background image

1

1

7

7

 

 
Auxiliary Heat Differential:  This determines how far from the setpoint the temperature has to be before the 
auxiliary heat turns on.  This is only available for heat pump systems.   
 
Start Delay (Minutes): This item sets the minimum amount of time the heating system must run before the 
Auxiliary Heat Stage is used.  To use this start delay, EEC must be enabled and Hold must be off. 

 

EEC 

Settings 

Conventional (1 Cool / 1 Heat)

 

Heat Pump (1 Cool / 2 Heat) 

Dual Fuel Heat Pump (1 Cool / 2 Heat)

Heat EEC 

*5 

0 - 10 

Heat EEC 

*5 

0 - 10 

Cool EEC 

*5 

0 - 10 

Cool EEC 

*5 

0 - 10 

 

Aux Heat Differential 

*2 

1 - 10 

Start Delay (Minutes) 

*5 

0 - 4hr:15min 

 

Anticipator Control 
 

The Anticipator Control settings are used to “anticipate” the need to turn the system on or off before the 
temperature is actually at the setting.  As humans, we perceive temperature as a combination of heat in the air 
and heat radiated from the walls and surroundings.  The thermostat also measures a combination of air and wall 
temperature.  When heating, the air temperature rises faster than the wall temperature.  The thermostat will turn 
the heat off briefly to prevent overheating the air while the wall temperature catches up.   
 
When cooling, the thermostat will periodically run the cooling system to circulate the air and remove humidity 
when the temperature is close to, but not above the desired cool setting.   
 
Because of the PID algorithm and auto balance routine which monitors the performance of the HVAC system, 
the anticipator settings are automatic by default.  However, the anticipator settings may be adjusted if desired. 
 
Heat Anticipator: This adjusts the tendency of the thermostat to turn the heating unit off before the desired heat 
setting is reached.  This is done to avoid overheating the air while the walls and furniture catch up.  A setting of 
0-4 is intended for fast reacting heating systems, such as forced air.  A setting of 6-10 is intended for slow 
reacting heating systems, such as radiant heat.  A setting of 5 is used for automatic anticipation.   
 
A lower setting will decrease the tendency to turn off the heating system before the desired heat setting is 
reached.  If the heating system response time is slower, as are most radiant heating systems, a higher number 
will help maintain an even space temperature. 
 
Cool Anticipator: This adjusts the tendency of the HVAC to run the cooling system to refresh and dehumidify 
the air before the temperature rises to the desired cool settings.  A setting of 0-4 is intended for more humid 
climates and will increase the tendency for the cooling system to turn on to refresh and dehumidify the air.  A 
setting of 6-10 is intended for dry climates and will decrease the tendency to run the cooling system below the 
cooling setting.  A setting of 5 is used for automatic anticipation. 
 
2

nd

/3

rd

 Stage Extended On: When enabled and if any 2

nd

 or 3

rd

 stage turns on, it will remain on until the 

heat/cool is satisfied, regardless of the settings for any stage differentials.  The default setting is off. 
 

Cool Anticipator 

*5 

Heat Anticipator 

*5 

2

nd

/3

rd

 Stage Extended On 

*Off 

Содержание RC-1000

Страница 1: ...s must be observed for installation in Europe CE 1 This equipment must be installed in accordance with National wiring rules for the country in which it is installed 2 All product labels instructions...

Страница 2: ...Removing an existing thermostat 1 Disconnect the power to the control transformer 2 Remove the cover to the existing thermostat 3 Disconnect the wires going to each terminal on the thermostat Label ea...

Страница 3: ...iagram for the application See Figures 8 11 Upon completion of wiring the thermostat push all excess wiring into the hole in the wall Plug the hole with the supplied insulating foam to ensure an accur...

Страница 4: ...must remain in place Figure 4 Thermostat power up for test or configuration purposes Important Notes 1 For HVAC systems with a single transformer for heating and cooling the metal jumper between Term...

Страница 5: ...onfiguration steps under the wiring diagram for the respective HVAC system type 7 If the thermostat or HVAC system does not perform as stated in the Power Up steps under the wiring diagram for the res...

Страница 6: ...res or wire strands at the connections 2 Connect power to the transformer and system The display will show the current thermostat settings 3 Press FAN and select On The fan should come on 4 Press FAN...

Страница 7: ...re A temperature sensor can be physically connected to the Remote Temp Sensor terminals on the thermostat or the RC 1000 can obtain the outdoor temperature from a remote system If the RC 1000 can not...

Страница 8: ...d system The display will show all of the thermostat settings 3 Press FAN and select On The fan should come on 4 Press FAN and select Auto The fan should go off 5 Press HOLD and select On to override...

Страница 9: ...m schedules SETTING THE COMMUNICATIONS JUMPER This thermostat comes from the factory with the communications jumper J8 labeled COMM JUMPER on the thermostat printed circuit board installed See Figure...

Страница 10: ...ound Zone 16 and Output 8 See Figure 9 THERMOSTAT CONTROLLER Black Green Yellow UP Communication Jumper Figure 9 Connections to HAI Home Control System Notes 1 Additional thermostats are connected in...

Страница 11: ...Comm on the right terminal strip See Figure 10 UP Green Black THERMOSTAT ANY SYSTEM WITH A RELAY OR 5 15 VDC OUTPUT 5 15 VDC Communication Jumper Figure 10 Connections to a Remote Setback Switch Notes...

Страница 12: ...ed pair with foam polyethylene insulated conductors shielded must be used Wire runs must not exceed 250 feet Make the connections to the Green and Black terminals under the section marked Remote Temp...

Страница 13: ...ns and Scroll Wheel 1 Remove the thermostat face from the thermostat base 2 Remove the local control jumper See Figure 12 3 Align the tabs of the thermostat face with the slots of the thermostat base...

Страница 14: ...gs 6 Read the warning and then press Continue to proceed 7 To exit Setup mode press Back several times until the Home Page is displayed Notes 1 The thermostat will automatically default to the Home Pa...

Страница 15: ...e method for scheduling temperature change commands Program Mode Schedule Program setpoints are based on time of day and day of week None The internal program schedule is disabled Use this when connec...

Страница 16: ...ng again Raising this number will increase the total time that the heating system is off saving energy but may allow the temperature to drift farther from the setpoint decreasing comfort When combined...

Страница 17: ...ance of the HVAC system the anticipator settings are automatic by default However the anticipator settings may be adjusted if desired Heat Anticipator This adjusts the tendency of the thermostat to tu...

Страница 18: ...ry heat is used in a dual fuel heat pump system If the outdoor temperature is above the Upper Balance Setpoint 45 F by default the heat pump is used exclusively If the outdoor temperature falls below...

Страница 19: ...hermostat and the remote system are set to the proper configurations for communication SYMPTOM ACTION TO TAKE Temperature Reading Incorrect 1 Allow 30 minutes for thermostat to adjust 2 Adjust calibra...

Страница 20: ...medies thereof In no event shall HAI be liable for incidental expenses or consequential loss or damages For the complete HAI Warranty for USA policy see the HAI web site at www homeauto com Any implie...

Отзывы: