a)
Check that the gas supply is turned ON and the gas service cock
is OPEN.
b)
Slacken the screw in the gas cock inlet pressure test point and
connect a suitable manometer. Refer to Figure 20.
c)
Turn the control knob fully anticlockwise to the standby position.
d)
Switch on the electrical supply. The display reads ‘o’.
e)
Turn the control knob to the desired temperature position and fully
open any DHW tap. The fan should start and after a few seconds
ignition will commence.
f)
If the burner fails to light the fan will stop. Initially this may be due
to air in the gas supply line. The boiler will automatically have five
attempts at ignition. It may be necessary to turn the control knob fully
anti-clockwise to the reset/Standby position and repeat (d). (See
section 5.4).
g)
When the boiler has lit the display will show ‘H.’ Allow the
appliance to run for at least 10 minutes and check that the gas
supply pressure measured at the appliance inlet pressure test point is
20 ± 1 mbar for natural gas.
h)
Close the DHW tap and ensure that the burner goes out (the
display reads ‘o’) and the pump stops after an over-run period of 5
minutes.
i)
Ensure that the room thermostat (if fitted) is calling for heat. Turn
the clock override switch to the ‘I’ position. The ignition sequence will
commence and when flame is detected the display will show ‘C.’
j)
Set the clock to the desired times by setting the tabs.
k)
Slide the clock override switch to the ‘timed’ position and check
the operation of the clock and room thermostat (if fitted).
5.2
COMMISSIONING THE APPLIANCE
Refer to Figures 19 & 20
If, at any time during the commissioning procedure, it
is required to prevent the appliance from modulating,
set the control knob to the Service position (fully
clockwise).
If the gas inlet pressure is outside the required value check
that the gas pipe is of the correct diameter or contact the
gas provider to adjust the gas meter governor.
19
20
THIS BOILER IS FACTORY SET, SO THAT NO
COMBUSTION OR GAS INLET RATE CHECK IS
REQUIRED. HOWEVER IF THE APPLIANCE FAILS TO
OPERATE CORRECTLY CONTACT THE HALSTEAD
BOILERS LTD SERVICE HELPLINE: 08450 710780.
IF A COMBUSTION & GAS INLET RATE CHECK IS TO BE
CARRIED OUT THEN REFER TO SECTION 6.1
!
PRESSURE GAUGE
7 SEGMENT DISPLAY
CONTROL KNOB
CLOCK OVERRIDE
SWITCH
ARROW INDICATES
CURRENT TIME
CONTINUOUS ON
TIMED
OFF
TABS IN = OFF PERIOD
TABS OUT = ON PERIOD
24hr TIME CLOCK
INLET PRESSURE TEST POINT
(REMOVE SCREW AND CONNECT
MANOMETER)
GAS VALVE
20