[Notes on System Design]
•
Never bundle control cables and input/output cables with high-voltage and large-current carrying
cables such as power supply cables. Keep these cables at least 200 mm away from the power
supply or high-voltage cables. Otherwise, malfunction may occur due to noise.
•
For use in a nuclear energy facility, or other facility of such official importance, please consult
your local distributor.
[Notes on Installation]
•
Operate (or store) MONITOUCH under the conditions indicated in this manual and related
manuals. Failure to do so could cause fire, malfunction, physical damage or deterioration.
•
Understand the following environmental limits for use and storage of MONITOUCH. Otherwise,
fire or damage to the unit may result.
- Avoid locations where there is a possibility that water, corrosive gas, flammable gas,
solvents, grinding fluids or cutting oil can come into contact with the unit.
- Avoid high temperature, high humidity, and outside weather conditions, such as wind, rain or
direct sunlight.
- Avoid locations where excessive dust, salt, and metallic particles are present.
- Avoid installing the unit in a location where vibration or physical shock may be transmitted.
•
Equipment must be correctly mounted so that the main terminal of MONITOUCH will not be
touched inadvertently.
•
Tighten the MONITOUCH mounting screws to the specified torque. Excessive tightening may
distort the panel surface. Loose tightening may cause MONITOUCH to come off, malfunction or
be short-circuited.
•
Tighten terminal screws on the power input terminal block equally to a torque of 0.5 N•m.
•
Check the appearance of MONITOUCH when it is unpacked. Do not use the unit if any damage
or deformation is found.
•
MONITOUCH has a glass screen. Do not drop or give physical shock to the unit.
[Notes on Cable Connection]
•
Connect the cables correctly to the terminals of MONITOUCH in accordance with the specified
voltage and wattage. Over-voltage, over-wattage or incorrect cable connection could cause fire,
malfunction or damage to the unit.
•
Be sure to establish a ground of MONITOUCH. The FG terminal must be used exclusively for
the unit with the level of grounding resistance less than 100
Ω
.
•
Prevent any conductive particles from entering into MONITOUCH. Failure to do so may lead to
fire, damage or malfunction.
(To be continued)
CAUTION
Содержание Monitouch V7
Страница 1: ...V7...
Страница 3: ......
Страница 17: ......
Страница 57: ......
Страница 95: ...2 38 3 Errors Displayed on the V7 Series Please use this page freely...
Страница 97: ......
Страница 150: ...1 Ethernet 2 FL net OPCN 2 3 MELSECNET 10 4 CC Link 5 OPCN 1 6 T LINK 7 PROFIBUS DP Network Communications...
Страница 151: ......
Страница 207: ......
Страница 343: ...5 136 29 Automationdirect PLC Please use this page freely...