11  Trouble Shooting Chart 

Problem 

Solution 

Normal Supply LED not illuminated 

Check supply voltage it should be set to 27.2VDC. 
Nominal fault voltages are - Low  = (<18VDC)  
High = (> 28VDC )  

FACP Earth Fault LED illuminated 

Check  all  input  and  output  cabling  and  wiring  assemblies 
for short to ground 

FACP System Fault LED illuminated  Ensure correct panel configuration 

Check all connections for loose wiring 

FACP  Warning  System  Fault  LED 
illuminated 

Check correct E.O.L is fitted 
Check wiring is connected correctly 

RS485  Communication  Bus  not 
working 

Refer FACP LCD. This may identify where there is a break 
in the communication line 
Check  the 

SmartTerminal

  Diagnostic  Config  LED  is 

flashing.  If  not  the  FACP  is  not  communicating  with  the 
SmartTerminal. Check the RS485 cabling. 
If flashing check the 

SmartTerminal’s

 address. 

 

Содержание Ampac SmartTerminal AS7240

Страница 1: ...Fire detection and evacuation solutions that save lives SmartTerminal AS7240 Installation and Operation Guide MAN2990 1...

Страница 2: ...n Cabling 7 3 1 SmartTerminal Termination Board Interconnection 7 3 2 FACP Comms 7 4 Firefinder Plus Installation Cabling 8 4 1 SmartTerminal Termination Board Interconnection 8 4 2 FACP Comms 8 5 Set...

Страница 3: ...to be monitored by local personnel and limited control is required Front panel controls that allow the resetting of alarms and activation silencing of alarm devices Enabling operational access to the...

Страница 4: ...ress extremes of temperature abuse etc is at an easily accessible height and such that the indicators are at eye level Typical locations for the panel are the first and most obvious point of contact f...

Страница 5: ...en detaching this connector as it is necessary to depress the small locking tab to unlock the connector from its base To reconnect the cable the connector must first be correctly aligned then pushed i...

Страница 6: ...PANEL CLIPS INTO FRONT DOOR INSERT KEY TABS HERE TO UNLOCK ENCLOSURE CONNECT BRD82LTB CN1 TO BRD82ICC CN5 BRD82ICC BRD82LTB HINGE PIN 1 HINGE PIN 2 Figure 2 Exploded View BRD82LTB KNOCKOUTS CN1 R 6mm...

Страница 7: ...O PS LOOP 1 LOOP 2 B RS485 RS485 SHD 2 3 4 COM 1 2 AUX OUT2 2 3 4 3 1 4 1 ETH 27V 0V DIAGNOSTICS RS232 RS485 TERM LOAD RESET HLI PORT PWR IN N O C N C N O C N C N O C N C RELAY 1 RELAY 2 RELAY 3 COMM...

Страница 8: ...RN20 LOOP COMMS BRD82LTB2 TB1 TB4 M1 M2 CN2 CN5 CN4 COMMUNICATIONS EXTENDER BOARD FACP MAIN BOARD RJ45 CABLE TO AVAILABLE 27VDC CONNECTOR 3 WAY SHIELDED COMMS CABLE SHIELD 24VDC C15 C12 ZD2 ZD3 TH2 TH...

Страница 9: ...sts of the code version number current address and four adjustment markers These markers A A C and C are used to indicate the keys that adjust the address and LCD contrast Use the PREVIOUS A and NEXT...

Страница 10: ...odule s information while double clicking on the add on will open its editing dialog box The SmartTerminal Menu Right clicking on the SmartTerminal add on parent item from the Tree View opens the menu...

Страница 11: ...o this panel entitled Panel Add on 1 and Panel Add on 5 respectively Double clicking on an entry in the list opens the editing dialog box for that particular SmartTerminal Editing Figure 10 The SmartT...

Страница 12: ...nal added to reference 2 Select the smart terminals associated Edit button to open the individual editing window Figure 12 Smart terminal editing window In this editing window you can choose what info...

Страница 13: ...tTerminal should automatically transition to the normal state Should a failure occur on power up press the RESET button located on the LCD PCB see Figure 5 and check the address is correct Normal The...

Страница 14: ...will present an audible feedback beep to the user KEYSWITCH Access levels There are two levels of access Access level 1 only the previous and next front panel controls are operative All other control...

Страница 15: ...Silence Resound Used to silence the alarm devices Toggle function to resound any silenced alarm devices if the ALARMS SILENCED indicator is lit Only alarm devices configured with the silence able attr...

Страница 16: ...f any of the alarm devices sounders and or strobes have been disabled and flashes if any of the alarm devices sounders and or strobes are in fault Disable has priority over fault Illuminated steady if...

Страница 17: ...ers configured to be silence able have been silenced in response to any activation sources indicating the resound function is active Illuminated when there are one or more faults on the system Faults...

Страница 18: ...d on the LCD stating the system is not normal and the operator should see the FACP Alarm If configured the screen format for reporting loop sensor zone fire condition is FIRE ORIGIN Zzzz RECENT Zzzz T...

Страница 19: ...ce faults or device disables present on the system The highest priority current system status will be displayed and can be one of the following listed in order of highest to lowest priority 1 SYSTEM A...

Страница 20: ...uirements Optional 27VDC Power Supply Batteries 27VDC 18VDC 12 4mA back light off buzzer off 43 8mA back light on buzzer on 2 core 1 5 to 2 5mm 1 8A plus 400mA Battery Charging 12Ahr 27VDC OUTPUTS Aux...

Страница 21: ...Fault LED illuminated Ensure correct panel configuration Check all connections for loose wiring FACP Warning System Fault LED illuminated Check correct E O L is fitted Check wiring is connected correc...

Страница 22: ...22 UNCONTROLLED DOCUMENT NOTE Due to AMPAC s commitment to continuous improvement specifications may change without notice...

Отзывы: