1. Applicable ambient temperature range:
The machine is adaptive in following situation
Cooling
Heating
Indoor temperature
Outdoor temperature
Indoor temperature
Outdoor temperature
max. DB/WB
min. DB/WB
max. DB/WB
min. DB/WB
max. DB/WB
min. DB/WB
max. DB/WB
min. DB/WB
32/23 C
18/14 C
4
3
/26 C
10/6 C
27 C
15 C
24/18 C
-15 C
2. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similar qualified person.
3. If the fuse on the indoor PC board is broken please change it with the type of T 5A/250V(For AD100S2SM7FA/
AD71S2SM7FA/AD125S2SM7FA/AD140S2SM7FA)
4. The wiring method should be in line with the local wiring standard.
5. The power cable should be:
H05RN-F 3G 4.0mm²(outdoor unit 1U71S2SS5FA/1U100S2SN5FA),or H05RN-F 3G 6.0mm²(outdoor unit
1U125/140S2SP5FA),
The connecting cable should be:
H05RN-F 4G 2.5mm
2
All the cables shall have got the European authentication certificate. During installation, when the connecting cables
break off, it must be assured that the grouding wire is the last one to be broken off.
6. The power cable and connect cable should be self-provided.
7. The breaker of the air conditioner should be all-pole switch, and the distance between its two contacts should be no
less than 3mm.
8. The indoor unit installation height is at least 2.5m.
9. A leakage breaker must be installed.
10.For
AD71S2SM7FA/AD100S2SM7FA /AD125S2SM7FA/AD140S2SM7FA,we
can get the 10
different ESP
through adjust wired controller YR-E17A, please refer
below:
AD71S2SM7FA
AD100S2SM7FA
AD125S2SM7FA
AD140S2SM7FA
static presssure grade
static presssure(Pa)
0
25
37
50
70
90
100
120
130
150
0
25
37
50
70
90
100
120
130
150
25
37
50
70
90
100
110
120
130
150
AD71S2SM7FA
AD100S2SM7FA
AD125S2SM7FA
AD140S2SM7FA
25
37
50
70
90
100
110
120
130
150
Adjsutment metchod by wired controller YR-E17
A
:In the state of ON and non screen saving state, press Fan+ Set keys for
5 seconds to enter static pressure grade adjustment state with static pressure icon flashing and current static pressure
grade statically displaying. Press key↑↓ to change static pressure grade, then press Set key to confirm.
Details please refer to wired controller operation & installation manual.
Adjsutment metchod by Infrared remote conInfrared receiver RE-02:Step a:set the Infrared remote controller at
condition: FAN mode ,fan speed high Step b:then aim the remote controller at the infrared remote receiver RE-02,
press HEALTH button 4+N times(1≤N≤10,integer)within 12 seconds ,then the receiver will beep N+1 times ,the
static pressure level N is been set successfully.
Note:For Infrared remote controller YR-
E17A
, need press ON/OFF button make the controller’s at OFF status first,then
●
open the button cover press FRESH button will enter FAN mode interface.
9
10
1
2
(factory default)
3
4
5
6
7
8