Safety Precautions   

■ 

Symbol description

 

 

Dear user, 

For  the  better  understanding  of  this  Manual  and  the  proper  operation  of  the  chiller,  the  marks  and 
symbols used in this Manual are described as follows: 

 

WARNING

: it is likely to cause death, serious injury and other  severe accidents if the 

user fails to do as required. 

 

CAUTION

: it is possible for severe accident to occur   

 

WARNING

 

Installation  and  maintenance  must  be  carried  out  by  professionals  experienced  in  this  type  of  unit  in 
accordance with applicable local codes and rules on installation and maintenance. We are not liable for 
any unit damage or casualty due to non-conformance with this requirement. 

The  power  supply  must  be  switched  off  prior  to  maintenance  and  relocation  of  the  unit;  otherwise, 
personal  injury  or  death  may  be  caused  by  electric  shock.  Do  not  touch  such  hot  components  as 
compressor and exhaust pipe directly. 

When  the  water  system  contains  water,  control  the  startup  and  shutdown  of  the  water  pump  via  the 
water pump output point on the unit controller; otherwise, the anti-freezing protection of the unit will not 
work, causing the freezing crack to the heat exchanger. If the unit is to idle for a long time in winter, drain 
the water from the water system via the drain valve to prevent the freezing crack of the heat exchanger, 
the water pipe and other parts on water side. Furthermore, the water pump shall be power off to avoid 
starting up against frost without water. 

To  prevent  the  heat  exchanger  on  water  side  from  being  frozen  due  to  foreign  matters  entered,  a 
self-contained  water  filter  must  be  installed  on  the  water  return  pipe  of  the  unit  (specific  installation 
position is shown in water system diagram). 

Dregs and dirt in the water pipe network including filter and heat exchanger may seriously damage the 
heat  exchanger and water pipe. Installers and users must ensure the quality  of chilled water, not  use 
anti-icing mixtures containing salt and prevent the entry of air into the water system, because the salt 
and air can oxidize and corrode steel parts inside the heat exchanger. 

When the unit is installed, it must be protected against wind and earthquakes as required. Otherwise, 
accidents such as dumping or falling of the unit may occur. 

The fixed foundation must have sufficient bearing capacity when the unit is installed. The base of the unit 
must be fixed on a solid foundation to prevent the unit from sinking or causing injury due to insufficient 
strength. 

Before repairing and transferring the machine, the power must be cut off, otherwise the electric shock 
will cause injury and death. Do not directly touch  high temperature components such as compressors 
and exhaust pipes. 

The  installer  and  the  user  must  ensure  the  quality  of  the  chilled  water.  It  is  forbidden  to  use  the  salt 
anti-icing mixture and no air is allowed to enter the water system. 

The unit is forbidden to be installed in places such as toilet exhaust, hospital operating room exhaust, 
sewer treatment equipment, etc., where there is much dirt, oil, salt, and a large amount of sulfurized gas, 
which will cause corrosion of the unit components. 

It is forbidden to use refrigerant or refrigerant oil other than those specified by the model. Failure to do so 
may result in damage to the unit, resulting in a fire or explosion. 

Содержание CA0065EANR

Страница 1: ...t pump unit model CA0065EANR One World One Home Installation and Operation Manual of Commercial Air Conditioner This Manual applies to modular air cooled heat pump chiller units Modle CA0065EANR This Manual applies to modular air cooled heat pump chiller units Modle CA0035EAND CA0070EAND CA0130EAND ...

Страница 2: ... following notes for the proper use and maintenance more efficient operation and longer service life of unit 1 This Manual includes information necessary for the proper installation commissioning startup and maintenance so please read it carefully before the startup or maintenance 2 Installation must be performed by trained professionals 3 For the first startup please follow the steps herein to en...

Страница 3: ...ulation 19 Electrical Connection 19 Operation Inspection 12 Calculations of Water System Inventory 15 Type Selection of Auxiliary Electric Heater 15 Connection Diagram of the Unit Power Wires 16 Electrical Parameters 16 Address Code Setting 17 Requirements for Communication Wires 17 Connection of Communication Wires 17 Maintenance 18 Debugging And Running 24 Repair And Maintenance 25 Faults And Tr...

Страница 4: ...ed a self contained water filter must be installed on the water return pipe of the unit specific installation position is shown in water system diagram Dregs and dirt in the water pipe network including filter and heat exchanger may seriously damage the heat exchanger and water pipe Installers and users must ensure the quality of chilled water not use anti icing mixtures containing salt and preven...

Страница 5: ...s and be installed by professional electricians The electrical part must be protected from moisture otherwise it will cause electric shock fire and other accidents The leakage protector must be set correctly Leakage circuit breakers must be installed in accordance with electrical codes and incorrect installation may result in electric shock The power cord should not be pulled too tightly Doing so ...

Страница 6: ...ncluding gloves work clothes etc can prevent accidental personal injury It is forbidden to use fuses that exceed normal capacity Replacing a fuse with a wire or the like will be a safety hazard or cause a fire It is forbidden to short circuit the safety device and force the unit to start This can result in damage to the unit fire explosions etc It is forbidden to use other uses beyond the scope of...

Страница 7: ... enabling the centralized control and independent control the controller has high anti interference capability and can control the unit from as far as 1000 meters the monitoring of unit operation is convenient in case of unit fault the controller will display corresponding fault codes Convenient installation The unit is designed to maximize the ease of installation The cooling system has been fabr...

Страница 8: ...5 1 2 Main components of the unit ...

Страница 9: ...o the weight of the unit during operation 2 The foundation can be channel steel designed by the user according to the unit size or concrete structure The surface should be level to ensure the smooth flow of the unit 3 Add 10 20mm rubber cushion between the unit and the foundation 4 The unit and foundation can be fixed with Φ16 or Φ18 foot bolts ...

Страница 10: ...0 2170 Package Size Length width height mm 2320 830 2270 weight Unit net weight kg 700 Unit gross weight kg 715 Unit operating weight kg 750 Noise dB A 65 Maximum inlet and outlet water temperature difference 10 Note 1 Nominal cooling capacity conditions effluent temperature 7 C outdoor ambient temperature 35 C water flow 0 172 m3 h kW 2 Nominal heating conditions outlet temperature 45 C outdoor a...

Страница 11: ...sure Below 0 7MPa Chilled water quality Free from corrosive copper iron dissolved matters of welding materials Installation site Provided with snow protection and ventilation Ambient temperature Refer to the above diagram operating range Relative humidity Below 90 Optimal operating temperature 12 for cooling 40 for heating Note This operating range is measured according to GB T 18430 1 rated water...

Страница 12: ...ting Capcity Heating Capcity Heating Capcity Heating Capcity Heating Capcity Heating Capcity Heating Capcity Heating Capcity Heating Capcity Heating Capcity Heating Capcity Heating Capcity 30 00 0 40 0 47 0 55 0 63 0 73 0 84 0 95 1 09 1 14 1 19 1 32 1 44 35 00 0 38 0 45 0 53 0 60 0 71 0 82 0 93 1 06 1 10 1 15 1 28 1 39 40 00 0 35 0 43 0 51 0 59 0 69 0 80 0 91 1 03 1 07 1 12 1 23 1 34 45 00 0 31 0 ...

Страница 13: ...lace to improve the heat exchange The installation position shall have enough strength to withstand the unit weight and the vibration during operation The unit shall not be installed at a place that is dirty oily salty and exposed to a large amount of sulfur gas The chiller unit shall not be installed at such place where flammable gas may leak Because the flammable gas leaked and accumulated aroun...

Страница 14: ...1 Installation 1500 450 450 450 1500 450 450 Unit mm Unit mm 1 Diagram of installation space for single chiller unit 300 4 8 1000 Guiding device 2 Diagram of installation space for multiple chiller units ...

Страница 15: ...12 Installation 3 Diagram of arrangement of multiple chiller units Unit mm ...

Страница 16: ... water pipe shall be carried out prior to the connection between the pipe and the unit 6 The drain valve on the outlet pipe is self contained manual or automatic exhaust valve shall be set at the highest point of the water circulation system for the normal operation of the unit the valve handle must be removed so that the valve is not adjusted 7 Water quality control Industrial water used as hot w...

Страница 17: ... outlet pipe is very low the unit will automatically operate for a period to maintain the temperature of the water system and prevent the water pipe from being frozen so the unit must be energized in winter If the unit is not used in winter drain the water from the water system or fill such anti freezing mixture as ethylene glycol and glycerol into the water system The water filter must be install...

Страница 18: ... combined Number of modules 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Overall nozzle dimensions mm 65 80 100 125 150 200 250 Symbol Description Check valve Automatic exhaust valve Water filter Stop valve Thermometer Pressure gauge Water pump Flexible connection Expansion tank Electronic water processor 3 way valve 2 way valve Symbol Description Fan coil Fan coil Fan coil Fan coil Heater ...

Страница 19: ... long time please discharge water from the unit through the water outlet pipeline connected with the plate heat exchanger of the unit If no water discharge is required for the unit in winter do not cut off the power supply The fan coil in the water system must be provided with a 3 way valve to ensure that the water system is smoothly circulated after the winterizing water pump is started CAUTION T...

Страница 20: ...low rate in the pipe m s Pipe diameter mm 12 20 25 32 40 50 65 80 Closed water system 0 4 0 5 0 5 0 6 0 6 0 7 0 7 0 9 0 8 1 0 0 9 1 2 1 1 1 4 1 2 1 6 Open water system 0 3 0 4 0 4 0 5 0 5 0 6 0 6 0 8 0 7 0 9 0 9 1 0 0 9 1 2 1 1 1 4 Pipe diameter mm 100 125 150 200 250 300 350 400 Closed water system 1 3 1 8 1 5 2 0 1 6 2 2 1 8 2 5 1 8 2 6 1 9 2 9 1 6 2 5 1 8 2 6 Open water system 1 2 1 6 1 4 1 8 1...

Страница 21: ... or equal to Vmin 310 265 20 25L 3 7 Expansion tank volume calculation The air conditioning water system must be installed with a certain volume of expansion water tank to adapt to the change of system water volume caused by water temperature changes thermal expansion and contraction to prevent the freezing of winter water system and the instability of pump suction pressure at the same time as sys...

Страница 22: ...ance of at least 3mm Please install it yourself 4 2 Electric control Control of auxiliary electric heating The start of electrical heating is to provide an auxiliary heating function at low temperatures The inlet and outlet of the auxiliary electric heating are connected in series to the total outlet pipe of the air cooling module unit and the control node for auxiliary electric heating is provide...

Страница 23: ...trol contact and the auxiliary electric heating overload protection control contact are provided only 220V output control signal is provided and the passive thermal relay for overload protection is provided by the user The normally closed contact of the passive thermal relay is connected to the overload protection control contact When the current is too large the thermal relay protection is discon...

Страница 24: ...0 Host OFF OFF OFF OFF 1 Slave 1 ON OFF OFF OFF 2 Child machine 2 OFF ON OFF OFF 3 Child machine 3 ON ON OFF OFF 4 Slave 4 OFF OFF ON OFF 5 Child machine 5 ON OFF ON OFF 6 Slave 6 OFF ON ON OFF 7 Slave 7 ON ON ON OFF 8 Slave 8 OFF OFF OFF ON 9 Slave 9 ON OFF OFF ON 10 Slave 10 OFF ON OFF ON 11 Slave 11 ON ON OFF ON 12 Slave 12 OFF OFF ON ON 13 Slave 13 ON OFF ON ON 14 Slave 14 OFF ON ON ON 15 Slav...

Страница 25: ...ld not exceed 1000m 3 For the communication between the handheld communicator and the host within 300m shielded twisted pair with diameter of 0 75mm2 and above must be used Line to extend the connection between the handheld communicator and the electronic control cabinet 4 For long distance communication connections between 300m and 1000m the A and B communication lines must be shielded twisted pa...

Страница 26: ...23 Compressor drive module Capacitor plate Lightning protection board Refrigerant heat sink Reactance ...

Страница 27: ... a single compressor Galvanometer confirmation 6 23A 3 Operating current of a single fan Galvanometer confirmation 0 2 3 6A 4 Unit inlet water temperature during cooling operation Thermometer confirmation 8 28 5 Unit outlet water temperature during cooling operation Thermometer confirmation 5 21 6 Unit inlet water temperature during heating operation Thermometer confirmation 24 50 7 Unit outlet wa...

Страница 28: ...igerant R410A and lubricant When the system is working properly there is no need to replenish refrigerant or lubricating oil and it is not allowed to charge or replace refrigerant and lubricant If it is necessary to replenish due to leakage please refer to the charging amount specified on the nameplate on the unit 6 2 Maintenance During the use of the unit certain routine inspections must be carri...

Страница 29: ...26 maintenance plan can be carried out according to different usage conditions in different regions Description for user self test items check items for professionals ...

Страница 30: ...in 60min locked 16 E26 01 02 The system compressor module variable frequency side current detection circuit abnormal 4 times in 60min locked 17 E27 01 02 The system compressor module instantaneous power failure 4 times in 60min locked 18 E28 01 02 Abnormal power supply on the control panel of the system compressor module 4 times in 60min locked 19 E29 01 02 The system compressor module out of step...

Страница 31: ...ecoverable 48 E69 01 02 Refrigerant lack protection of system One lock 49 E71 Overtop Temperature difference of in and out water 3 times in 60min locked 50 E72 Running time exceeded One lock 51 E76 01 02 Lower temperature of exhaust temperature sensor of system compressor 3 times in 60min locked 52 E77 01 02 Open circuit or short circuit in oil temperature sensor of system recoverable 53 E78 01 02...

Страница 32: ...capacity Check the fan Heating 7 Short circuit found in air circuit Check the cause of short circuit and take troubleshooting Heating 8 Incomplete defrosting Replace the poor 4 way valve or defrosting sensor Heating 3 Too low exhaust pressure 1 Lack of refrigerant Adjust the charge of refrigerant Cooling heating 2 Low suction pressure Refer to Low Suction Pressure Cooling heating 3 Low ambient tem...

Страница 33: ...ault in communication of wired controller 1 Incorrect unit numbering Check the unit numbering and correct it Cooling heatin g 2 Incorrect connection of communication wires Check the order of connection of communication wires 3 Damaged PCB Replace the PCB 4 Poor wired controller Replace the wired controller 10 Over current fault of compressor 1 High exhaust pressure and high suction pressure Refer ...

Страница 34: ...d Closed recirculation systems may require anti corrosion control including the following for reference only a inhibitors of sodium nitrite borate and organic matter b sodium nitrite borate and silicate c high concentration of complex acid salt pH control d pH and sulfite control e polyphosphites and silicates f alkaline phosphate and sulfite control Since the control of water quality is very diff...

Страница 35: ...ater temperature cleaning system etc No need to control Corrosion control 1 1 low concentration of corrosion inhibitors 1 2 anti calcium carbonate scale coating 1 3 pH control 1 4 Suitable manufacturing materials 1 1 High concentration 200 500ppm corrosion inhibitor 1 2 Low concentration 20 30ppm corrosion inhibitor 1 3 pH control 1 4 Suitable manufacturing materials 1 1 high concentration of corr...

Страница 36: ...er is earlier However artificial damages e g damages caused by external force operation against rules installation or maintenance by non professional units users improper transport hoisting and engineering installation etc and damages due to external force majeure are not covered by the warranty In such case we will according to relevant regulations charge for repairing or replacing parts at cost ...

Страница 37: ......

Страница 38: ......

Страница 39: ......

Страница 40: ......

Отзывы: