background image

Page  27

31-5000752   Rev. 0

Homeowner Information

ELECTRICAL SHOCK HAZARD!

Turn OFF electric power to unit before performing any 

maintenance or removing panels or doors.

FAILURE TO DO SO COULD RESULT IN BODILY 

INJURY OR DEATH.

 WARNING

Heat Pump Operation

Your new heat pump has several characteristics that you 

should be aware of:

• 

Heat pumps satisfy heating demand by delivering large 

amounts of warm air into the living space. This is quite 

different  from  gas-or  oil-fired  furnaces  or  an  electric 

furnace which deliver lower volumes of considerably 

hotter air to heat the space.

• 

Do not be alarmed if you notice frost on the outdoor coil 

in the winter months. Frost develops on the outdoor 

coil during the heating cycle when temperatures are 

below 45°F. An electronic control activates a defrost 

cycle lasting 5 to 15 minutes at preset intervals to clear 

the outdoor coil of the frost.

• 

During the defrost cycle, you may notice steam rising 

from  the  outdoor  unit.  This  is  a  normal  occurrence. 

The thermostat may engage auxiliary heat during the 

defrost  cycle  to  satisfy  a  heating  demand;  however, 

the unit will run to normal operation at the conclusion 

of the defrost cycle.

In case of extended power outage...

If the outdoor temperature is below 50°F and power to your 

outdoor unit has been interrupted for one hour or longer, 

observe the following when restoring power to your heat 

pump system.

• 

Set the room thermostat selector to the “Emergency 

Heat” setting to obtain temporary heat for a minimum 

of 6 hours. This will allow system refrigerant pressures 

and temperatures enough time to return to a stabilized 

condition.

• 

In  Emergency  Heat  mode,  all  heating  demand  is 

satisfied  by  auxiliary  heat;  heat  pump  operation  is 

locked  out.  After  a  6  hour  “warm-up”  period,  the 

thermostat can then be switched to the “Heat” setting 

and normal heat pump operation may resume.

Thermostat Operation

The  wall-mounted  thermostat  controls  your  heat  pump. 

The thermostat is available in various configurations from 

different manufacturers. The information below is typical for 

most thermostats. Ask your dealer for specific information 

regarding the model of thermostat installed.

Fan Switch

In AUTO or INT (intermittent) mode, the blower operates 

only when the thermostat calls for heating or cooling. This 

mode  is  generally  preferred  when  humidity  control  is  a 

priority. 

The  ON  or  CONT  mode  provides  continuous  indoor 

blower operation, regardless of whether the compressor or 

auxiliary heat are operating. This mode is required when 

constant air circulation or filtering is desired.

On models without a fan selection switch, the fan will cycle 

with the outdoor unit.

System Switch

Set  the  system  switch  for  heating,  cooling  or  auto 

operation.  The  auto  mode  allows  the  heat  pump  to 

automatically switch from heating mode to cooling mode to 

maintain predetermined comfort settings. Many heat pump 

thermostats  are  also  equipped  with  an  emergency  heat 

mode which locks out heat pump operation and provides 

temporary heat supplied by the auxiliary heat.

Indicating Light

Most  heat  pump  thermostats  have  an  amber  light 

which  indicates  when  the  heat  pump  is  operating  in  the 

emergency heat mode.

Temperature Indicator

The  temperature  indicator  displays  the  actual  room 

temperature.

Important System Information

• 

Your system should never be operated without a clean 

air filter properly installed.

• 

Return air and supply air registers should be free from 

restrictions or obstructions to allow full flow of air.

IF YOUR SYSTEM DOES NOT WORK, BEFORE 

REQUESTING A SERVICE CALL:

1. 

Ensure  thermostat  is  set  below  (cooling)  or  above 

(heating) room temperature and that the system lever 

is in the “COOL”, “HEAT” or “AUTO” position.

2. 

Inspect your return air filter: If it is dirty, your heat pump 

may not function properly.

3. 

Check  indoor  and  outdoor  disconnect  switches. 

Confirm circuit breakers are ON or that fuses have not 

blown. Reset breakers/replace fuses as necessary.

4. 

Inspect the outdoor unit for clogged condenser coils, 

(grass cuttings, leaves, dirt, dust or lint). Ensure that 

branches, twigs or other debris are not obstructing the 

condenser fan.

Содержание GE APPLIANCES NS17HS

Страница 1: ...31 5000752 Rev 0 11 22 GEA READ CAREFULLY KEEP THESE INSTRUCTIONS NS17HS SINGLE STAGE HIGH EFFICIENCY SPLIT SYSTEM HEAT PUMP UP TO 17 SEER 9 5 HSPF UP TO 16 SEER2 8 5 HSPF2 Service Manual...

Страница 2: ...al for personal injury or death Electric shock hazard Can cause injury or death Before attempting to perform any service or maintenance turn the electrical power to unit OFF at disconnect switch es Un...

Страница 3: ...53 33 9 50 25 0 120 0 2 6 1 3 825 NS17H60SA4 208 230 60 1 197 253 32 5 50 23 9 124 5 2 6 1 3 825 UNIT DIMENSIONS IN Model Dimensions inch Shipping Weight lbs A Width B Depth C Height NS17H18SA4 28 25...

Страница 4: ...146 H4TXV02 7 8 3 8 7 8 3 8 7 8 3 8 NS17H60SA4 164 H4TXV03 1 1 8 3 8 1 1 8 3 8 7 8 3 8 Factory charged for 15 feet of line set adjust per installation instructions Field supplied adapter required COO...

Страница 5: ...ompressors usually do not require hard start maybe needed for utility brown out or low voltage areas 42 48 60 81J69 Crankcase Heater 18 24 30 93M04 Prevents liquid migration to compressor in cold weat...

Страница 6: ...e 6 31 5000752 Rev 0 FAN BLADE SPECS 4SHP17LE 51 Fan Blade Dia of Blades Pitch Part 18 22 2 24 23C06 24 22 2 24 23C06 30 22 2 24 23C06 36 26 3 24 23V42 42 26 3 29 23V43 48 26 3 29 23V43 60 26 3 29 23V...

Страница 7: ...Page 7 31 5000752 Rev 0 Figure 1 Typical Parts Arranegment Figure 2 Typical Parts Arranegment...

Страница 8: ...the outdoor section To reduce the possibility of noise transmission the foundation slab should NOT be in contact with or be an integral part of the building foundation See Figure 3 General Read this e...

Страница 9: ...rhang is 36 NOTE At least one side should be unobstructed by a wall or other barrier Table 2 Clearances 30 around Control Box 24 6 Figure 4 NOTE See Table 2 for specific minimum clearance guidelines D...

Страница 10: ...enced burnout it is recommended that the existing line set and indoor coil be replaced NOTE Refrigeration Piping Use only refrigerant grade copper tubes Split systems may be installed with up to 50 fe...

Страница 11: ...STRAP THE LIQUID LINE TO THE VAPOR LINE FLOOR JOIST OR ROOF RAFTER REFRIGERANT LINE SET INSTALLING HORIZONTAL RUNS NOTE Similar installation practices should be used if line set is to be installed on...

Страница 12: ...instructions Figure 5 1 Connect gauges and equipment as shown in Figure 5 2 Set the recovery machine for liquid recovery and start the recovery machine Open the gauge set valves to allow the recovery...

Страница 13: ...sing bulb insulation is required if mounted external to the coil casing sensing bulb installation for bulb positioning STUB END TEFLON RING LIQUID LINE ASSEMBLY WITH BRASS NUT DISTRIBUTOR ASSEMBLY 3 I...

Страница 14: ...side to liquid line service valve service port B Connect gauge set center port to bottle of nitrogen with regulator C Remove core from valve in vapor line service port to allow nitrogen to escape NITR...

Страница 15: ...INT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WRAP SERVICE VALVES To help protect service valve seals during brazing wrap water saturated cloths around service valve bodies and copper...

Страница 16: ...ve on the high side of the manifold gauge set in order to pressurize the line set and the indoor unit E After a few minutes open one of the service valve ports and verify that the refrigerant added to...

Страница 17: ...frigerant Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit G Perform the following Close manifold gauge valves Shut off HFC 410A cylinder Reinst...

Страница 18: ...er may result in property damage Size wiring and circuit breaker s per Product Specifications and unit rating plate WARNING ELECTROSTATIC DISCHARGE ESD Precautions and Procedures Electrostaticdischarg...

Страница 19: ...th nameplate rating Field wiring connections are tight and factory wiring has not been disturbed and are tight Indoor fan motor is on correct speed tap 2 Set thermostat selector switch to OFF and fan...

Страница 20: ...When the low pressure switch trips the control board will cycle off the compressor and the strike counter in the board will count one strike The low pressure switch is ignored under the following con...

Страница 21: ...de Heating and cooling operation will be allowed in this fault condition NOTE The coil temperature probe is designed with a spring clip to allow mounting to the outside coil tubing Coil sensor locatio...

Страница 22: ...the control board will initiate a defrost cycle Actuation When the reversing valve is de energized the Y1 circuit is energized and the coil temperature is below 35 F 2 C the board logs the compressor...

Страница 23: ...rform demand or time temperature defrost operation System will still heat or cool ON ON Fault Demand Defrost Control Failure Indicates that demand defrost control has internal component failure Cycle...

Страница 24: ...jumper is installed on the DELAY pins the compressor will be cycled off for 30 seconds going in and out of the defrost mode Units are shipped with jumper installed on DELAY pins NOTE The 30 second off...

Страница 25: ...nser coils Use a soft bristle brush with light pressure only DO NOT damage or bend condenser coil fins Damaged or bent fins may affect unit operation Figure 9 Removing Louvers Remove two screws at top...

Страница 26: ...conditions that may cause panels to be blown around and battered WARNING REMOVAL STEP 1 INSERT PANEL UNDER UNIT TOP CAP LIP AND LIFT SLIGHTLY TO CLEAR SIDE LIP OF PANEL FROM BASE STEP 2 PANEL INSTALLA...

Страница 27: ...available in various configurations from different manufacturers The information below is typical for most thermostats Ask your dealer for specific information regarding the model of thermostat instal...

Страница 28: ...T OPERATE CONTACT YOUR SERVICING DEALER Be sure to describe the problem and have the model and serial numbers of the equipment available If warranty replacement parts are required the warranty must be...

Страница 29: ...Page 29 31 5000752 Rev 0 Figure 11 Typical Factory Wiring 018 through 036 models...

Страница 30: ...Page 30 31 5000752 Rev 0 Figure 12 Typical Factory Wiring 042 through 060 models...

Страница 31: ...Page 31 31 5000752 Rev 0 Figure 13 Wiring Diagram 018 036 Models...

Страница 32: ...Page 32 31 5000752 Rev 0 Figure 14 Wiring Diagram 042 060 Models...

Страница 33: ...IENT TEMPERATURE IS BELOW 65 F CHARGE THE SYSTEM IN HEATING MODE 2 ALL HEAT PUMPS HAVE FACTORY INSTALLED OUTDOOR TXV 3 START THE SYSTEM IN HEATING AND RAISE THE THERMOSTAT SETTING TO MAXIMUM SETTING 4...

Страница 34: ...TEMPERATURE IS BELOW 65 F CHARGE THE SYSTEM IN HEATING MODE 2 ALL HEAT PUMPS HAVE FACTORY INSTALLED OUTDOOR TXV 3 START THE SYSTEM IN HEATING AND RAISE THE THERMOSTAT SETTING TO MAXIMUM SETTING 4 CHEC...

Страница 35: ...IENT TEMPERATURE IS BELOW 65 F CHARGE THE SYSTEM IN HEATING MODE 2 ALL HEAT PUMPS HAVE FACTORY INSTALLED OUTDOOR TXV 3 START THE SYSTEM IN HEATING AND RAISE THE THERMOSTAT SETTING TO MAXIMUM SETTING 4...

Страница 36: ...RATURE IS BELOW 65 F CHARGE THE SYSTEM IN HEATING MODE 2 ALL HEAT PUMPS HAVE FACTORY INSTALLED OUTDOOR TXV 3 START THE SYSTEM IN HEATING AND RAISE THE THERMOSTAT SETTING TO MAXIMUM SETTING 4 CHECK AIR...

Страница 37: ...AMBIENT TEMPERATURE IS BELOW 65 F CHARGE THE SYSTEM IN HEATING MODE 2 ALL HEAT PUMPS HAVE FACTORY INSTALLED OUTDOOR TXV 3 START THE SYSTEM IN HEATING AND RAISE THE THERMOSTAT SETTING TO MAXIMUM SETTIN...

Страница 38: ...OW 65 F CHARGE THE SYSTEM IN HEATING MODE 2 ALL HEAT PUMPS HAVE FACTORY INSTALLED OUTDOOR TXV 3 START THE SYSTEM IN HEATING AND RAISE THE THERMOSTAT SETTING TO MAXIMUM SETTING 4 CHECK AIR FLOW AND RUN...

Страница 39: ...E 1 IF AMBIENT TEMPERATURE IS BELOW 65 F CHARGE THE SYSTEM IN HEATING MODE 2 ALL HEAT PUMPS HAVE FACTORY INSTALLED OUTDOOR TXV 3 START THE SYSTEM IN HEATING AND RAISE THE THERMOSTAT SETTING TO MAXIMUM...

Страница 40: ...less than 15ft subtract this amount see Installation Instructions for more details Charge Using the Weigh in Method If the system is void of refrigerant locate and repair any leaks evacuate system and...

Страница 41: ...o charge shown on unit nameplate Indoor Matchup Subcool Additional Charge Heat 5 F Cool 1 F lbs oz 3 0 Ton HP NAM36P1 15 8 1 lb 2 oz NAM30P1 14 7 1 lb 6 oz NAM36E1 15 8 1 lb 2 oz NAM36V2 17 8 1 lb 1 o...

Страница 42: ...__________________________________________ Rated LoadAmpacity ________________ Compressor _______________________ Outdoor Fan ________________________ Maximum Fuse or Circuit Breaker _________________...

Страница 43: ...Page 43 31 5000752 Rev 0 Notes...

Страница 44: ...Printed in the U S A All specifications and illustrations subject to change without notice and without incurring obligations...

Отзывы: