Traditional concentric flue system, Figure 3a, with a maximum length of
5000mm. The flanged flue elbow is designed with 3° slope towards the
appliance so that the condensate can easily drain off. It has to be
considered that for every metre horizontal flue length the terminal exit
centreline is approx. 45 mm higher than the elbow’s centreline.
The standard telescopic terminal is 615mm max length and 430mm min
length, but can be cut to a minimum flue length of 250mm, which is
suitable for single, 100mm (4"), brick walls.
3a
TERMINAL (C13) - PART NO.956120
2.5.1
KIT A + TELESCOPIC HORIZONTAL WALL
TERMINAL (C33) - HBL PART 956081
2.5.2
KIT B VERTICAL CONCENTRIC FLUE
3b
Standard concentric (ø100/60) vertical flue application, Figures
3b, 3c, through roof attics with a maximum length of 12000mm.
The kit comprises of the roof terminal, flashing kit, vertical
adaptor with sampling point and bracket.
The maximum length is measured from the top of the appliance
casing to the underside of the air cowl.
For installation details refer to the flue kit instructions.
Fig 3(c) Offset vertical flue.
‘a’ measured from boiler flue outlet centre line to the centre line
of the extension elbow.
‘b’ measured from the top of the boiler to the underside of the air
cowl.
Maximum allowable length of a + b = 8900mm
3c
If the standard horizontal terminal is likely to cause nuisance to a
neighbour or buildings, because of excess pluming, then this
particular flue kit raises the flue gas outlet point to a higher
elevation with the minimum amount of changes. The flue gas duct
is teed-off from the concentric part and covered by an 80mm
outer tube to protect the flue duct from freezing. The air in-take
remains at the lower level (see Figure 3d).
If choosing this option then the external flue duct length should be
taken into account when calculating equivalent flue length.
For installation details refer to the flue kit instructions.
FLUE KIT (C13) – PART NO. 956084
2.5.3
2.5.3 KIT C: HORIZONTAL ANTI-PLUME
Dimensions from vertical terminals to opening
windows should be in line with Figure 5.
Roof terminal
with rain cover
and pitched roof
flashing kit.