Page 38
31-5000752 Rev. 0
17 SEER SINGLE STAGE HEAT PUMP CHARGING PROCEDURE (R410A)
NS17H48S
CHARGE BY WEIGHT:
1 - THE CONDENSER UNIT IS FACTORY CHARGED WITH R410A
2 - THE RATING PLATE LISTED CHARGE AMOUNT IS FOR 15 FEET OF LINE SET
3 - ADD 0.6 OZ OF FREON FOR EVERY ONE FOOT OF LINE SET OVER 15 FEET
4 - REMOVE 0.6 OZ OF FREON FOR EVERY ONE FOOT OF LINE SET UNDER 15 FEET
CHARGE BY SUBCOOLING (COOLING MODE):
1 - IF AMBIENT TEMPERATURE IS ABOVE 65ºF, CHARGE THE SYSTEM IN COOLING MODE
2 - THE SUBCOOLING METHOD IS USED FOR SYSTEMS WITH INDOOR TXV
3 - START THE SYSTEM IN COOLING AND LOWER THE THERMOSTAT SETTING TO MINIMUM SETTING
4 - CHECK AIR FLOW AND RUN THE SYSTEM FOR 20 MINUTES FOR STABILIZATION
5 - THE VALUES LISTED IN THE TABLE BELOW ARE BASED ON 70 TO 80ºF INDOOR RETURN AIR TEMPERATURE
6 - ADJUST CHARGE TO MEET THE SUBCOOLING LISTED UNDER “COOLING” FOR THE LISTED INDOOR MATCH
CHARGE BY SUBCOOLING (HEATING MODE):
1 - IF AMBIENT TEMPERATURE IS BELOW 65ºF, CHARGE THE SYSTEM IN HEATING MODE
2 - ALL HEAT PUMPS HAVE FACTORY INSTALLED OUTDOOR TXV
3 - START THE SYSTEM IN HEATING AND RAISE THE THERMOSTAT SETTING TO MAXIMUM SETTING
4 - CHECK AIR FLOW AND RUN THE SYSTEM FOR 20 MINUTES FOR STABILIZATION
5 - THE VALUES LISTED IN THE TABLE BELOW ARE BASED ON 65 TO 75ºF INDOOR RETURN AIR TEMPERATURE
6 - ADJUST CHARGE TO MEET THE SUBCOOLING LISTED UNDER “HEATING” FOR THE LISTED INDOOR MATCH
7 - IF FEASIBLE, DOUBLE CHECK THE FINAL CHARGE LEVEL DURING THE COOLING SEASON
OPERATING PRESSURES CHECK:
1 - THE PRESSURE VALUES LISTED BELOW ARE NOT INTENDED FOR CHARGING, BUT TO CONFIRM PROPER SYSTEM
OPERATION
2 - THE PRESSURE VALUES CAN VARY BASED ON THE DIFFERENT INSTALLATONS
SUBCOOLING AT SERVICE VALVE
INDOOR UNIT
COOLING ± 1ºF
HEATING ± 5ºF
NAM48V1, NAM48P1
5
11
NAM48V2
4
10
NCU(C,U)48(B,C)
4
16
NCU(C,U)49C
7
11
NCU(U,C)5060C
4
16
NCU(U,C)60C
11
13
NCHC48B
2
13
NCHC48C
4
14
NCHC60D
9
13
NORMAL OPERATING PRESSURES (± 10 PSI LIQUID / ± 5 PSI SUCTION)
HEATING
COOLING
AMBIENTºF
20
30
40
50
60
65
75
85
95
105
115
LIQUID/SUCTION 300 / 61 314 / 76
328 / 90
341 / 107 356 / 126 231 / 134 269 / 136 311 / 138 358 / 140 409 / 144 467 / 146
Содержание GE APPLIANCES NS17HS
Страница 7: ...Page 7 31 5000752 Rev 0 Figure 1 Typical Parts Arranegment Figure 2 Typical Parts Arranegment...
Страница 29: ...Page 29 31 5000752 Rev 0 Figure 11 Typical Factory Wiring 018 through 036 models...
Страница 30: ...Page 30 31 5000752 Rev 0 Figure 12 Typical Factory Wiring 042 through 060 models...
Страница 31: ...Page 31 31 5000752 Rev 0 Figure 13 Wiring Diagram 018 036 Models...
Страница 32: ...Page 32 31 5000752 Rev 0 Figure 14 Wiring Diagram 042 060 Models...
Страница 43: ...Page 43 31 5000752 Rev 0 Notes...