37
WATER HOUSING GROUP SET
9.11
THERMISTORS - DHW OR HEATING
The thermistors are immersed in the waterways hence slight water
loss is likely during this operation. Provision should be made to
collect a small amount of water underneath the appliance.
a)
Remove the casing front panel and lower the controls fascia
panel as described in section 9.6 step (a).
b)
Isolate the appliance from the system as follows:
If replacing DHW thermistor turn off the inlet water valve (see
section 5) and open all DHW taps to empty the DHW circuit).
If replacing CH thermistor, turn off the boiler flow and return
from the system using the isolation valves as shown in section 5.
c)
Unclip and remove the electrical connector plug from the
thermistor. Unscrew the thermistor from the waterway.
d)
Replace the thermistor and re-assemble in reverse order. Ensure
the copper washers are correctly fitted to provide a sealed
joint. Re-commission the system as described in section 5.
PLATE HEAT
EXCHANGER
SOCKET HEAD
CAPSCREWS (2)
(Secure plate
heat exchanger)
DHW
FLOWSWITCH
(Pink Wires)
LARGE BRASS NUT
(Water flow
regulator behind)
DHW PRESSURE
SENSING PIPES
PRESSURE RELIEF
VALVE
BYPASS
(Underneath)
FLOW SWITCH
SECURING
SCREWS (2)
PRIMARY/FLOWSWITCH
(Violet Wires)
LARGE
HEXAGON
NUT
‘O’ RING SEAL
FILTER
WATER FLOW REGULATOR
(Small diameter towards small
hexagonal nut)
SMALL
HEXAGONAL
NUT
PUMP
DHW
THERMISTOR
(Black Wires)
CH
THERMISTOR
(Grey Wires)
9.10
CH/DHW MICROSWITCH
a)
Remove the casing front panel and lower the controls fascia
panel as described in section 9.6 step (a).
b)
Release the appropriate micro switch assembly from the spindle
by sliding out the retaining spring clip (Refer to figure 37).
c)
Unscrew the three screws fixing the plastic housing halves
together and slide the micro switch forwards to release it from
the housing.
d)
Transfer the electrical connections to the new micro switch, fit the
new micro switch and re-assemble in reverse order.
9.9.1
a)
On completion of replacing the PCB the CH maximum heat
input will require setting.
b)
Connect a suitable manometer to the gas inlet and burner
pressure test points (see Fig. 35).
c)
Set the clock to the ON position (I) and ensure any external
controls are calling for heat.
d)
Set the Main Switch to the Heating & Water position and turn
the temperature control knobs to high.
e)
Wait until appliance has lit (in CH mode only) and turn
potentiometer P3 (max CH set point) to the required burner
pressure between 9.7 and 1.3 mbar (originally factory set at
6.3mb)
PCB CH HEAT INPUT SETTING
PROCEDURE
29
36
OVERHEAT THERMOSTAT
PHIAL
PIPE CLIP
ELECTRICAL
CONNECTIONS
SECURING NUT &
OVERHEAT RESET BUTTON
c)
Remove carefully the control knob clips holding the control
knob in position and pull out the three control knobs from the
front of the fascia panel (Fig. 30).
d)
Unclip the electrical connector plugs from the PCB (refer to
section 7).
e)
Remove the six self taping screws securing the PCB
f)
Remove the PCB. Re-assembly is in reverse order
Содержание Ace High
Страница 8: ...8 EXPLODED DIAGRAM for key no references see spare parts catalogue Drawing amended 8 6 00 6 ...
Страница 25: ...INTERNAL WIRING DIAGRAMS 7 7 1 FUNCTIONAL FLOW WIRING DIAGRAM 23 ...
Страница 26: ...7 2 ILLUSTRATED WIRING DIAGRAM 24 ...
Страница 40: ...Ace Ace High Wickes Combi 82 102 05 04 ACE ACE HIGH WICKES COMBI 82 102 ...