22
(a) Keep a gradient (1/50-1/100) of the drainpipes and avoid lobbing or curving.
• Proper Piping
• Improper Piping
Static Pressure Range
unit: Pa
4. Drainpipes
(b) When connecting the drainpipe to the equipment, don’t apply too much force on one side of the equipment.
Meanwhile, the piping should be positioned as close to the equipment as possible.
(c) For the drainpipe, the general purpose hard PVC tube can be purchased at local shops. During the connection,
insert the end of PVC tube into the wash port and fasten it with drainage hose and thread clip. Binding agents
shouldn’t be used to connect the wash port and drainage hose.
Static Pressure Range
0~200
MVAH009-030MV2AA
MVAH036-048MV2AA
Unit:in
20 /8
drainp ipe
18 5/8
16 1/4
gasp ipe
liquid pipe
18 3/8
18 3/8
16
29
11 /8
11 /8
18 3/8
39 3/8~78 6/8in
hanging
heat insultor
gradient of 1/100
or over
bolt
airo utletp ort
avoidl obing
don't putpipe
into water
avoid curving