MID-STATIC DUCTED TECHNICAL OVERVIEW
G-14
ENGLISH
Error Codes
The error codes that are displayed on the indoor units may vary from the outdoor unit codes. The information communicated by
the error code will be the SAME for both indoor and outdoor units even though the numbers may differ.
Indoor
LED4
Indoor
LED3
Outdoor
LED
Diagnosis
2
1
1
Outdoor EEPROM failure
2
2
2
IPM overcurrent or short circuit
2
3
/
Compressor over current during deceleration
2
4
4
Communication failure between the IPM and outdoor PCB
2
5
5
Module operated overload (compressor overload protection)
2
6
6
Module low or high voltage
2
7
/
Compressor current sampling circuit fault
2
8
8
Overheat protection for discharge temperature
2
9
9
Malfunction of the DC fan motor
3
0
10
Malfunction of defrost temperature sensor
3
1
11
Suction temperature sensor failure
3
2
12
Ambient temperature sensor failure
3
3
13
Discharge temperature sensor failure
3
4
/
PFC circuit loop voltage
3
5
15
Communication failure between the indoor & outdoor unit
3
6
16
Lack of refrigerant or discharging
3
7
17
4-way valve switching failure
3
8
18
Loss of synchronism detection
3
9
/
Low DC or AC voltage
4
0
20
Indoor thermal overload
4
1
21
Indoor coil frosted
4
2
/
PFC circuit loop overcurrent
4
3
23
Module thermal overload
4
4
24
Compressor start failure, over-current
4
5
25
Phase current protection (IPM)
4
6
26
MCU reset
4
7
27
Module current detect circuit malfunction
4
8
28
Liquid pipe sensor failure: Circuit A
4
9
29
Liquid pipe sensor failure: Circuit B
5
0
30
Liquid pipe sensor failure: Circuit C
5
1
31
Liquid pipe sensor failure: Circuit D
5
2
32
Gas pipe sensor failure: Circuit A
5
3
33
Gas pipe sensor failure: Circuit B
5
4
34
Gas pipe sensor failure: Circuit C
5
5
35
Gas pipe sensor failure: Circuit D
5
6
36
Gas pipe sensor failure: Circuit E
5
7
/
Compressor overcurrent detected by IPM
5
8
38
Malfunction of module temperature sensor momentary power failure detection
5
9
39
Malfunction of condensing temperature sensor
6
0
40
Liquid pipe sensor failure: Circuit E
6
1
41
Toci temperature sensor failure
6
2
42
High Pressure switch open
6
3
43
Low Pressure switch open
6
4
44
System high pressure protection: Overcharged, high condensing temperature or malfunction of fan motor
6
5
45
System low pressure protection: Undercharged, low defrosting temperature, or malfunction of fan motor
0
1
/
Indoor ambient temperature sensor failure
0
2
/
Indoor coil temperature sensor failure
0
4
/
Indoor PCB EEPROM failure
0
7
/
Communication fault between the indoor and outdoor unit
0
8
/
Communication fault between the controller and Indoor unit
0
12
/
Drain system malfunction
0
13
/
Zero cross signal detected wrong
0
14
/
Indoor fan motor malfunction
Содержание AW07EH2VHA
Страница 2: ...Aug 2020 Manual release Revision History ...
Страница 12: ... This page intentionally left blank ...
Страница 30: ...OUTDOOR TECHNICAL OVERVIEW B 18 ENGLISH Wiring Diagrams 2U18MS2VHB ...
Страница 31: ...OUTDOOR TECHNICAL OVERVIEW B 19 ENGLISH Wiring Diagrams 3U24MS2VHB ...
Страница 32: ...OUTDOOR TECHNICAL OVERVIEW B 20 ENGLISH Wiring Diagrams 4U36MS2VHB ...
Страница 36: ... This page intentionally left blank ...
Страница 45: ...WALL MOUNT TECHNICAL OVERVIEW C 9 ENGLISH Topic Title Wiring Diagrams ...
Страница 68: ... This page intentionally left blank ...
Страница 78: ... This page intentionally left blank ...
Страница 100: ...MEDIUM STATIC DUCTED PRO SERIES TECHNICAL OVERVIEW H8 ENGLISH Topic Title Wiring Diagram ...
Страница 114: ... This page intentionally left blank ...
Страница 122: ...TROUBLESHOOTING REFERENCES J 10 ENGLISH Refrigeration Diagrams 3U24MS2VHB Refrigerant Diagram ...
Страница 123: ...TROUBLESHOOTING REFERENCES J 11 ENGLISH Refrigeration Diagrams 4U36MS2VHB REFERENCES PAGE 101 NGLISH ...