background image

Outdoor unit

6.Purging Method:

7

3-way valve

2-way valve
6.35mm(1/4")

12.7mm(1/2")

9.52mm(3/8")

15.88mm(5/8")

Push the air out of the indoor unit

and piping as followes:

(1) Remove the valve cap on 2-way

      valve in outdoor unit.

(2) Loosen by 1/2 turn the flare nut of

     gas pipe, which is conneted to

     3-way valve.

(3) Loosen 2-way valve by 90

o

 using

     hexagon wrench, and after approx.

     10 sec tighten it up. Gas comes out

     through flare nut on wide pipe. If no

     gas is discharged, tighten flare nut

     with specified torque.

(4) Open 2-way and 3-way valves

      using specified torque.

(5) Tighten the caps on the valves

      with specified torque.

Valve rod

Valve cap

7-9

20-25

Tighten torque N.m

When connecting pipe exceeds 5 meters, 16g refrigerant shall be added

per exceeding meter. Charge according to the following list.

Piping length

Additional amount

5m

7m

10m

No need

32g

(This must be strictly controlled within 90

o

 and 10 sec.)

Note: When extending piping, air inside piping shall be removed by using external

         refrigerant gas, charge according to the following list.

80g

Brand new outdoor unit is charged 50g or 80g(only for 24k unit) more refrigerant than regulated weight.

Only for first installation, this extra 50g or 80g(only for 24k unit) can be used to purge air in pipes.

During this procedure, 50g or 80g(only for 24k unit) refrigerant will be discharged in piping.

3-way valve

2-way valve

SFST18TR3

S F S T 2 4 T R 3

Содержание HSU-18CI03

Страница 1: ...ing hole cover Arrangement of piping directions Rear left Rear right Left Below Right The marks from to in the figure are the parts numbers The distance between the indoor unit and the floor should be...

Страница 2: ...controller on a wall place where the indoor unit can receive signals when the fluorescent lamps in the room are lightened Place which is less affected by rain or direct sunlight and is sufficiently v...

Страница 3: ...ticle When the mounting plate is first fixed for the position of wall hole Fix to side bar and lintel a mounting bar Which is separately sold and then fasten the plate to the fixed mounting bar Make a...

Страница 4: ...aslant from the underside and then put it down perpendicularly Remove terminal cover at right bottom corner of indoor unit then take off wiring cover by removing its screws When connecting the cable a...

Страница 5: ...fully into terminal block then tighten the screws Pull the cable slightly to make sure the cables have been properly inserted and tightened After the cable connection never fail to fasten the connecte...

Страница 6: ...orrect proper operation can not be carried out and controller may be damaged If the drain elbow is used please attach it as figure Note Only for heat pump unit Forced fastening without careful centeri...

Страница 7: ...specified torque Valve rod Valve cap 7 9 20 25 Tighten torque N m When connecting pipe exceeds 5 meters 16g refrigerant shall be added per exceeding meter Charge according to the following list Piping...

Страница 8: ...pan of the indoor unit and confirm that drainage is carried out surely to outdoor In case that the attached drain hose is in a room please apply heat insulation to it without fail Please kindly expla...

Отзывы: