14
Control panel
•DW-86L579BP/729BP/829BP/959BP
•DW-86L579BPT/729BPT/829BPT/959BPT/959W/828W
35
• A fl ashing alarm cannot be cancelled unless the malfunction is eliminated. The buzzing
alarm can be temporarily silenced for 30 minutes by pressing the“Silence” key. However,
If the problem is not fi xed. the buzzer alarm will resume after 30 minutes.
• When using the freezer, the battery switch must be turned on to charge the battery.
• When there is a power outage, the battery sustains the temperature display. If the
battery voltage is insuffi cient. the temperature display will turn off .
• While the battery is still capable of providing power to the display, the temperature
display can be turned off by unplugging the power cord and turning off the battery
control switch.
• The freezer is also designed to auto-adjust the inner temperature set point in high
ambient temperatures When the ambient temperature is warmer than 35
℃
and the
set point temperature is set to be lower than -82
℃
, the set point temperature will
automatically default to -82
℃
. If the ambient temperature is equal to or cooler than
30
℃
,the set point will resume at the intended inner set point. This feature extends the
life expectancy of the freezer.
Caution
Alarm Type
Tricolor lamp panel
Buzzer
A prompt box pops up.
High-low temperature alarm
Red
Y
Y
Power-off alarm
Red
Y
Y
Door opening alarm
Red
Y
Y
Main temperature sensor fault alarm
Yellow
Y
N
Heat exchanger fault alarm
Yellow
Y
N
Condenser dirty alarm
Yellow
Y
N
High ambient temperature alarm
Yellow
Y
N
Battery fault alarm
Yellow
Y
N
Backup system fault alarm
Yellow
Y
N
DW-86L579BPT/729BPT/829BPT/959BPT/959W/828W
• Under alarm, the beeper alarm could be ceased by pressing any key, and the fl ashing alarm and
remote alarm will not be ceased(DW-86L579BPT/729BPT/829BPT/959BPT/959W/828W:Click “×”
on the upper right-hand corner in the prompt box to stop the buzzer alarm. If there is no prompt box,
click the alarm on the bottom of the homepage to view the alarm, and then stop the buzzer alarm.).
• If the alarm condition is still available, the beeper alarm will be recovered automatically 30 minutes
after ceasing.
Automatic recovery of alarm
Содержание DW-86L579BP
Страница 1: ......