Indoor unit

1.Fitting of the Mounting Plate and Positioning of the wall Hole

2.Making a Hole on the Wall and Fitting the Piping Hole Cover

When the mounting plate is first fixed

When the mounting plate is fixed side bar and lintel

1.Carry out, based on the neighboring pillars or lintels, a proper leveling for the plate to be
   fixed against the wall, then temporarily fasten the plate with one steel nail.
2. Make sure once more the proper level of the plate, by hanging a thread with a weight
from
    the central top of the plate, then fasten securely the plate with the attachment steel nail.
3. Find the wall hole location A using a measuring tape

A=170mm

35

Fit the level line

Refer to the previous article, "    When the mounting plate is first fixed   ", for the
position of wall hole.

Fix to side bar and lintel a mounting bar, Which is separately sold, and then fasten

the plate to the fixed mounting bar.

Make a hole of 70 mm in diameter,

slightly descending to outside the wall.

Install piping hole cover and seal it

off with putty after installation

(Section of wall hole)

Piping hole pipe

Outdoor side

Thickness
of wall

Indoor side

Wall hole

70mm

3.Installation of the Indoor Unit

Drawing of pipe

[ Rear piping ]

Draw pipes and the drain hose, then fasten them with the adhesive tape

[ Left

Left-rear piping ]

In case of left side piping, cut away, with a nipper, the lid for left piping.

In case of left-rear piping, bend the pipes according to the piping direction to the mark of hole for left-rear

piping which is marked on heat insulation materials.

3

G

Indoor unit

70mm

Содержание 0010554405B

Страница 1: ... of piping directions Rear left Rear right Left Below Right Connecting electric cable for indoor and outdoor Drain hose Heating insulating material 4X50 4X25 Piping hole cover Read this manual before installation 1 Driver 2 Hacksaw 3 Hole core drill 4 Spanner 17 19 and 26mm 5 Torque wrench 17mm 22mm 26mm 6 Pipe cutter 7 Flaring tool 8 Knife 9 Nipper 12 Reamer 10 Gas leakage detector or soap and wa...

Страница 2: ... is sufficiently ventilated Place possible to bear the unit where vibration and noise are not increased Place where discharged wind and noise do not cause a nuisance to the neighbors Place where a distance marked is available as illustrated in the above figure Before inserting power plug into receptacle check the voltage without fail The power source is the same as the corresponding name plate Ins...

Страница 3: ...Refer to the previous article When the mounting plate is first fixed for the position of wall hole Fix to side bar and lintel a mounting bar Which is separately sold and then fasten the plate to the fixed mounting bar Make a hole of 70 mm in diameter slightly descending to outside the wall Install piping hole cover and seal it off with putty after installation Section of wall hole Piping hole pipe...

Страница 4: ... outside the room cable into left side of the wall hole in which the pipe has already existed 2 Pull out the cable on the front side and connect the cable making a loop signal wire Change for fresh air tube 1 Insert the drain hose into the dent of heat insulation materials of indoor unit 2 Insert the indoor outdoor electric cable from backside of indoor unit and pull it out on the front side then ...

Страница 5: ...5mm2 HSU 24C03 V ZF Indoor unit Outdoor unit L 1 N 2 HSU 18H03 V ZXF HSU 22H03 V ZXF 1 Two ways for the installation of indoor part as illustrated Way One For all the models In the guard ring connect outlet joint with the fresh air tube Way Two Only for the models of 09 12 Insert the joint of water collecting pan into the fresh air tube then connect the other end of joint with mesh enclosure of wa...

Страница 6: ...d cause a leakage of gas Pipe Diameter Liquid side 6 35mm 1 4 Gas side 9 52mm 3 8 Fastening torque Drawing for the installation of indoor and outdoor units Insert the cable according to terminal number in the same manner as the indoor unit Fix the cable with a clamp 18N m 40N m Half union Flare nut Spanner Torque wrench 6 Gas side 12 7mm 1 2 50N m 6 Easily demount cleaning of indoor unit 1 Top inl...

Страница 7: ...nding piping air inside piping shall be removed by using external refrigerant gas charge according to the following list Brand new outdoor unit is charged 50g or 80g 22k 24k more refrigerant than regulated weight Only for first installation this extra 50g or 80g 22k 24k can be used to purge airin pipes During this procedure 50g or 80g 22k 24k refrigerant will be discharged in piping This must be s...

Страница 8: ...n pan of the indoor unit and confirm that drainage is carried out surely to outdoor In case that the attached drain hose is in a room please apply heat insulation to it without fail Please kindly explain to our customers how to operate through the instruction manual Gas leak from pipe connecting Heat insulation of pipe connecting Are the connecting wirings of indoor and outdoor firmly inserted to ...

Отзывы: