Indoor unit
Fix to side bar and lintel a mounting bar, Which is separately sold, and then
fasten the plate to the xed mounting bar.
Refer to the previous article, “ When the mounting plate is
position of wall hole.
Make a hole of 60 mm in diameter, slightly descending to outside the wall.
Install piping hole cover and seal it off with putty after installation
When the mounting plate is rst xed
1. Carry out, based on the neighboring pillars or lintels, a
to be xed against the wall, then temporarily fasten the plate with one steel nail.
2. Make sure once more the proper level of the plate, by hanging a thread with a
weight from the central top of the plate, then fasten securely the plate with the
attachment steel nail.
3. Find the wall hole location A using a measuring tape
When the mounting plate is xed side bar and lintel
Indoor side
Outdoor side
1
Fitting of the Mounting Plate and Positioning of the wall Hole
Ø60mm
Wall hole
Thickness of wall
(Section of wall hole)
Piping hole pipe
Lid for right
piping
Lid for under piping pipe
Fix with adhesive tape
Lid for left piping
Heat insulation
material
Drain hose
Piping
Pipe supporting
plate
Indoor/outdoor electric cable
Indoor/outdoor electric cable and drain hose must be bound with refrigerant
piping by protecting tape.
[ Other direction piping ]
Cut away, with a nipper, the lid for piping according to the piping direction and
then bend the pipe according to theposition of wall hole. When bending, be
careful not to crash pipes.
Connect beforehand the indoor/outdoor electric cable, and then pull out the
connected to the heat insulation of connecting part specially.
proper leveling for the plate
rst xed “, for the
2
Making a Hole on the Wall and Fitting the Piping Hole Cover
G
Drawing of pipe
3
Installation of the Indoor Unit
[ Rear piping ]
Draw pipes and the drain hose, then fasten them with the adhesive tape
[ Left
·
Left-rear piping ]
In case of left side piping, cut away, with a nipper, the lid for left piping.
In case of left-rear piping, bend the pipes according to the piping direction to
the mark of hole for left-rear piping which is marked on heat insulation materials.
1. Insert the drain hose into the dent of heat insulation materials of indoor unit.
2. Insert the indoor/outdoor electric cable from backside of indoor unit, and pull it
out on the front side, then connect them.
3. Coat the aring seal face with refrigerant oil and connect pipes.
Cover the connection part with heat insulation materials closely, and make sure
xing with adhesive tape
Fixing the indoor unit body
Hang surely the unit body onto the upper notches of the
mounting plate. Move the body from side to side to verify its
secure xing.
In order to x the body onto the mounting plate,hold up
the body aslant from the underside and then put it down
perpendicularly.
mounting plate
When you unload the indoor unit,please use
then lift the bottom of the body outward
slightly and lift the unit aslant until it
leaves the mounting plate.
agraffe mounting plate
Unloading of indoor unit body
your hand to arise the body to leave agraffe,
Selection of pipe
2
Floor fixing dimensions
of the outdoor unit
(Unit:mm)
114.2
590
114.2
320
1U09JACFRA
1U12JACFRA
Floor fixing dimensions
of the outdoor unit
(Unit:mm)
140
500
628
131
131
140
256
360
1U09BYFSRA
1U12BYFSRA
1U18RABFRA
660
130
130
400.2
1U24SABFRA
FOR 09K 12K
FOR 18K
FOR 24K
A=170mm
C=130mm
B=
Ø
60mm
D=47mm
B=Ø60mm
A=218mm
C=151mm
B=Ø60mm
B=Ø60mm
D=38.5mm
D=38.5mm
D=47mm
1U35JACFRA
1U26JACFRA
1U53RABFRA
1U71SABFRA
Содержание 1U71SABFRA
Страница 11: ...Pinping diagrams Domestic air conditioner 4 Pinping diagrams Filter Filter ...
Страница 12: ...Operation range Domestic air conditioner 5 Operation range 10 0 20 16 32 10 20 15 10 ...
Страница 15: ...CN4 CN3 CN10 CN1 CN2 CN9 CN7 CN6 CN5 CN8 CN11 Connector Wiring Diagram Domestic Air Conditioner 13 PCB 2 ...
Страница 43: ...Seivice diagnosis Domestic air conditioner 41 ...
Страница 44: ...Seivice diagnosis Domestic air conditioner 42 ...
Страница 45: ...Seivice diagnosis Domestic air conditioner 43 ...
Страница 56: ...Circuit diagrams Domestic air conditioner 54 ...