Outdoor unit

1.Installation of Outdoor Unit

3.Connection

4.Attaching Drain-Elbow

2.Connection of pipes

Install according to

To bend a pipe, give the roundness as large as possible not to crush the pipe

Connecting the pipe of gas side first makes working easier.

The max vertical distance between the indoor unit and the outdoor unit is 5 m.

Use the same method on indoor unit. Loosen the screws on terminal block and insert the  plugs fully into
terminal block, then tighten the screws.

If wiring is not correct, proper operation can not be carried out and controller may be damaged.

 If the drain-elbow is used, please attach it as
 figure. (Note: Only for heat pump unit.)

Forced fastening without careful centering
may damage the threads and cause a
leakage of gas.

Pipe Diameter   (     )

Liquid side  6.35mm(1/4")

Liquid side  9.52mm(3/8")

Fastening torque

Drawing for the installation of indoor and outdoor units

Insert the cable according to terminal number in the same manner as the indoor unit.

Fix the cable with a clamp.

18N.m

40N.m

Half union

Flare nut

Spanner

Torque wrench

6

Gas side  12.7mm(1/2")

50N.m

Outdoor unit

Gas side  15.88mm(5/8")

60N.m

Be careful that matters, such as wastes of sands, etc. shall not enter the pipe.

Содержание HSU-18CI03

Страница 1: ...ing hole cover Arrangement of piping directions Rear left Rear right Left Below Right The marks from to in the figure are the parts numbers The distance between the indoor unit and the floor should be...

Страница 2: ...controller on a wall place where the indoor unit can receive signals when the fluorescent lamps in the room are lightened Place which is less affected by rain or direct sunlight and is sufficiently v...

Страница 3: ...ticle When the mounting plate is first fixed for the position of wall hole Fix to side bar and lintel a mounting bar Which is separately sold and then fasten the plate to the fixed mounting bar Make a...

Страница 4: ...aslant from the underside and then put it down perpendicularly Remove terminal cover at right bottom corner of indoor unit then take off wiring cover by removing its screws When connecting the cable a...

Страница 5: ...fully into terminal block then tighten the screws Pull the cable slightly to make sure the cables have been properly inserted and tightened After the cable connection never fail to fasten the connecte...

Страница 6: ...orrect proper operation can not be carried out and controller may be damaged If the drain elbow is used please attach it as figure Note Only for heat pump unit Forced fastening without careful centeri...

Страница 7: ...specified torque Valve rod Valve cap 7 9 20 25 Tighten torque N m When connecting pipe exceeds 5 meters 16g refrigerant shall be added per exceeding meter Charge according to the following list Piping...

Страница 8: ...pan of the indoor unit and confirm that drainage is carried out surely to outdoor In case that the attached drain hose is in a room please apply heat insulation to it without fail Please kindly expla...

Отзывы: