Outdoor unit

1.Installation of Outdoor Unit

3.Connection

4.Attaching Drain-Elbow

2.Connection of pipes

Install according to

To bend a pipe, give the roundness as large as possible not to crush the pipe

Connecting the pipe of gas side first makes working easier.

The max vertical distance between the indoor unit and the outdoor unit is 5 m.

Use the same method on indoor unit. Loosen the screws on terminal block and insert the  plugs fully into

terminal block, then tighten the screws.

If wiring is not correct, proper operation can not be carried out and controller may be damaged.

 If the drain-elbow is used, please attach it as

 figure. (Note: Only for heat pump unit.)

Drawing for the installation of indoor and outdoor units

Insert the cable according to terminal number in the same manner as the indoor unit.

Fix the cable with a clamp.

Half union

Flare nut

Spanner

Torque wrench

6

Outdoor unit

Forced fastening without careful centering

may damage the threads and cause a

leakage of gas.

Be careful that matters, such as wastes of sands, etc. shall not enter the pipe.

Pipe Diameter   (     )

Liquid side  6.35mm(1/4")

Fastening torque

18N.m

Gas side  12.7mm(1/2")

50N.m

Содержание HSU-18HEA03(T3)

Страница 1: ...Piping hole cover Arrangement of piping directions Rear left Rear right Left Below Right The marks from to in the figure are the parts numbers The distance between the indoor unit and the floor shoul...

Страница 2: ...s can be left In the case of fixing the remote controller on a wall place where the indoor unit can receive signals when the fluorescent lamps in the room are lightened Place which is less affected by...

Страница 3: ...ticle When the mounting plate is first fixed for the position of wall hole Fix to side bar and lintel a mounting bar Which is separately sold and then fasten the plate to the fixed mounting bar Make a...

Страница 4: ...o the dent of heat insulation materials of indoor unit 2 Insert the indoor outdoor electric cable from backside of indoor unit and pull it out on the front side then connect them 3 Coat the flaring se...

Страница 5: ...lease change it with the type of T 3 15A 250V 3 The wiring method should be in line with the local wiring standard 4 After installation the power plug should be easily reached 5 When connecting the ca...

Страница 6: ...he screws If wiring is not correct proper operation can not be carried out and controller may be damaged If the drain elbow is used please attach it as figure Note Only for heat pump unit Drawing for...

Страница 7: ...torque Valve rod Valve cap 7 9 20 25 Tighten torque N m When connecting pipe exceeds 5 meters 20g refrigerant shall be added per exceeding meter Charge according to the following list Piping length A...

Страница 8: ...r in the drain pan of the indoor unit and confirm that drainage is carried out surely to outdoor In case that the attached drain hose is in a room please apply heat insulation to it without fail Pleas...

Отзывы: