2. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similar qualified person.
3. If the fuse on PC board is broken please change it with the type of T 3.15A /250VAC.
4. The wiring method should be in line with the local wiring standard.
5. The power cable should be:
H07RN-F 5G 4.0mm
2
( For series 482(380-400V, 3N~, 50Hz));
H07RN-F 5G 2.5mm
2
( For series 362(380-400V, 3N~, 50Hz));
H05RN-F 3G 6.0mm
2
(For series 282,362 (1PH,220-230V~,50Hz));
H05RN-F 3G 4.0mm
2
(For series 242 (1PH,220-230V~,50Hz));
H05RN-F 3G 2.5mm
2
(For series 182 (1PH,220-230V~,50Hz));
The connecting cable should be:
For series 182 , H05RN-F 3G 2.0mm
2
+1X0.75mm
2
For the others, the connecting cable should be H05RN-F 4G 0.75mm
2
All the cables shall have got the European authentication certificate. During installation, when the connecting cables
break off, it must be assured that the grouding wire is the last one to be broken off.
6. The power cable and connect cable should be self-provided.
7. The breaker of the air conditioner should be all-pole switch, and the distance between its two contacts should be no
less than 3mm.
8. The indoor unit installation height is at least 2.5m.
9. A leakage breaker must be installed.
1. Applicable ambient temperature range:
The machine is adaptive in following situation
6
Safety Precautions
Cooling
Heating
Indoor temperature
Outdoor temperature
Indoor temperature
Outdoor temperature
max. DB/WB
min. DB/WB
max. DB/WB
min. DB/WB
max. DB/WB
min. DB/WB
max. DB/WB
min. DB/WB
ON-OFF
Inverter
32/23 C
18/14 C
43/26 C
10/6 C
27 C
15 C
24/18 C
-7 C
32/23 C
18/14 C
43/26 C
-5 C
27 C
15 C
24/18 C
-7 C