11.2 0151800227A PCB
SW01 is used to set wire controlled address of and set capabilities of master; SW03 is used to set indoor unit
address (combine original communication address and address of centralized controller)
SW01_
1
SW01_2
SW01_3
SW01_4
Address of
wire controlled
indoor unit
[1]
[2]
[3]
[4]
Address of wire controlled indoor unit (group address)
OFF
OFF
OFF
OFF
0# (wire controlled master unit) (default)
OFF
OFF
OFF
ON
1# (wire controlled slave unit)
OFF
OFF
ON
ON
2# (wire controlled slave unit)
OFF
OFF
ON
ON
3# (wire controlled slave unit)
…
…
…
…
……
ON
ON
ON
ON
15# (wire controlled slave unit)
SW01_5
SW01_6
SW01_7
SW01_8
Capability of
indoor unit
[5]
[6]
[7]
[8]
Capability of indoor unit
ON
OFF
ON
OFF
36000BTU (MVAH036MV2AA
)
ON
OFF
ON
ON
42000BTU (MVAH042MV2AA
)
48000BTU (MVAH048MV2AA
)
(A) Definition and description of SW01
(B) Definition and description of SW03
Note 2:
• Set the address by dip switch when connecting the centralized controller or gateway or charge system.
• Address of centralized controller =communication a 0 or +64.
SW03_ 2=OFF, address of centralized controller =communication 0=communication address SW03_
2=ON, address of centralized controller=communication 64 (applies when centralized controller is used
and there are more than 64 indoor units)
SW03
Set the
communication
and central
control address
by dip switch
(*Note 2)
[1] [2] [3] [4] [5] [6] [7] [8]
Communication
address
Central control
address
ON
OFF OFF OFF OFF OFF OFF OFF
0
(default)
0
(default)
ON
OFF OFF OFF OFF OFF OFF
ON
1
1
ON
OFF OFF OFF OFF OFF
ON
OFF
2
2
…
…
…
…
…
…
…
…
…
…
ON
OFF
ON ON ON ON ON ON
63
63
ON ON
OFF OFF OFF OFF OFF OFF
0
64
ON ON
OFF OFF OFF OFF OFF
ON
1
65
ON ON
OFF OFF OFF OFF
ON
OFF
2
66
…
…
…
…
…
…
…
…
…
…
ON ON ON ON ON ON ON ON
63
127
OFF …
…
…
…
…
…
…
Set the address by wired controller
or automatically (default)