HAKARU PLUS CORPORATION Tel. 81-6-6300-2195

05/12/16   TFL-B101Q DS (FL6)

Page 3

Overview of Display Modes, Scaling Capabilities and Operating Modes

Input Hi

Input Low

std

Input Hi

Input Low

std Inv

FLB202Q MODE O1

+ Input 

- Input 

+ Input 

- Input 

+ Input 

- Input 

0

0

0

biploar center zero

Input Hi

Input Hi

Input Hi

Input Low Input Low

Input Low

center zer

o

1/2

1/2

1/2

Standard Scaling

 

Standard display mode selected and 

scaled so bar increases as input signal 

increases from Low to Hi.

Halfway Zero Point

 

Center point display mode selected and 

scaled, so the bar increases upwards or 

downwards from the center point, for sig-

nals that are greater or less than half the  

calibrated full scale range respectively. 

When the input is equal to half the full 

scale range, only the center segment will 

be on.

Inverse Scaling

Standard display mode selected and 

scaled so the bar increases as the 

input signal decreases from Hi to Low.

Bipolar Center Zero

 

Center point display mode selected and 

scaled, so the bar increases upward from 

zero, for increasing positive inputs and 

downward from zero for increasing neg-

ative inputs. When the input is zero, only 

the center segment will be on.

CH1

CH2

Standard Display Mode

CH1

CH2

Center Zero Display Mode

min_max

SP1

SP2

SP3

SP4

dual bar rvsd

SP1

SP2

SP3

SP4

Display with 4 Set Points 

 

With Standard display or Center point 

mode selected, the setpoints are 

 indicated by an 

ON

 segment outside 

the bar display area and by an 

OFF

 

segment inside the bar display area.

Horizontal or Reverse Mounting 

Meters can be mounted horizontally 

in the panel and for those applica-

tions that require an opposite growth 

of the bar, the meter can be verti-

cally or horizontally mounted upside 

down 

Mode 0 Channel Inputs

MODE

1

3

2

Horizontal and Reverse Mounting 

with Custom Face Plate Installed

Mode 3 Hysteresis Band between SP1 & SP2

This mode enables the Hysteresis function.  In order for Hysteresis to function, SP2 must be set to a value greater than SP1, and SP2 should 

be selected as High (h) Setpoint (See page 7).  When these conditions are met, and Mode 3 is selected, then a Hysteresis band is created 

for the SP1 relay, with the upper limit of SP2 and the lower limit of SP1. SP2 relay continues to operate 

normally.

•For a tank filling application SP1 is set to a Low (L) Setpoint. SP1 relay can control a pump that fills 

the tank. With Mode 3 selected, SP1 relay activates for inputs less than the SP1 level.  Once activated, 

SP1 relay will stay ON until the tank is filled to the SP2 level.

•For a tank emptying application SP1 is set to a High (h) Setpoint. SP1 can control a pump that emp-

ties the tank. With Mode 3 selected, SP1 relay activates for inputs greater than the SP2 level.  Once 

activated, SP1 relay will stay ON until the tank is emptied to the SP1 level.

MODE

1

3

2

Tank Filling

SP1

Tank starts
filling when
level is at or
below SP1

SP2

SP1

Tank stops
filling when
level is at SP2

SP2

Tank Emptying

SP1

Tank stops
emptying when
level is at SP1

SP2

SP1

Tank starts
emptying when
level is at or
above SP2

SP2

Содержание TFL-B101Q

Страница 1: ...ly AC DC Auto sensing wide range supply PS1 std 85 265 VAC 95 370 VDC 2 5W max 4 2W PS2 15 48 VAC 10 72 VDC 2 5W max 4 2W Operating Temp 0 to 60 C Storage Temp 20 C to 70 C Relative Humidity 95 non co...

Страница 2: ...dia grams are used to visually assist in following programming steps The following symbols are used to represent the functions and displays of the meter When two fingers are shown side by side the tw...

Страница 3: ...side the bar display area and by an OFF segment inside the bar display area Horizontal or Reverse Mounting Meters can be mounted horizontally in the panel and for those applica tions that require an o...

Страница 4: ...driver to release two plastic catches on either side of the case and levering backwards Step 4 Starting with the top first insert a small flat bladed screw driver and carefully lever the plastic catc...

Страница 5: ...the Scaling by pressing the ZERO and SPAN buttons simultaneously for two seconds Both scaling memories will be erased and an internal default scale factor will be loaded This provides a display of zer...

Страница 6: ...libration of the meter it is best to start with a reset of the scaling STEP C RESET THE SCALING ON CHANNEL ONE 1 Apply power to the meter and press the CH1 ZERO and CH1 SPAN buttons simultaneously for...

Страница 7: ...e Display Driver Board See the layout diagram on Page 4 and 14 for the exact location The steps to setup the setpoints are as follows 1 SELECT THE RELAY ACTIVATION MODE FOR EACH INSTALLED RELAY Make s...

Страница 8: ...ity as to the signal status especially just after transitioning to a new zone However if two or more setpoints with differently specified colors are positioned at the same set point value the color sp...

Страница 9: ...t the analog output as measured on the external multimeter to be the required value 20mA in this example When the HI button is pressed the UP or DOWN indicator LED shows the direction of change Releas...

Страница 10: ...s 23 and 24 have a unique plug and socket outline to prevent cross connection The main board uses standard right angled connectors Replacement 2 3 and 4 pin plug connectors are available see Accessori...

Страница 11: ...EXC Display Board Front SP1 SP2 SP3 SP4 Zero Span 0 10 20 30 40 50 60 70 80 90 100 Display Board Front SP1 SP2 SP3 SP4 Zero Span 0 10 20 30 40 50 60 70 80 90 100 Zero SP4 SP3 SP2 SP1 100 0 10 30 50 70...

Страница 12: ...ated I Series input modules that have span or zero potentiometers can be interchanged between any I Series com patible meter without recalibration because all of the analog scaling and reference circu...

Страница 13: ...fset 0 _ Increase Span Decrease 141E I Series Input Signal Conditioning Modules IF02 Line Frequency SPAN ZERO Frequency to Voltage Conversion 60 to 500VAC 269D IA12 AC Millivolt RMS Sigma Delta 371A A...

Страница 14: ...re IS02 Pressure Load Cell 5 10VDC Exc 20 2mV V 4 6 wire 2 20 mV V 10V 5V 4W 6W EXC Pressure Transducer PRESSURE 151A IR03 Linear Potentiometer 1K min POTENTIOMETER 1K Minimum Digital Scaling Input Ex...

Страница 15: ...tting Right angled Connector 6mm 0 24 10mm 0 39 26 5mm 1 05 Push On Connector for FI series IO board The adapter snaps on the 36x144 mm 1 42 x5 69 case and enables single unit or stack mounting in an...

Страница 16: ...ader position 4 3 2 1 1 2 3 4 5 75 Turn Potentiometer 0 Equivalent Circuit Increase Zero Decrease 5 4 3 2 1 Decrease Zero Increase 1 2 3 4 5 75 Turn Potentiometer 0 Zero Pot Disabled SPAN Turn Clockwi...

Страница 17: ...have one 10 Amp relay or two 5 Amp relays plus 16 bit analog output or an extra 5 Amp relay Auto sensing AC DC wide range power supplies 85 265 V AC 95 370 V DC or 18 36 V AC 9 60 V DC Quick easy mou...

Страница 18: ...HAKARU PLUS CORPORATION Tel 81 6 6300 2195 Page 18 05 12 16 TFL B101Q DS FL6 Space...

Страница 19: ...40 40 30 35 25 20 0 5 10 15 9x5 45 45 40 30 35 25 20 0 5 10 15 10x5 50 50 45 40 30 35 25 20 0 5 10 15 12 15 0 3 6 9 1 10 100 1000 1 5 15 150 1500 2 20 200 2000 2 5 25 250 2500 3 30 300 3000 4 40 400 4...

Страница 20: ...e IS05 Pressure Load Cell 20 2mV V 5 10V Exc 4 wire IS06 Pressure Load Cell Ext Exc 20 2mV V 4 wire IS07 Pressure 20 2mV V with High Impedance and External Excitation IT03 RTD 100 Pt 2 3 4 wire 200 to...

Отзывы: