Halstead ACE HE 24 Скачать руководство пользователя страница 12

10

INSTALLATION REQUIREMENTS

3

3.1

STATUTORY REQUIREMENTS

GAS SAFETY (INST

ALLATION AND USE) REGULATIONS

1996 (AS AMENDED)

The appliance is suitable only for installation in GB and IE and

should be installed in accordance with the rules in force.
In GB, a CORGI Registered Installer must carry out the installation.
It must be carried out in accordance with the relevant requirements
of the:

Gas Safety (Installation and Use) Regulations

The appr

opriate Building Regulations either The Building

Regulations, The Building Regulations (Scotland), Building
Regulations (Northern Ireland).

The W

ater Fitting Regulations or Water Byelaws in Scotland.

The Current I.E.E Wiring Regulations.

Wher

e no specific instructions are given, reference should be

made to the relevant British Standard code of Practice.
In Ireland (IE), the installation must be carried out by a Competent
Person and installed in accordance with the current edition of I.S.813
"Domestic Gas Installations", the current Building Regulations and
reference should be made to the current ETCI rules for electrical
installation.
It should also be in accordance with the relevant recommendations in
the current editions of the following British Standards and Codes of
Practice: BS 5449, BS 5546, BS 5440-1, BS 5440-2, BS 6798, BS
6891, Institute of Gas Engineer document IGE/UP-7, BS 7074
(expansion vessel) and IS813 for IE.

IMPOR

TANT NOTE:

Manufactur

er's instructions must NOT be

taken in any way as overriding statutory obligations.

3.3

FLUE TERMINAL POSITION

Detailed r

ecommendations for flue installation are given

in BS 5440-1. The following notes are for general
guidance.
a)

The appliance MUST be installed so that the ter

minal is exposed

to the external air.

b)

It is impor

tant that the position of the terminal allows free

passage of air across it at all times.

c)

It is ESSENTIAL TO ENSURE that pr

oducts of combustion

discharging from the terminal cannot re-enter the building or any
other adjacent building, through ventilators, windows, doors, other
sources of natural air infiltration, or forced ventilation/air
conditioning.

d)

The minimum acceptable dimensions fr

om the terminal to

obstructions and ventilation openings are specified in Figure 5.

e)

If the ter

minal discharges into a pathway or passageway check

that combustion products will not cause nuisance and that the
terminal will not obstruct the passageway.

f)

Wher

e the lowest part of the terminal is fitted less than 2000 mm

(78 in) above the ground, above a balcony or above a flat roof to
which people have access, the terminal MUST be protected by a
purpose designed K6 terminal guard (optional extra: Part No. 951507).

g)

The air inlet / flue outlet MUST NOT be closer than 25 mm (1 in)

to combustible material.

h)

Condensing appliances have a tendency to for

m a plume of

water vapour at the terminal under certain operating conditions.  This
is normal but positions where this would cause damage or a
nuisance should be avoided. Consideration should be given to the
dispersal of the plume in terms of adjacent surfaces and
neighbouring properties. A special flue terminal, (Kit C), is available
to raise the flue discharge point; use of this terminal will limit the
maximum flue length available. For further information contact:
Halstead Boiler Ltd, Service Help Line: 01926 834834.

3.2

APPLIANCE LOCATION

The following limitations MUST be obser

ved when

siting the appliance:
a)

The appliance is not suitable for exter

nal installations.  The

position selected for installation should be within the building,
unless otherwise protected by a suitable enclosure and MUST allow
adequate space for installation, servicing and operation of the
appliance and for air circulation around it (Section 2.4 and 3.4).

b)

This position MUST allow for a suitable flue system and ter

minal

position.  The appliance must be installed on a flat vertical wall,
which is capable of supporting the weight of the appliance and
any ancillary equipment.

c)

If the appliance is to be fitted in a timber framed building it

should be fitted in accordance with the British Gas publication
‘Guide for Gas Installations In Timber Frame Housing’, Institute of
Gas Engineers document IGE/UP-7.  If in doubt, advice must be
sought from the Local Gas Supplier.

d)

The appliance is appr

oved to a protection rating of IP20.

Therefore if the appliance is to be installed in a room containing a
bath or a shower, any electrical switch or control utilising mains
electricity must be so situated that it cannot be touched by a person
using the bath or shower.  Attention is drawn to the requirements of
the current BS 7671 (I.E.E Wiring Regulations) and in Scotland the

electrical provisions of the Building Regulations applicable in
Scotland.

3.4

VENTILATION REQUIREMENTS

Detailed r

ecommendations for air supply are given in BS 5440-2.

The following notes are for general guidance.

a)

It is not necessar

y to have a purpose provided air vent in the

room or internal space in which a room-sealed appliance is
installed.

b)

Cupboar

d or compartment ventilation is not necessary for a

room-sealed appliance providing that the minimum clearances are
maintained.

c)

Wher

e an open flued, (B23), system is used, then an air vent

must be provided in the same room or internal space as the flue
duct air inlet, with a minimum free-area of at least:

Ace HE 30

117 cm

2

Ace HE 24

87.5 cm

2

Содержание ACE HE 24

Страница 1: ......

Страница 2: ...Leads 30 9 3 Gas Control Valve 31 9 4 Fan 32 9 5 Burner 33 9 6 Combustion Chamber Front Insulation 33 9 7 Combustion Chamber Rear Insulation 33 9 8 Heat Exchanger 34 9 9 Pump Head Only 34 9 10 Diverte...

Страница 3: ...ene and wash your hands before eating drinking or going to the lavatory If you do suffer irritation to the eyes or severe irritation to the skin seek medical attention Gas and Electricity Consumer Cou...

Страница 4: ...x kW 19 7 25 4 50 30 C Btu h 67300 86700 Net kW 18 4 22 9 Central Heating Input Btu h 62800 78200 Max Rate Gross kW 20 4 24 8 Btu h 69700 84700 Net kW 5 6 6 9 Central Heating Input Btu h 19100 23600 M...

Страница 5: ...y Ltr 1 8 2 1 Integral expansion vessel capacity Ltr 8 Maximum heating system water content using fitted expansion vessel 0 75 bar Ltr 84 Electrical supply 230V 50Hz Fuse at 3A Internal fuse T4H 4A 25...

Страница 6: ...lat roof flashing plate Vertical flue kit Part no 956081 Flue system application Vertical flue kit Part no 956081 Split pipe vertical flue outlet kit Part no 956080 with flat roof flashing plate Raise...

Страница 7: ...6081 2 5 2 KIT B VERTICAL CONCENTRIC FLUE 3b Standard concentric 100 60 vertical flue application Figures 3b 3c through roof attics with a maximum length of 12000mm The kit comprises of the roof termi...

Страница 8: ...In replacement installations the chimney has to be cleared of debris and all flue parts Chimney plate Flexible corrugated plastic flue liner 80mm according to EN 14471 Max length 30m Min length 5m KIT...

Страница 9: ...mm and 500 mm long each duct extends the flue length by up to 950 mm and 450 mm respectively 93 Extension Elbow Allows an additional bend in the flue and has an equivalent length of 1550 mm This elbow...

Страница 10: ...ON PLUME DIVERTER TERMINAL INSTALLATION INSTRUCTIONS The diverter allows the terminal clearance to be reduced as follows see diagrams below Clearance H From a surface facing the terminal 600mm Clearan...

Страница 11: ...2 9 APPLIANCE HYDRAULIC CIRCUITS 4 CH MODE DHW MODE 9...

Страница 12: ...y a purpose designed K6 terminal guard optional extra Part No 951507 g The air inlet flue outlet MUST NOT be closer than 25 mm 1 in to combustible material h Condensing appliances have a tendency to f...

Страница 13: ...ain is routed to outside it should be to a drain or soak away and any external pipe work should be in 32 mm Insulation to protect from freezing in cold weather conditions is also advisable 3 6 GAS SUP...

Страница 14: ...rol panel This can be viewed by lowering the bottom front panel PRESSURE RELIEF VALVE A pressure relief valve set to 3 bar 43 5 psi is supplied with the appliance however it will start to open at appr...

Страница 15: ...SIGN Note No automatic bypass required however it is recommended to leave one radiator open to ensure pump over run function It is also recommended to fit TRV s on all radiators except in the rooms wi...

Страница 16: ...paper template in the required position ensuring that the necessary clearances are achieved Ensure square ness by hanging a plumb line b Mark the position of the largest wall fixing holes Refer to Fig...

Страница 17: ...system pipes to the central heating flow and return valves using 22mm pipe work 12 VIEW OF CONNECTIONS ON REAR OF BOILER 4 5 GAS CONNECTION Refer to Figure 12 Connect the gas supply pipe to the gas s...

Страница 18: ...no less than 15mm diameter copper pipe to the outlet The pipe outlet should be positioned so that the discharge of water or steam can be noticed but cannot create a hazard to the occupants of the prem...

Страница 19: ...lue system extension ducts as necessary referring to the flue kit instructions and fit to the flue elbow e Fit the flue terminal to the flue system ensuring that the duct joints are not disturbed and...

Страница 20: ...rectly and does not leak 5 Drain the entire system using the manual drain valve to flush out any debris and refill to 0 2 bar above the system design pressure between 0 5 and 1 0 bar by repeating the...

