Outdoor unit

6.Purging Method:

1.Remove the four screws of fresh air box from the back cover.
2.Use six screws to fix fresh air box onto the designated position on the outdoor unit.
3.Remove two screws of the pipe junction of the fresh air box, then insert the flared departure of
   the change for fresh air tube into the pipe junction and then fix with the screws.
4.Use four screws to fix the fresh air box onto the back cover, as illustrated:

Fresh air  box

Fresh air
   box

Fresh air tube

Fresh air tube

Fresh air tube

Screw
 hole

Dust
filtration
mesh

Screw

Screw

Joint of tube

Flared departure

5.Installation instruction on the outdoor part of the fresh air device

 Back
cover

Note:After wiring, the connecting terminals of outdoor unit and change-fresh-air as well as the wiring sheath should be
placed in the change-for-fresh-air box against the rain.

Connecting terminal

Fresh air signal
wire
  (with guard ring)

 Change-for-fresh-air box

7

3-way valve

2-way valve
6.35mm(1/4")

12.7mm(1/2")

2-way valve
6.35mm(1/4")

3-way valve

9.52mm(3/8")

HSU-09C03/VA(ZXF)
HSU-09H03/VA(ZXF)
HSU-12C03/VA(ZXF)
HSU-12H03/VA(ZXF)

HSU-18C03/V(ZXF)
HSU-18H03/V(ZXF)

2-way valve
9.52mm(3/8")

3-way valve

15.88mm(5/8")

HSU-22C03/V(ZXF)
HSU-22H03/V(ZXF)
HSU-22C03/V(ZF)
HSU-22H03/V(ZF)

HSU-12H03/VB(ZXF)
HSU-12H03/V(ZXF)

HSU-24C03/V(ZXF)

12.7mm(1/2")

HSU-24C03/V(ZF)

HSU-24H03/V(ZXF)
HSU-24H03/V(ZF)
HSU-24HK0307

Note: When extending piping, air inside piping shall be removed  by using external refrigerant gas, 

charge according to the following list.

Brand new outdoor unit is charged 50g or 80g(22k,24k) more refrigerant than regulated weight. Only for 
first installation, this extra 50g or 80g(22k,24k) can be used to purge airin pipes.
          During this procedure, 50g or 80g(22k,24k) refrigerant will be discharged in piping.(This must be
          strictly controlled within 90

o

 and 10 sec.)

When connecting pipe exceeds 5 meters, 20g or 60g
(only for 22k

24k) refrigerant shall be added per exceeding

 meter. Charge according to the following list. 

Piping length

Additional amount

5m

7m

No need 40g

10m

100g

for 9k 12k 18k

Push the air out of the indoor unit
and piping as followes:

(1) Remove the valve cap on 2-way valve in outdoor unit.

(2) Loosen by 1/2 turn the flare nut of gas pipe, which is

is conneted to 3-way valve.

(3) Loosen 2-way valve by 90

o

 using hexagon wrench, 

and after approx.10 sec tighten it up. Gas comes out

     through flare nut on wide pipe. If no gas is discharged,

tighten flare nut with specified torque.

(4) Open 2-way and 3-way valves using specified torque.

(5) Tighten the caps on the valves with specified torque.

Valve rod

Valve cap

7-9

20-25

Tighten torque N.m

for  22k 24k 

Max. Length:       for  9K :        A=7m
                            for 12K:       A=10m
                            for 18K 22K 24K:  A=20m

Max.Elevation:

for  9K 12K: B=5m

for 18K 22K 24K: B=10m

5m

7m

No need 120g

10m

300g

20m

900g

C

Outdoor unit

Indoor unit

Outdoor unit

Indoor unit

Oil trap

A

B

Outdoor unit

Indoor unit

A

B

A

B

CAUTION
In case more than 5 metres

ˈ

oil trap

should be installed every 5~7m.

C

HSU-24HD0307

Содержание 0010554405B

Страница 1: ... of piping directions Rear left Rear right Left Below Right Connecting electric cable for indoor and outdoor Drain hose Heating insulating material 4X50 4X25 Piping hole cover Read this manual before installation 1 Driver 2 Hacksaw 3 Hole core drill 4 Spanner 17 19 and 26mm 5 Torque wrench 17mm 22mm 26mm 6 Pipe cutter 7 Flaring tool 8 Knife 9 Nipper 12 Reamer 10 Gas leakage detector or soap and wa...

Страница 2: ... is sufficiently ventilated Place possible to bear the unit where vibration and noise are not increased Place where discharged wind and noise do not cause a nuisance to the neighbors Place where a distance marked is available as illustrated in the above figure Before inserting power plug into receptacle check the voltage without fail The power source is the same as the corresponding name plate Ins...

Страница 3: ...Refer to the previous article When the mounting plate is first fixed for the position of wall hole Fix to side bar and lintel a mounting bar Which is separately sold and then fasten the plate to the fixed mounting bar Make a hole of 70 mm in diameter slightly descending to outside the wall Install piping hole cover and seal it off with putty after installation Section of wall hole Piping hole pipe...

Страница 4: ... outside the room cable into left side of the wall hole in which the pipe has already existed 2 Pull out the cable on the front side and connect the cable making a loop signal wire Change for fresh air tube 1 Insert the drain hose into the dent of heat insulation materials of indoor unit 2 Insert the indoor outdoor electric cable from backside of indoor unit and pull it out on the front side then ...

Страница 5: ...5mm2 HSU 24C03 V ZF Indoor unit Outdoor unit L 1 N 2 HSU 18H03 V ZXF HSU 22H03 V ZXF 1 Two ways for the installation of indoor part as illustrated Way One For all the models In the guard ring connect outlet joint with the fresh air tube Way Two Only for the models of 09 12 Insert the joint of water collecting pan into the fresh air tube then connect the other end of joint with mesh enclosure of wa...

Страница 6: ...d cause a leakage of gas Pipe Diameter Liquid side 6 35mm 1 4 Gas side 9 52mm 3 8 Fastening torque Drawing for the installation of indoor and outdoor units Insert the cable according to terminal number in the same manner as the indoor unit Fix the cable with a clamp 18N m 40N m Half union Flare nut Spanner Torque wrench 6 Gas side 12 7mm 1 2 50N m 6 Easily demount cleaning of indoor unit 1 Top inl...

Страница 7: ...nding piping air inside piping shall be removed by using external refrigerant gas charge according to the following list Brand new outdoor unit is charged 50g or 80g 22k 24k more refrigerant than regulated weight Only for first installation this extra 50g or 80g 22k 24k can be used to purge airin pipes During this procedure 50g or 80g 22k 24k refrigerant will be discharged in piping This must be s...

Страница 8: ...n pan of the indoor unit and confirm that drainage is carried out surely to outdoor In case that the attached drain hose is in a room please apply heat insulation to it without fail Please kindly explain to our customers how to operate through the instruction manual Gas leak from pipe connecting Heat insulation of pipe connecting Are the connecting wirings of indoor and outdoor firmly inserted to ...

Отзывы: