rear outlet 620mm max M...

Страница 6: ...rd flue assembly Equivalent Length Shown is 3045mm Where Lb is 919mm and Lw is 820mm Lw is measured to the outside wall face Fig 4b As 4a but with one additional extension in length Lb Equivalent Leng...

Страница 7: ...t length shown is 2325mm Where Lh measured from the top of the boiler casing to the centre line of the extra elbow 551mm and length Lw measured from the centre line of the extra elbow to the outside w...

Страница 8: ...LOADED DIAGRAM Drawing amended 7 05 99 79 48 17 47 59 12 4 11 7 13 8 80 5 64 63 81 37 38 39 60 43 21 62 77 19 67 68 66 76 78 26 25 56 49 19 71 75 49 65 73 46 34 35 36 61 55 28 44 15 23 18 19 22 14 30...

Страница 9: ...T be installed so that the terminal is exposed to the external air 3 1 STATUTORY REQUIREMENTS 3 2 BOILER LOCATION SAFETY INSTALLATION AND USE REGULATIONS 1984 AS AMENDED It is the law that all gas app...

Страница 10: ...temperature difference of 11 C between the flow and return pipes on the boiler The resistance through each model of boiler at the required flow rate may be found in Section 2 3 3 7 WATER SYSTEMS An o...

Страница 11: ...MOTORISED VALVE VALVED BY PASS LOOP WATER CONTENT 7 LITRES MINIMUM Fit either two motorised valves or one 3 way motorised valve COLD WATER STORAGE OPEN VENT INDIRECT CYLINDER AUTOMATIC AIR VENT MINIM...

Страница 12: ...dequate clearance for fitting the right hand inner case The central heating flow must be connected to the 22mm connection on the top manifold The central heating return must be connected to the 22mm c...

Страница 13: ...ned and make the necessary hole s in the ceiling roof Proceed to k f ADDITIONAL ELBOW OR FLANGED DUCT WITH ELBOW Using the wall mounting template and the dimensional information given in section 2 4 2...

Страница 14: ...se with the four screws previously removed 4 5 AIR FLUE DUCT INSTALLATION 4 5 1 PREPARING THE AIR FLUE DUCTS If the wall thickness is less than 800mm 31in the air flue duct may be fitted without acces...

Страница 15: ...n 425mm L 76mm MAX 319mm 17mm 19 ASSEMBLING THE FLUE SYSTEM TOP 1 SLIDE EXTERNAL SEALING RING UPTO FLUE TERMINAL L 2 STANDARD DUCT Push ducts fully over elbow and drill two 3 3mm dia holes Secure with...

Страница 16: ...SEALING RING FIBRE SEAL FITTED 4 5 3 INSTALLING THE AIR FLUE DUCT FROM OUTSIDE THE BUILDING Flue hole diameter 100mm wall liner not necessary a Secure the flue elbow with seal to the appliance using 4...

Страница 17: ...conomical heating system However should the boiler be installed for use with a combined PUMPED CH GRAVITY DHW system the small jumper plug in the front of the control box must be repositioned in the g...

Страница 18: ...HEATING VALVE HOT WATER VALVE 230V MAINS INPUT OR A B C 4 5 6 8 NOT USED 5 2 1 9 3 8 2 1 10 3 1 2 3 L N E BROWN BLUE GREY ORANGE GREEN YELLOW BROWN BLUE GREY ORANGE GREEN YELLOW 1 3 2 1 2 4 5 2 1 5 1...

Страница 19: ...THERMOSTAT 2 1 E N L L N E 9 8 3 2 1 9 2 3 BOILER PUMP 6 3 N L 3 4 N L 6 4 3 2 1 Honeywell ST699B 1002 Link L 5 8 ST 799A ST6400 ST6300 PROGRAMMER 2 Pump Live 1 Switched Live L Permanent Live 230V 50...

Страница 20: ...he boiler and system should now be allowed to reach its maximum working temperature and examined for water leaks o Turn off the heating system and drain whilst still hot p Refill and vent ensuring all...

Страница 21: ...of the boiler complete with its electrodes d Inspect and if necessary clean the burner assembly If either electrode shows signs of damage or wear replace it e Inspect and if necessary clean the main i...

Страница 22: ...ISOLATE the mains electrical supply remove the front painted panel by sliding up and then away from the boiler remove the right hand portion of the inner case by first pulling off the control knob the...

Страница 23: ...e the valve manifold assembly from the boiler 7 9 MAIN BURNER a Remove the four screws securing the left hand inner case Remove the case by sliding it forwards and off the appliance b Remove the combu...

Страница 24: ...EN YELLOW RED RED WHITE WHITE PINK BROWN BLUE GREEN WHITE GREEN YELLOW GREEN YELLOW BLUE BROWN BLACK PURPLE BLUE RED WHITE WHITE RED BLUE RED BROWN RED BLACK BLACK GREEN YELLOW 2 1 N L ORANGE BLACK OR...

Страница 25: ...ignition lockout turn thermostat to maximum setting and ensure programmer is switched on before pressing reset button YES NO Replace the fan Is there 230V at the fan motor Replace the fan YES NO Chec...

Страница 26: ...rode All 1 500574 5 Gas Valve Without Ignition Device All 1 500569 6 Ignition Device For Gas Valve All 1 500570 7 Aquastat PCB All 1 600513 8 Thermistor All 1 500572 9 Overheat Cut Off Device All 1 50...

Страница 27: ...nd flue are to be positioned and make the necessary hole in the wall s for the air flue duct as defined in section 4 2 c Install the boiler as described in section 4 with the exception of the flue sys...

Страница 28: ...ax 01787 474588 SERVICE HOTLINE 01203 351424 Halstead Boilers are continuously improving their products and therefore reserve the right to change specifications without prior notice and accept no liab...

Отзывы: