Installation work for air outlet ducts

Calculate the draft and external static pressure and select the length,

shape and blowout.

A   Blowout duct

2-spot, 3-spot and 4-spot with     200 type duct are the standard

specifications.

Note

  (1) Shield the central blowout hole for 2-spot.

          (2) Shield the blowout hole around the center for 3-spot.

Limit the difference in length between spots at less than 2:1.

Reduce the length of duct as much as possible.

Reduce the number of bends as much as possible. (Corner R should

be as larger as possible.)

Use a band. etc. to connect the main unit and the blowout duct

flange.

Conduct the duct installation work before finishing the ceiling.

Connection of suction, exhaust ducts
a.Fresh air inlet

Inlet can be selected from the side or rear faces depending on the

working conditions.

Use the rear fresh air inlet when the simultaneous intake and exhaust

is conducted. (Side inlet cannot be used.)

b.Exhaust (Make sure to use also the suction.)

Use the side exhaust port.

Good example

Bad example

Bad example

Exhaust hole

State seeing from top of unit

Side fresh air inlet

Rear fresh air inlet

Fig.1

Fig.2

Drainage Test

Conduct a drainage test after completion of the electrical work.

During the trial, make sure that drain flows properly through the

piping and that no water leaks from connections.

In case of a new building, conduct the test before it is furnished

with the ceiling.

Be sure to conduct this test even when the unit is installed in the

heating season.

Attached drain hose clamp

Drain piping

Main unit

Drain situation can be checked with transparent socket

Remove grommet.

Make sure to install

it back after test.

Insert water supply hose

for 20 mm ~ 30 mm to

supply water.

(Insert hose facing

toward bottom.)

Pour water into a convex joint.

Procedures

Supply about 1000 cc of water to the unit through the air outlet

using a feed water pump.

Check the drain while cooling operation.

Before the electrical work has not been completed, connect a convex

joint in the drain pipe connection to provide a water inlet. Then, check

if water leaks from the piping system and that drain flows through

the drain pipe normally.

(1)
(2)

(3)

(4)

(a)

(b)

Ceiling surface

Heat

insulation

Suction panel

(Silent panel)

Air conditioner main unit

Special

blowout

(Option)

Blowout duct

(Optional  or

m a r k e t e d

item)

Hole for check

s p e c i a l   i n l e t

(option) (with air

filter)

inlet duct

 (optional or

 marketat item)

B

A

C

Drain Pipe

Air Duct

Installation Procedure

19

Installation Procedure

Содержание AD100S2SM7FA

Страница 1: ...ning 21 AD71S2SM7FA AD100S2SM7FA AD125S2SM7FA AD140S2SM7FA Keep this operation manual for future reference Original instructions This product must only be installed or serviced by qualified personnel Please read this manual carefully before installation Accessory 13 ...

Страница 2: ......

Страница 3: ... the inside of the stop value cover A contains fluorinated greenhouse gases covered by the Kyoto Protocol B fatory refrigerant charge of the product see unit name plate C additional refrigerant amount charged in the field D total refrigerant charge E outdoor unit F refrigerant cylinder and manifold for charging Haier Industrial Park No 1 Haier road Qingdao P R China A B C D kg kg kg R32 WARNING If...

Страница 4: ...connectionmustbeincorporatedinthewiring Makesureinstallationisdoneaccordingtolocalwiringregulationbyprofessionalpersons Makesuregroundconnectioniscorrectandreliable Aleakageexplosion proofbreakermustbeinstalled Theinstallationandserviceofthisproductshallbecarriedoutbyprofessionalpersonnel whohavebeentrainedandcertifiedbynationaltraining organizationsthatareaccreditedtoteachtherelevantnationalcompe...

Страница 5: ... instructions set forth in the User s Guide Installation shall be done by professional people don t install unit by yourself For the purpose of safety the air conditioner must be properly grounded in accordance with specifications Always remember to unplug the air conditioner before opening inlet grill Never unplug your air conditioner by pulling on the power cord Always grip plug firmly and pull ...

Страница 6: ...jury or death Installation by yourself is not encouraged because it could cause such problems as water leakage electrical shock or fire accident by some improper handing Installationbyyourselfisnotencouragedbecauseitcould cause such problems as water leakage electrical shock or fire accident by some improper handing Do not install nearby the place where may have leakage of flammable gas Depending ...

Страница 7: ...ture of the unit for any damage after a use of long period of time Insufficient ventilation could cause an oxygen deficiency accident If the structure is not repaired immediately the unit could topple down to cause a personal injury When cleaning the system stop the operation and turn off the power switch Do not put water containers on the unit such as a flower vase etc Cleaning should never be do...

Страница 8: ...m 9 A leakage breaker must be installed 10 For AD71S2SM7FA AD100S2SM7FA AD125S2SM7FA AD140S2SM7FA we can get the 10 different ESP through adjust wired controller YR E17A please refer below AD71S2SM7FA AD100S2SM7FA AD125S2SM7FA AD140S2SM7FA static presssure grade static presssure Pa 0 25 37 50 70 90 100 120 130 150 0 25 37 50 70 90 100 120 130 150 25 37 50 70 90 100 110 120 130 150 AD71S2SM7FA AD10...

Страница 9: ...all connected through 3 pieces of polar wire 6 Communication wiring The wire controller is equipped with special communication wiring in the accessories 3 core terminal 1 white 2 yellow 3 red is connected with the terminal A B C of wire controller respectively The communication wiring is 5 meter long if the actual length is more than it please distribute wiring according to below table Communicati...

Страница 10: ...ver to ordinary heating operation Heat pump type warming With the heat pump type warming the mechanism of heat pump that concentrate heat of outdoor air with the help of refrigerant to warm the indoor space is utilized Defrosting operation When a room is warmed with a heat pump type air conditioner frost accumulates on the heat exchanger of outdoor unit along with the drop of indoor temperature Si...

Страница 11: ... is consumed even the air conditioner is in stop Clean the air filter and set it in the place Care and Cleaning of the unit Clean with soft and dry cloth If it is very dirty dissolve neutral detergent in the lukewarm water and make the cloth wet with the water After wiping clean off the detergent using clean water 1 Clean the air filter by lightly tapping it or with the cleaner It is more effectiv...

Страница 12: ...supply power in normal Isn t the signal receiving section exposed to the direct sunlight or strong illumination Isn t the earth leakage breaker in action It is dangerous Turn off the power supply switch immediately and contact the sales dealer Power supply switch is not ON Cooling or heating is not sufficient Is the thermostat adjust as required Isn t the air filter dirty Isn t any doors or window...

Страница 13: ...AN mode during cooling To prevent frost from being accumulated on the indoor unit heat exchanger it is sometimes automatically switched to the FAN mode but it will soon return to the cooling mode Even if the operation switch is turned on cooling dehumidifying or heating is not operable for three minutes after the conditioner is stopped Because the protecting circuit is activated During this time a...

Страница 14: ... cross sigal detected wrong Note 1 The outdoor failure can also be indicated by the indoor unit the checking method as follo ws If the outdoor error code is M DECIMAL the indoor unit s wired controller display will show the after converted hexadecimal code of M 20 DECIMAL for example if the outdoor error code is 2 the indoor unit wired controller display will flash the error code 16 2 2 20 22 chan...

Страница 15: ...ghtening the Connecting pipe 2 3 4 Brass nut gas side for AD140S2SM7FA 1 5 8 Brass nut gas side for others 1 3 Coupler heat insulation gas side 1 For indoor side pipe joint gas side 4 Coupler heat insulation liquid side 1 For indoor side pipe joint liquid side 5 Accessories group 1 Drainage fittings group 6 Instructions 1 Air conditioner operation 13 ...

Страница 16: ...esult from a falling of the unit Execute the prescribed installation construction to prepare for earthquakes and the strong winds of typhoons and hurricanes etc Improper installations can result in accidents due to a violent falling over of the unit For electrical work please see that a licensed electrician executes the work while following the safety standards related to electrical equipment and ...

Страница 17: ...The place where salt breeze blows Seaside etc The place where dense soot smoke exists The place where humidity is extraordinarily high The place where near the machine which radiates the electromagnetic wave The place where voltage variation is considerably large For details consult your sales dealer The electric work must be burden on the authorized engineer with qualification for electric work a...

Страница 18: ...QUIPMENT MALFUNCTION AND OR PROPERTY DAMAGE Preparation of indoor unit Before or during the installation of the unit assemble necessary optional panel etc depending on the specific type Select places for installation satisfying following conditions and at the same time obtain the consent on the part of your client user Places where chilled or heated air circulates freely When the installation heig...

Страница 19: ...g side Supply water Water level 0 5 mm 0 0 2 Bring the piping side slightly lower Hanging bolt M10 nut Main unit M10 washer M10 spring washer 1 Preparation for suspending the unit a Size of hole at ceiling and position of hanging bolts Combination with silent panel b Hanger bolts installation Use care of the piping direction when the unit is installed Hanging bolt M10 Hole in anchor Hole in plug I...

Страница 20: ... the right figure Take care not to apply external force onto the drain pipe connection part For unit with water pump drain pipeuse hard PVC general purpose pipe VP which can be purchased locally When connecting insert a PVC pipe end securely into the drain socket before tightening securely using the attached drain hose and clamp Adhesive must not be used for connection of the drain socket and drai...

Страница 21: ...Conduct a drainage test after completion of the electrical work During the trial make sure that drain flows properly through the piping and that no water leaks from connections In case of a new building conduct the test before it is furnished with the ceiling Be sure to conduct this test even when the unit is installed in the heating season Attached drain hose clamp Drain piping Main unit Drain si...

Страница 22: ... sizes and circuit protection from table below This table shows 20 m length wires with less than 2 voltage drop POWER SUPPLY INDOOR OUTDOOR CONNECTION Make wiring to supply power to the outdoor unit so that the power for the indoor unit is supplied by outdoor unit terminal blocks Item Model Phase Switch breaker A Circuit breaker Overcurrent protector rated capacity A Power source wire size minimum...

Страница 23: ...cury hexavalent chromium polybrominated biphenyls and polybrominated diphenyl ethers are not more than 0 1 mass fraction and cadmium is not more than 0 01 mass fraction Please recycle the refrigerant before scrapping moving setting and repairing the air conditioning for the air conditioning scrapping should be dealt with by the qualified enterprises Move and scrap the air conditioning ...

Страница 24: ... our policy of continuous product improvement these dimensionsandspecificationsmaychangeatanytime Youshouldthereforecheckwithyourdealeror Haier s Customer Care Centre to ensure this flyer correctly describes the products currently available Fisher Paykel Australia Pty Ltd Level 1 1 Eden Park Drive Macquarie Park NSW 2113 Phone Customer Care 1300 729 948 Email customer care haier com au Fisher Paykel...

Отзывы: