Domestic air conditioner
8.4.2.3 Indoor AC fan motor malfunction
Indoor Display E14
The rotation speed detected by the Hall IC during fan motor operation is used to determine
abnormal fan motor operation
when the detected rotation feedback signal don’t received in 2 minutes
■
Operation halt due to breaking of wire inside the fan motor.
■
Fan motor overheat protection
■
Operation halt due to breaking of the fan motor lead wires
■
Detection error due to faulty indoor unit PCB
* Caution Be sure to turn off power switch before connect or disconnect connector, or else parts
damage may be occurred.
Service diagnosis
17
Method of
Malfunction
Detection
Malfunction
Detection
Conditions
Supposed
Causes
Yes Troubleshooting
Check whether terminals
on indoor pcb is well?
Electrify the machine again and turn it on in the cooling operation,
Measure voltage between the positions 1and 3 of Terminal CN5 on
the indoor PCB
the voltage is about 90-220vac
check whether motor can run
when turn on the unit
the indoor motor is damaged and need replace
Yes
NO
NO
Yes
Measure whether there is voltage pulse(0-5VDC)
between the positions middle wire and black wire
of Terminal CN2 on the indoor PCB
NO
the indoor pcb is damaged and need replace
Pull out the terminals on the indoor
mainboard and reinsert them.
No
Yes
Is it ok?
Yes
Содержание 1U09DR4EAA
Страница 11: ...Piping diagrams Domestic air conditioner 3 Piping diagrams 9...
Страница 12: ...Operation range Domestic air conditioner 4 Operation range 10...
Страница 21: ...Performance Curves Diagram Domestic air conditioner 19 9 2 heating capacity temp curves...
Страница 22: ...Domestic air conditioner 20 9 3 Cooling power consumption temp curves Performance Curves Diagram...
Страница 23: ...Domestic air conditioner 9 4 heating power consumption temp curves 21 Performance Curves Diagram...