The distance between air duct outlet and air conditioner outlet is according to the length of
actually installed air duct and in service behavior of the static pressure terminal:  Installation
sketch map for long and short air duct is showed below, when connect to short air duct, using
low static terminal (terminal color is white), the distance between air duct outlet and air
conditioner outlet is no more than 0.5m; when connect to long air duct, using middle static
terminal (terminal color is red), the distance between air duct outlet and air conditioner outlet
could be within 5m at this point.

As figure shown, suspend and install the unit.

Drain piping of condensed water should keep a downhill grade of 1% or more. Use insulating
pipe to cover the drain piping of condensed water to keep warmth.

Figure 5

Figure 6

16

air return shutter

air return duct

sling dog

 drain piping

 transition
 air duct

air outlet

duct

air diffuser

 joint of air diffuser

M8 broad foundation bolt

M8 suspension screw

M8 broad lock ring

M8 nut

Unit

Installation for air duct of indoor unit

This type of unit uses circular air duct with its caliber of 180mm.
An additional transitive air duct is necessary for the circular air duct to connect to the air
supply inlet. It should be also connected to its respective air diffuser separately. See Fig.1.
Adjust the wind speed of each air diffuser outlet to keep in line on the whole, so as to meet a
demand of the air conditioner in the room.

1. Installation of air discharge duct

Indoor unit

  flexible  joint  or
static  pressurebox

 transitive air duct

circular air duct

joint of air diffuser

 air diffuser

Fig1: Duct connected

Instructions to installation

Все каталоги и инструкции здесь:

 http

:

//splitoff.ru/tehn-doc.html

Содержание AD092XLERA

Страница 1: ...ON INSTALLATION MANUAL AD092XLERA AD122XLERA AD142XLERA AD182XLERA R410A MULTI SPLIT SERIES ROOM AIR CONDITIONER No 0010577705 Please read this manual carefully before using this air conditioner Pleas...

Страница 2: ...afety precautions Notes for safety Parts and Functions Trouble shooting Customer Need to know When trouble happens Operation and Maintenance Failure code 1 2 3 5 6 7 8 9 10 11 12 23 24 25 http splitof...

Страница 3: ...fluorochlorichydrocarbon All th Consult your local authorities for the nameand address of the waste materialscollecting cente Safety Instructions and Warnings Before starting the air conditioner read...

Страница 4: ...pecifications The refrigerating circuit is leak proof The machine is adaptive in followingsituation 1 Applicable ambient temperature range 2 If the supply cord is damaged it must bereplaced by the man...

Страница 5: ...ay cause water leak electrical shock and fire hazard Don t put fingers or any other things into the inlet outlet and swing louver while theconditioner is in Because the highspeed fan is very dangerous...

Страница 6: ...use acci dents Pets and plants should not be blowed directly in the air flow Otherwise will suffer damage Don t operate the air conditioner with damp hands Otherwise will be shocked Only use correctly...

Страница 7: ...ating noise Air conditioner should be located in well vented and easily accessible place Air conditioner should not be located in thefollowing places a Places with machine oils or other oilva b Seasid...

Страница 8: ...e remote controller Never connect the earth wire with the gas pipe water pipe lightening arrester or phone line Never install the air conditioner where the flammable gas is easily leaked Do not spray...

Страница 9: ...Parts and Functions 7 INDOOR UNIT Electrical box Air inlet Drain pan Air outlet http splitoff ru tehn doc html...

Страница 10: ...rbed by indoor unit During operation white fog comes out of indoor unit When in COOL or DRY mode a thin water fog can be seen blown out of unit this is the condensed fog because the suddenly cooled in...

Страница 11: ...atically stops Water or vapor generated from the outdoor unit during heating This happens when the frost accumulated on the outdoor unit is removed during defrosting operation Defrosting operation Ple...

Страница 12: ...tallation please use the air conditioner according to the specification in the operation manual Using Directions Adjust suitable airflow direction Avoid direct sunlight and airflow Keep the proper ind...

Страница 13: ...he above mentioned items or when following phenomenon is observed stop the operation of the air conditioner and contact your sales dealer 1 The fuse or breaker often shuts down 2 Water drops off durin...

Страница 14: ...res Execute the installation accurately based on following the installation manual Again improper installations can result in water leakage electric shocks and fires When a large air conditioning syst...

Страница 15: ...angle 8 Pipe Expander Instructions to installation WARNING Its improper installation can also result in heat generation or fire When setting up or moving the location of the air conditioner do not mix...

Страница 16: ...unit shall be ensured to receive thesignal while t 1 Drill a hole in the wall and insert the connecting pipe and wire through a PVC wall through tube purchased locally The wall hole shall be with a o...

Страница 17: ...unit a specially designed return air bellows shall be installed as shown in Figure 3 Figure 4 Figure 3 Figure 4 A Installing building roof Ceiling Air supply Air outlet duct Unit Return air Return ai...

Страница 18: ...rain piping of condensed water to keep warmth Figure 5 Figure 6 16 air return shutter air return duct sling dog drain piping transition air duct air outlet duct air diffuser joint of air diffuser M8 b...

Страница 19: ...ulation layer is needed for air supply and return duct First paste a glue nail to the air duct and then attach the insulation cotton that has a tinfoil layer and use the glue nail cover to fix Finally...

Страница 20: ...ause indoor water leakage CAUTION Requirements The indoor drain pipe shall be thermal insulated The connection part between the drain pipe and the indoor uni The drain pipe shall be slant downwards gr...

Страница 21: ...pipe Drain confirmation During trial run check that there is no leakage at the pipe connection part during water draining even in winter 19 Rigid PVC pipe VP31 5mm internal diameter Pipe Foamed PE wit...

Страница 22: ...LERA AD182XLERA Flare connection Gas pipe 3 way valve Indoor Unit Outdoor unit Liquid pipe 2 way valve Flare connection A To outdoor unit To gas pipe A adaptor from 9 52 to 12 7 6 35 mm 1 4 0 8 1 5 9...

Страница 23: ...the address must be 3 Indoor unit that connect to valve D the address must be 4 2 Installation check and trial operation Check the Layout of the Drain Pipe and Connection Wires and also the piping an...

Страница 24: ...ss it through the end ring of connecting line then connect it to the terminal block and tighten screw Wiring methods Ring Terminal T B Brazed seam B 8 0 9 0 mm d 4 3 5 3 mm T 1 0 2 0 mm For your refer...

Страница 25: ...F 3G 2 5 mm2 POSSIBLE REASONS Faulty temperature sensor Tai 01 Sensor disconnected or broken or at wrong position or short circuit Faulty temperature sensor Tc1 Sensor disconnected or broken or at wro...

Страница 26: ...ver current of the system or broken of the current sensor or malfunction with indoor or outdoor fan motors or faulty PCB 15 16 17 14 19 System high pressureprotection High pressure switch is disconnec...

Страница 27: ...26 Faulty sensor Toci Sensor disconnected or broken or short circuit 2A Low voltage protection VDC 194V too low voltage from power source High voltage protection VDC 400V too high voltage from power...

Страница 28: ...ROUP Qingdao Haier Air Conditioner Electric Co Ltd Address Haier Garden Qianwangang Road Economic Development Zone Qingdao Shandong 266555 P R China Web Site http www haier com http splitoff ru tehn d...

Отзывы: