Unit pipe spec and connection method (unit: mm)
A. Outdoor Unit
Mobel
Gas pipe side
Liquid pipe side
Diameter (mm)
Connecting method
Diameter (mm)
Connecting method
AV08NMSETA
Ø19.05
Flared joint
Ø9.52
Flared joint and Brazing (here
including two connecting
methods because of using a
reduser pipe)
AV10NMSETA
Ø22.22
Flared joint and Brazing (here
including two connecting
methods because of using a
reduser pipe)
Ø9.52
AV12NMSETA
Ø25.4
Ø12.7
Flared joint
B. Indoor Unit
Model Capacity
Gas pipe side
Liquid pipe side
Diameter (mm)
Connecting method
Diameter (mm)
Connecting method
07
Ø9.52
Flared
Ø6.35
Flared
09
Ø9.52
Ø6.35
12
Ø12.7
Ø6.35
16
Ø12.7
Ø6.35
18
Ø12.7
Ø6.35
24
Ø15.88
Ø9.52
28
Ø15.88
Ø9.52
30
Ø15.88
Ø9.52
38
Ø15.88
Ø9.52
48
Ø15.88
Ø9.52
72
Ø25.4
Braze
Ø9.52
96
Ø25.4
Ø9.52
Note:
• AS072, AS092 gas pipe: Ø12.7mm; AS182 gas pipe/liquid pipe: Ø15.88/9.52mm
C. Pipe spec and the torque
Diameter (mm)
Torque (N.m)
Ø6.35
14~18
Ø9.52
34~42
Ø12.7
49~61
Ø15.88
68~82
Ø19.05
84~98