Maximum flue resistance permitted for a twin flued
system = 52 Pa
Minimum flue resistance permitted for a twin flued
system = 23.5 Pa
Flue Component
Flue Resistance (Pa) Part Number
Twin Flue Adaptor (required)
9.5
-
Air Inlet Terminal (required)
3
-
Chimney Terminal (required)
0.5
-
80 mm dia straight duct 1 metre
1
956101
80 mm dia straight duct 2 metre
2
956102
90° Elbow (80/80)
8
956100
45° Elbow (80/80)
4
956099
This flue system kit is designed for installations where the air intake position
is different than the flue duct exit point. The kit comprises of a twin adaptor
from which the air intake is taken from the adjacent outside wall (see
example Figure 3g) and the flue duct is routed vertically through the roof.
It has to be noted that the flue duct is under pressure when the
appliance is in operation and the duct can leak poisonous carbon
monoxide if the duct components are not correctly assembled. It is
not
recommended to route the flue duct through living space areas, i.e.
bed rooms, living rooms etc.
For installation details refer to the instructions provided with the twin
flued kit.
For C53 flue systems the terminal for the supply of combustion air and
for the evacuation of combustion products shall not be installed on
opposite walls of the building.
FLUE LENGTHS
Length supplied in standard kit - horizontal
815mm
Max horizontal length
(from boiler to chimney - 60/100mm)
2000mm
Min horizontal length
(from boiler to chimney - 60/100mm)
100mm
Max vertical length
(from boiler to chimney - 60/100mm)
2000mm
Min vertical length
(from boiler to chimney - 60/100mm)
200mm
Length supplied in standard kit - vertical
(available in 10m, 20m and 30m length)
N/A
FLEXITUBE MUST BE PURCHASED AS AN ACCESSORY TO COMPLETE THE KIT
(See below)
Flexi tube min length
5m
Flexi tube max length
30m
ACCESSORIES
Description
Part No.
Resistive Length
HORIZONTAL - 60/100 Accessories
Flue extension duct - 500mm
956092
450mm
Flue extension duct - 1000mm (Incl. 1 x support bracket)
956093
950mm
93° extension elbow
956091
1550mm
45° extension elbow (pair)
956090
775mm
Air inlet duct - included in kit
N/A
N/A
Straight adapter (60/80) - included in kit
N/A
N/A
91.5° adapter elbow (80/80) - included in kit
N/A
N/A
Support bracket - 100mm
840517
N/A
93° flanged elbow - included in kit
956082
N/A
Vertical turret socket
956087
N/A
VERTICAL - Accessories
Flexi tube - 10m
956110
10m
Flexi tube - 20m
956111
20m
Flexi tube - 30m
956112
30m
Straight duct (80) - included in kit
N/A
N/A
Chimney terminal - included in kit
N/A
N/A
NOTE: RESISTIVE LENGTH INFORMATION ONLY REQUIRED FOR COAXIAL FLUE PARTS.
THE CORRUGATED (FLEXI TUBE) FLUE PARTS ARE FIXED AND ALL PARTS ARE REQUIRED
FOR EVERY APPLICATION.
PART NO. 956080
2.7
KIT F: TWIN FLUE SYSTEM (C53) –
7