6
2. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similar qualified person.
3. If the fuse on PC board is broken please change it with the type of T 3.15A /250VAC.
4. The wiring method should be in line with the local wiring standard.
5. The breaker of the air conditioner should be all-pole switch, and the distance between its two contacts should be no
less than 3mm. Such means for disconnection must be incorporation in the fixed wiring.
6. The installation height of the indoor unit is recommended from 2.5m to 2.7m.
7. The distance between its two terminal blocks of indoor unit and outdoor unit should not be over 5m. If exceeded, the
diameter of the wire should be enlarged according to the local wiring standard.
8. The waste battery shall be disposed properly.
9.For AD**SS1ERA,AD**SS1ERA(N),AD**SS1ERA(N)(P),we can get the 4 different ESP through adjust the indoor unit
PCB SW1-4 and SW1-5, please refer below:
1. Applicable ambient temperature range:
The machine is adaptive in following situation
AD09LS1ERA
AD12LS1ERA
AD18LS1ERA
AD24LS1ERA
Electrical components Case
Evaporator
Air outlet frame
Drain pan
Safety Precautions
Parts and Functions
Cooling
Heating
Indoor temperature
Outdoor temperature
Indoor temperature
Outdoor temperature
max. DB/WB
min. DB/WB
max. DB/WB
min. DB/WB
max. DB/WB
min. DB/WB
max. DB/WB
min. DB/WB
32/23 C
18/14 C
46/24 C
18 C
27 C
15 C
24/18 C
-15 C
Evaporator
Air outlet frame
Electrical components
Case
Drain pan
Attention:
The panel for AD*SS1ERA(N)and AD*SS1ERA(N)(P) is optional, for AD*SS1ERA(N)(P), it's with water pump, and
AD*SS1ERA(N) without pump .
AD09SS1ERA
AD09SS1ERA(N)
AD09SS1ERA(N)(P)
AD12SS1ERA
AD12SS1ERA(N)
AD12SS1ERA(N)(P)
AD18SS1ERA
AD18SS1ERA(N)
AD18SS1ERA(N)(P)
AD24SS1ERA
AD24SS1ERA(N)
AD24SS1ERA(N)(P)
SW01
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
--
--
--
0
0
--
--
--
--
--
--
0
1
--
--
--
--
--
--
1
0
--
--
--
--
--
--
1
1
--
--
--
0Pa
10Pa
20Pa
30Pa
Static pressure
The pump drain opening
Attention: cut off the power supply to adjust the SW1-4, and SW1-5, or else the operation is invalid.