Outdoor Installation
When the outdoor unit is installed
above the indoor units the
maximumheight should be 50m
When the outdoor unit is installed below the indoor units the maximum
height should be 40m
L1
L2
L5
L4
L7
L3
L8
L9
L10
L11
L6
Max.drop:15m
A
B
C
D
E
F
Long pipe and high drop
Max. length
Pipe in above figure
Single way total pipe length (=total liquid pipe length)
300m
L1+L2+L3+L4+L5+L6+L7+L8+L9+L
10+L11
Single way max. pipe length (max. length between
outdoor & indoor) actual / equivalent length
150m / 175m
L1+L3+L10+L11
Pipe length after first branch pipe (length between first
branch & farthest indoor)
40m
L1+L10+L11
Main pipe actual length (length between first gather
pipe & first branch pipe)
110m
L1
Height difference between indoor units
15m
--
Pipe length between indoor unit and the nearest branch
30m
--