Страница 21: ...e the DHW tap and ensure that the burner goes out the display reads o and the pump stops after an over run period of 5 minutes i Ensure that the room thermostat if fitted is calling for heat Turn the...

Страница 22: ...return thermisters which monitor the appliance s operating temperature Abnormal temperatures will cause the appliance to go to lockout and the LED display will show code 1 Allow the appliance to cool...

Страница 23: ...ive during frost conditions e Explain the function of the control knob and how to reset the appliance Emphasise that if cut outs persists the appliance should be turned off and the installer or servic...

Страница 24: ...ce vertical flue adaptor If suitable equipment to analyse the flue gas is available remove the plastic cap and fit a 6 mm inside diameter sample tube When the appliance is operating at maximum output...

Страница 25: ...nect the ignitor plug earth lead and detection plug from the ignitor and detection electrodes e Unscrew the screw holding the gas valve lead plug and disconnect the plug f Disconnect the electrical le...

Страница 26: ...g a soft brush If either the electrode or the ceramic insulation shows signs of damage or wear replace the electrode s and their gasket b Check that the alignments of the ignition and detection electr...

Страница 27: ...ection 6 1 e Check the operation of the appliance in both CH and DHW modes as applicable f Remove the manometer and tighten the inlet pressure test point sealing screw g Test for gas tightness 6 8 RE...

Страница 28: ...26 INTERNAL WIRING DIAGRAM 7 7 1 FUNCTIONAL FLOW WIRING DIAGRAM 29...

Страница 29: ...PLAY FASCIA PANEL Refer to Figure 31 The Digital Display shows error code 3 in a lockout condition To RESET the boiler turn the control knob fully anti clockwise to the 8 3 FAULT FINDING CODES In the...

Страница 30: ...ated which prevents the appliance from firing in CH mode for 5 minutes Ensure that the control is not in this mode by removing power from the control and restoring it after a delay of 10 seconds RESET...

Страница 31: ...tem failure Failure of internal self checking system Check PCB No flame E BCC error No flame Incorrect missing BCC Reseat or replace BCC if fitted Check CH flow and return Water flow failure Check pum...

Страница 32: ...the electrical supply leads d Unscrew the two screws holding the ignitor unit remove ignitor unit e Fit the new ignitor unit g Re assemble in reverse order ensure that the ignitor unit is orientated a...

Страница 33: ...rectly then check for gas soundness 36 34 35 If a new gas valve is fitted it must be adjusted to operate within the quoted CO2 values see Combustion set up table below A suitable calibrated flue gas a...

Страница 34: ...ed from valve body 4 5mm 4 5mm to top of screw If the gas control valve is changed then when the appliance is running the flue gas CO2 should be measured refer to section 6 1 and compared to the value...

Страница 35: ...ective mask is worn when changing or handling the insulation material Refer to Figure 42 a Ensure supply voltage is isolated and that the gas supply is isolated b Remove the gas control valve fan burn...

Страница 36: ...Remove the saddle brackets and slide the heat exchanger forwards and out p Re assemble in reverse order check integrity of the flow and return pipe O rings and fibre washers and replace as necessary...

Страница 37: ...g the hydroblock onto the mounting studs and remove the hydroblock j Align the replacement hydroblock against the mounting studs and secure using the three screws k Re assemble in reverse order ensure...

Страница 38: ...necessary and check for water leaks Note the pressure relief valve should not be used to drain the system 9 13 PRESSURE RELIEF VALVE Refer to Figure 48 a Ensure supply voltage is isolated b Disconnec...

Страница 39: ...he nut connecting the plate heat exchanger to the DHW water isolating cock pipe j Lift up the plate heat exchanger and remove k Fit the replacement plate heat exchanger using new case seals as necessa...

Страница 40: ...ew the auto air vent and fit replacement e Re assemble in reverse order ensure that all joints and seals are correctly re fitted f Open the isolating cocks and vent air from the system using the manua...

Страница 41: ...n the boiler using the manual drain tap on the CH flow water isolating cock figure 18 in conjunction with the manual bleed valve located on the top LHS of the heat exchanger refer to Figures 44 and 54...

Страница 42: ...ion vessel 1 451020 13 Pressure Relief Valve 1 300734 14 Flow Return temperature thermister 2 500661 15 Flue thermister ACE HE 1 500662 16 Plate Heat Exchanger 1 451015 17 Plate Heat Exchanger Filter...

Страница 43: ...55 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 41...

Страница 44: ...Direct Line 01787 475557 Fax 01787 474588 Service Helpline 01926 834834 Training 01926 834838 Email sales halsteadboilers co uk or service halsteadboilers co uk or training halsteadboilers co uk Webs...

Отзывы: