Indoor power supply wiring & signal wiring between indoor and outdoor & signal wiring between indoor.
Items
Total
Current of
Indoor Unite(A)
Cross
Section
AWG(mm
2
)
Length
in.(m)
Rated
Current of
Overflow
Breaker(A)
Rated current of residual
Circuit Breaker(A)
Ground Fault
Interruptor(mA)
Response time(S)
Cross Sectional Area of
Signal Line
Outdoor-
indoor AWG
(mm
2
)
Indoor-
indoorAWG
(mm
2
)
<7
14(2.5)
65.6(20)
10
10 A, 30mA, 0.1S or below
2 cores×AWG18-
AWG14(0.75-2.0 mm
2)
shielded line
≥7 and <11
12(4)
65.6(20)
16
16 A, 30mA, 0.1S or below
≥11 and <16
10(6)
82(25)
20
20 A, 30mA, 0.1S or below
≥16 and <22
8(8)
98.4(30)
32
32 A, 30mA, 0.1S or below
≥22 and <27
6(10)
131(40)
32
32 A, 30mA, 0.1S or below
• The electrical power line and signal lines must be tightly.
• Every indoor unit must have the ground connection.
• The power line should be enlarged if it exceeds the permissible length.
• Shielded lays of all the indoor and outdoor units should be connected together, with the shielded lay at the side of signal
lines of outdoor units grounded at one point.
• Signal lines should not exceed 3280ft(1000m)
Signal Wiring of Wired controller
Length of Signal Line ft (m)
Wiring Dimensions AWG (mm
2
)
<328(100)
22
(
0.3
)
×core shielding line
≥328(100)and <656(200)
20
(
0.5
)
×core shielding line
≥656(100) and <984(300)
18
(
0.754
)
×core shielding line
≥984(300) and <1312(400)
16
(
1.25
)
×core shielding line
≥1312(400)and <1968(600)
14
(
2
)
×core shielding line
The shielding lay of the signal line must be grounded at one end.
The total length of the signal line shall not be more than 600m.